4. Fucntion
1) Main power input - operation
(1) Version and Segment ( from 0 ~ 9 ) counts up by 0.3 seconds
when Power Supply inputs.
(2) LED blinks successively.
(3) The final operation indication appears after a self-inspection.
2) Mode and time setting
(1) Press "Delay + Open" key simultaneously to make setting menu
change during operation.
①
"SET" appears in Delay Segment.
②
Time unit appears in Open Segment
(2) Press the manual output key to make MODE change.
(Mode A>B>C>A)
(3) Press
▲
UP key to make Press Up key to make Time unit change
below decimal point. (0.01> 0.1> 1> 0.01)
(4)
▼
Down key is to down the value.
(5) The value is saved if there is no response for 3 seconds.
(6) All Input & Output operation are not available during setting time.
3) Time setting
(1) Delay time setting.
①
Press Delay key to make value change,
then use
▲
UP and
▼
DOWN key.
②
To make the first Delay time setting in MODE C,
follow
①
instruction during "A" kept in display.
③
To make the second Delay time setting in MODE C,
follow
①
instruction during "p" kept in display.
④
Delay time setting is available all in MODE A, B, C.
⑤
The value is saved, unless there is any response for 3 seconds.
⑥
Manual operation can be done under Open key input during
the set time.
⑦
Continual input is available under UP/DOWN key being pressed.
⑧
If saved as 999 sec in 1 sec. setting, 99.9 sec. is displayed
in 0.1 sec. setting. ( 9.99 sec. is displayed in 0.01 sec. setting )
-The saved value is converted by multiple value )
1 Sec setting 0.1 Sec setting 0.01 Sec setting
Setting range 0 - 999 Sec 0 - 99.9 Sec 0 - 9.99 Sec
(2) Open time adjustment
①
Press Open key to make value change,
then use
▲
UP and
▼
DOWN key.
②
To make the first Open time setting in MODE C,
follow
①
instruction during "A" kept in display.
③
To make the second Open time setting in MODE C,
follow
①
instruction during "p" kept in display.
④
Open time setting is available only in MODE B, C.
(3) How to set Solenoid output Voltage
Disassemble TW600 blank panel under Power supply turn off.
After remove M4 x 5mm bolt, connect blank panel power B/D's
connector to jumper cable that needed(J8(DC24V Hydraulic),
J3(DC24V Pneumatic), J1(AC110V, AC220V)).
(Factory setting : AC220V)
* Output Voltage must be same with Solenoid Valve Input Voltage in mold.
( Unless, it causes malfunction in operation)
*Note : Sequence timer controller Unit card is interchangeable without regard
for Pneumatic or Hydraulic, but the Controller case has to be fit in
according to a type.
SEQUENCE INJECTION TIMER
SEQUENCE INJECTION TIMER
5
6
*AC 110V
or
AC 220V
(Hydraulic /
Pneumatic)
*DC 24V
(Hydraulic)
*DC 24V
(Pneumatic)
>
>