![Yuasa NP Series Installation Use & Care Instructions Download Page 6](http://html1.mh-extra.com/html/yuasa/np-series/np-series_installation-use-and-care-instructions_3656612006.webp)
6
Write a description of any problems noted on the delivery slip before signing. If
the batteries or accessories (stand or rack, cabinet, case, connectors and so on)
have been damaged, ask the driver to witness the damage and immediately inform
the carrier that the delivery has been refused.
All batteries with damaged terminals, damaged cases or any trace of leaked
acid must be replaced.
3-2/ BATTERIES DELIVERED IN CABINETS
On reception, unwrap the cabinet.
Visually verify the condition of the cabinet and the batteries on both the
outside and the inside.
It is advised to check the terminal tightening with an isolated torque key to
avoid all loosening during transportation. To limit this risk we advise to use flexible
inter batteries connectors.
Warning: dangerous voltage levels may be present
Remove any hopping and fixing of the batteries before start up.
Space the
batteries to facilitate ventilation if possible.
Anything that does not conform must be informed in writing to YUASA’s
logistics department.
4/ STORAGE BEFORE INSTALLATION
4-1/ STORAGE SITE
If the battery is not installed and recharged immediately after delivery, it is
recommended that it be stored inside, in a clean, dry place at an ambient
temperature (15°C to 30°C).
Do not stack more than 2 pallets of batteries.
All batteries stored at temperatures of more than 30°C will have to be
recharged more quickly. (
See the TECHNICAL MANUAL corresponding to the type
of battery
).
4-2/ STORAGE DURATION
Summary of Contents for NP Series