2
B
front panel 160
×
80mm(width
×
height), cut out 152
+0.5
×
76
+0.5
mm, depth behind mounting surface 100mm.
C
front panel 80
×
160mm(width
×
height), cut out 76
+0.5
×
152
+0.5
mm, depth behind mounting surface 100mm.
C3
On top of C, there is additional light bar with 50 segments and 2 levels of luminosity.
D
front panel 72
×
72mm(width
×
height), cut out 68
+0.5
×
68
+0.5
mm, depth behind mounting surface 95mm
D2
front panel 48
×
48mm(width
×
height), cut out 45
+0.5
×
45
+0.5
mm, depth behind mounting surface 95mm, with 10
terminals
D5
width 22.5mm, DIN-Rail mount, external keypad E8 (or communication if address/BAUD rate is correct)
required for display and parameter setting
D6
front panel 48
×
48mm(width
×
height), cut out 45
+0.5
×
45
+0.5
mm, depth behind mounting surface 95mm, with 12
terminals
E
front panel 48
×
96mm(width
×
height), cut out 45
+0.5
×
92
+0.5
mm, depth behind mounting surface 100mm
E2
On top of E, there is additional light bar with 25 segments and 4 levels of luminosity.
E5
48
×
96mm(width
×
height), DIN-Rail mount, external keypad E8 (or communication if address/BAUD rate is
correct)) required for display and parameter setting
F
front panel 96
×
48mm(width
×
height), cut out 92
+0.5
×
45
+0.5
mm, depth behind mounting surface 100mm
③
Module type of multiple function I/O (MIO). N means none, no module installed.
I2
Single channel on-off signal input module. When a n external switch is connected, SV=SP1 When the switch is
open; SV=SP2 when the switch is closed.
I4
4~20mA/0~20mA analogue input module, with 24VDC power supply. Directly connecting to 2-wire transmitter.
V24/V12/V10
Isolated 24V/12V/10V DC voltage output module with maximum current of 50mA, supplying power
for external transmitter.
④
Module type of main output (OUTP). For control output or SV/PV retransmission.
L1
Large capacity, large size, normal open relay output module (Capacity: 250VAC/2A)
L2
Small capacity, small size, normal open + normal close relay output module (Capacity: 250VAC/1A
recommended for alarm)
L4
Large capacity, small size, normal open + normal close relay output module (Capacity: 250VAC/2A)
K1
“Burnt-proof” single-phase thyristor zero crossing trigger output module, trigger
ing
one loop of a TRIAC or a pair
of inverse parallel SCR with current of 5~500A.
K3
“Burnt-proof” three-phase thyristor zero crossing trigger output module, triggering 3-phase circuit. Each loop
can trigger TRIAC or a pair of inverse parallel SCR with current of 5~500A.
K5
“Burnt-proof” single-phase thyristor phase-shift trigger output module, suitable for 200
~
240VAC power grid.
K6
“Burnt-proof” single-phase thyristor phase-shift trigger output module, suitable for non-standard power
environment below 380VAC.
X3
Photo-electric isolated linear current output module, 0~20mA or 4~20mA, occupying internal 12VDC power.
X5
Photo-electric isolated linear current output module, 0~20mA or 4-20mA. Equipped with isolated power supply
without occupying internal 12VDC power.
W1
TRIAC no contact normal open discrete output module (Capacity: 100~240VAC/0.2A, burnt-proof)
W2
TRIAC no contact normal closed discrete output module (Capacity: 100~240VAC/0.2A, burnt -proof)
G
Solid-state relay, SSR voltage output module (DC12VDC/30mA)
⑤
Module type of alarm (ALM). For AL1 and AL2 alarm outputs.
L0
Large capacity, large size, normal open relay output module (Capacity: 250VAC/2A, recommended for alarm)
L0/L2/L4
Single relay output alarm, support AL1 one channel alarm
L3
Dual normal open relay output module, support AL1 and AL2 alarm
⑥
Module type of auxiliary output (AUX). For AU1 and AU2 alarms and control auxiliary output.
L0/L1/L2/L4
Single relay output alarm
L3
Dual normal open relay output module, support AL1 and AL2 alarm