7.2.2 And then the appropriate position of the meter box or insulating partition to determine
a point, screw on the matching self-tapping screws, and the meter hanging, and then the
meter below the two anchor points with self-tapping screws.
7.2.3 Connect according to the meter wiring diagram wiring.
7.2.4 If wiring is completed, according to the need to seal the lead side of the meter live live,
screw the top cover.
Recommended use of wire (for reference):
Rubber or plastic insulated wire Safe carrying capacity (1)
specificatio
n
(
mm
)
Nominal
section
(
mm2
)
Safe carrying capacity
(
A
)
BX
BL
X
BV
BL
V
1*1.13
1
20
18
1*1.37
1.5
25
22
1*1.76
2.5
33
25
30
23
1*2.24
4
42
33
40
30
1*2.73
6
55
42
50
40
7*1.33
10
80
55
75
55
7*1.76
16
105
80
10
0
75
7*2.12
25
140
10
5
13
0
10
0
7*2.50
35
170
14
0
16
0
12
5
19*1.83
50
225
17
0
20
5
15
0
19*2.14
75
280
22
5
25
5
18
5
19*2.50
95
340
28
0
32
0
24
0
Note
:
BX(BLX
)
copper
(
aluminum
)
core rubber insulated wire or BV(BLV
)
copper
(
aluminum
)
core PVC plastic insulated wire
,
widely used in 500V or less than 500V AC
and DC power distribution system. The temperature for the data listed in the above table is
35
℃
、
the safe carrying capacity value for the wire on single covered.