12-8/ A FEW POSSIBLE EXPLANATIONS, OTHER THAN A BATTERY PROBLEM,
FOR WHEN THE AUTONOMY IS NOT ACHIVED
a/ Temperature too low in relation to the data.
b/ Battery power higher than in the data.
c/ Significant voltage drop in the cables between the battery and the UPS.
d/ Battery not 100% charged.
e/ Cut-off voltage too high in relation to the data.
f/ The UPS stops before it reaches the cut-off voltage (through a delay, for example).
g/ Loss of a string (loosened terminal).