Wiring diagram of D2 size instruments (48×48mm) 

1: D2 size instruments don not support native 0

5V or 1

5V linear voltage input. The workaround 

is done by voltage divider into 0

500mV or 100

500mV. External precise resistor 25ohm can be 

parallel shunt to convert 4

20mA to 100

500mV 

then input from terminals 9 and 8. 

2: For COMM/AUX slot,   

installing S or S4 communication module  provides 

communication, installing L2 module provides AU1 

alarm output,   

installing L2 module provides AU1 alarm output, 

installing L3 dual relay module (with parameter bAud=0) provides AU1 and AU2 alarm output,   

installing L3 (with parameter bAud=2) provides AU1 and AL1 alarm output,   

installing I2 module (with parameter bAud=1) provides MIO on-off input simulation SP1/SP2. The external switch should 

be connected to terminal 3 and 5. 

 

Wiring diagram of D6 size instruments (48×48mm) 

 

1: Linear voltage of 500mV below input from 

terminal 10, 11. 0

5V or 1

5V linear voltage 

input from terminal 9 and 10. 

2: External precise resistor 250ohm can be 

parallel shunt to convert 4

20mA to 1

5V 

then input from terminals 9 and 10. 

3:  For  COMM/AUX  slot,  installing  S  or  S4 

communication 

module 

provides 

communication,   

installing  L2  module  provides  AU1  alarm 

output,   

installing L3 dual relay module (with parameter 

bAud=0) provides AU1 and AU2 alarm output,   

installing SL module provides RS485 communication and AU1 alarm output. 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

9

 

10

 

8

 

COM 

 

N/O 

 

 

+

 

100-240VAC~

 

AU1

 

COMM/AUX 

AU2

 

A

 

B

 

COM

 

 

COM 

 

N/O 

 

 

N/C 

 

N/O 

 

 

N/O 

 

 

+

 

G1 

 

 

G2 

 

 

Thyristor trigger output

K1

 

 

 

OUTP 

TXD

 

RXD

 

GND

 

Thyristor trigger output (K1) 

Summary of Contents for AI-519

Page 1: ...ls of temperature pressure flow level humidity etc CONTENTS 1 SUMMARY 1 1 1 MAIN FEATURES 1 1 2 ORDERING CODE DEFINITION 1 1 3 TECHNICAL SPECIFICATION 4 1 4 REAR TERMINAL LAYOUT AND WIRING 6 2 DISPLAY...

Page 2: ...nge of temperature ISO9001 and CE certified achieving world class level of quality anti interference ability and safety POINTS TO NOTE Always adjust parameters according to input output type and funct...

Page 3: ...output or SV PV retransmission L1 Large capacity large size normal open relay output module Capacity 250VAC 2A L2 Small capacity small size normal open normal close relay output module Capacity 250VA...

Page 4: ...ace or install modules by themselves when needed When replacing a module you should pull the controller out of the housing at first insert a small flat tip screwdriver into the opening between the ori...

Page 5: ...can be chosen Calibration The instrument applies the technology of automatic zero and digital calibration and is free of maintenance If the error exceeds certain range generally cleaning and drying t...

Page 6: ...power module Linear current output 0 20mA or 4 20mA Output voltage 11V maximum load resistance 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV a...

Page 7: ...ignal can be converted to 1 5V voltage signal by connecting a 250 ohm resistor and input from terminals 11 and 12 3 S S1 or S4 module can be installed in COMM slot for communication If relay TRIAC no...

Page 8: ...odule with parameter bAud 1 provides MIO on off input simulation SP1 SP2 The external switch should be connected to terminal 3 and 5 Wiring diagram of D6 size instruments 48 48mm 1 Linear voltage of 5...

Page 9: ...struments 22 5 x 100mm 1 Input 0 5V 1 5V input from 12 11 500mV below input from 10 11 4 20mA with 250ohm shunt resistor converted to 1 5V input from 12 11 2 Fixed with one channel alarm and communica...

Page 10: ...N4001 Load Thyristor trigger output SCR X2 5 500A BX BX Capacitor Resistor Absorber Circuit Varistor G1 G2 G1 G2 ZNR ZNR V V 100 240VAC TRIAC 5 500A Capacitor Resistor Absorber Circuit Varistor SCR Po...

Page 11: ...the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or the low limit of PV and the instrument will aut...

Page 12: ...password and then press can access System Parameter Table Setpoint Output Magnitude Switch In the basic display status pressing can switch lower display window between displaying setpoint or output m...

Page 13: ...Generally the smaller the value of CHYS the higher is the precision of auto tuning But the value of CHYS parameter should be large enough to prevent the instrument from error action around setpoint du...

Page 14: ...utput PV The instrument works as a temperature retransmitter SOP output SV The instrument works as a set current output onoF APId nPId POP SOP Act Acting method rE Reverse acting Increase in measured...

Page 15: ...t value or corresponding parameter value may be larger than 9999 please avoid choosing 0 but 0 000 instead The display value will become 00 00 when the value is larger than 9999 0 0 0 0 00 0 000 ScL S...

Page 16: ...he impulse current of induction load CtI 0 5 second and OPrt 5 second 0 3600 second OEF Work range of OPH When PV OEF the upper limit of OUTP is OPL when PV OEF the upper limit of OUTP is 100 For exam...

Page 17: ...tion are satisfied the instrument should alarm but there is no problem in the system Contrarily in an refrigerating system the unnecessary high limit or deviation high limit alarm may occur at the beg...

Reviews: