41
EP1
~
EP8
Field
parameter
definition
1 to 8 field parameters can be defined by parameters EP1to EP8. If the number of
the field parameters is less than 8, the first idle EP parameter should be set to “nonE”.
The initial values of EPs and Loc are EP1=HIAL, EP2=LoAL, EP3=HdAL, EP4=LdAL,
EP5=nonE, EP6=nonE, EP7=nonE, EP8=nonE and Loc=0.
You can redefine field parameters and Loc to change operation style. For example,
you can execute auto tuning from field parameter instead of by pressing
in basic
display status, and only take HIAL and HdAL as field parameter. The EP paramters
and Loc should be set as below:
EP1=HIAL, EP2=dHAL, EP3=At, EP4=nonE, Loc=1
nonE and all
parameter
codes