7
Wiring diagram of D2 size instruments (48×48mm)
1: D2 size instruments don not support native 0
~
5V or 1
~
5V linear voltage input. The workaround
is done by voltage divider into 0
~
500mV or 100
~
500mV. External precise resistor 25ohm can be
parallel shunt to convert 4
~
20mA to 100
~
500mV
then input from terminals 9 and 8.
2: For COMM/AUX slot,
installing S or S4 communication module provides
communication, installing L2 module provides AU1
alarm output,
installing L2 module provides AU1 alarm output,
installing L3 dual relay module (with parameter bAud=0) provides AU1 and AU2 alarm output,
installing L3 (with parameter bAud=2) provides AU1 and AL1 alarm output,
installing I2 module (with parameter bAud=1) provides MIO on-off input simulation SP1/SP2. The external switch should
be connected to terminal 3 and 5.
Wiring diagram of D6 size instruments (48×48mm)
1: Linear voltage of 500mV below input from
terminal 10, 11. 0
~
5V or 1
~
5V linear voltage
input from terminal 9 and 10.
2: External precise resistor 250ohm can be
parallel shunt to convert 4
~
20mA to 1
~
5V
then input from terminals 9 and 10.
3: For COMM/AUX slot, installing S or S4
communication
module
provides
communication,
installing L2 module provides AU1 alarm
output,
installing L3 dual relay module (with parameter
bAud=0) provides AU1 and AU2 alarm output,
installing SL module provides RS485 communication and AU1 alarm output.
1
2
3
4
5
6
7
9
10
8
COM
N/O
+
100-240VAC~
AU1
COMM/AUX
AU2
A
B
COM
COM
N/O
N/C
N/O
N/O
+
G1
G2
Thyristor trigger output
(
K1
)
OUTP
TXD
RXD
GND
Thyristor trigger output (K1)