32
installed in OUTP.
oP1.A=1,
0
~
10mA linear current output. Linear current output module should be
installed to main output.
oP1.A=2,
0
~
20mA linear current output. Linear current output module should be
installed to main output.
oP1.A=3,
spare
oP1.A=4,
4~20mA linear current output. Linear current output module should be
installed to main output.
oP1.A=5
~
7,
No applicable in AI-518.
oP1.A=8,
single channel phase-shift output. K5 module should be installed.
In this mode, AUX can not work as refrigerating output.
oP1.B shows the AUX output type. It works only when parameter oPL<0.
oP1.B=0
, time proportional output. Output modules such as SSR voltage
output, relay contact discrete output, thyristor cross zero trigger output, and TRIAC
no-contact discrete output can be installed in OUTP.
oP1.B=1,
0
~
10mA linear current output. Linear current output module should be
installed to main output.
oP1.B=2,
0
~
20mA linear current output. Linear current output module should be
installed to main output.