background image

 

 

Electro-Pneumatic Positioner   YT-1000L  Installation manual 

 

 

(3) Attach YT-1000L (with bracket) to the actuator yoke - DO NOT TIGHTEN COMPLETELY.   

(4) Connect YT-1000L feedback lever to the actuator clamp.  The gap on the YT-1000L feedback 

lever is 6.5mm.  The connection bar thickness should be less than 6.3mm.  <Figure 3>  

 

 

 

 

 

 

 

 

 

 

<Figure 3>

  

 

(5) Connect air filter regulator to the actuator temporarily.  Set supply pressure of the regulator in 

order to position the actuator clamp at 50% of valve stroke. <Figure 4>  

 

 

 

 

 

 

 

 

 

 

<Figure 4>

  

(6) Insert connection bar into the YT-1000L feedback lever.  The connection bar should be inserted 

at the 50% point on the feedback lever, which would help to reduce hysteresis. <Figure 5>                 

 

 

 

 

 

 

 

<Figure 5>

  

Young Tech Co.  #662-8 PumgMu Dong, Kimpo City, (415-809) Korea  (031) 986-4935   www.ytc.co.kr

 

Reviews: