6. Troubleshooting 

1)  SPTM-5V shows no output signal.   

A. 

Check actual input signal to SPTM-5V. 

 

B. 

Check power connection and + / - poles. 

 

2)  Input signal value to the positioner and output signal value from SPTM-5V differs 

dramatically.   

A. 

Check input signal value and supply voltage.    Insufficient voltage can affect input signal 

value. 

 

B. 

Check the installation of the positioner.    If the positioner is installed improperly, please 

refer to the positioner’s manual and re-install the positioner. 

 

C. 

Set the positioner’s zero and span.  Inaccurate zero and span setting can lower the 

accuracy and linearity.

 

D. 

Check the installation of the position transmitter.  If SPTM-5V is installed improperly, 

then refer to the manual and re-install. 

 

3)  Sudden changes in SPTM-5V’s output signal value.   

A. 

Please make sure that SPTM-5V’s lever is placed at 50% point.  If not, SPTM-5V 

needs to be re-installed and adjusted to be placed at the 50% point. 

 

B. 

Adjust the potentiometer.  Potentiometer’s load resistance is 10K

, and it should be 

ready at the 50% point. 

 

 

Summary of Contents for SPTM-5V Series

Page 1: ...Smart Position Transmitter PRODUCT MANUAL SPTM 5V SERIES VERSION 1 01...

Page 2: ...tions 4 2 3 Label Description 4 2 4 Product Number 5 2 5 Product Specification 5 2 6 Parts and Assembly 6 2 7 Dimension SPTM 5VL 7 2 8 Dimension SPTM 5VR 7 3 Installation 8 3 1 Safety 8 3 2 SPTM 5VL I...

Page 3: ...ponsible for any damages caused by user s negligence Manufacturer will not be responsible for any damages or accidents as a result of any alteration or modification of the product and its parts If any...

Page 4: ...uilt micro processor which transmits DC 4 20mA signal according to changes in valve or damper position 2 2 Main Features and Functions Designed to be Ex ia IIC T6 explosion proof grades Economical pri...

Page 5: ...Signal 4 20mA DC Load Resistance Max 600 28V DC Supply Voltage 9 28V DC Noise Range 50mV p p Conduit Entry PF 1 2 G 1 2 Enclosure IP 67 Explosion Proof Ex ia IIC T6 KCs Ambient Temp Operating 40 C 85...

Page 6: ...6 SPTM 5V series 2 6 Parts and Assembly...

Page 7: ...7 SPTM 5V series 2 7 Dimension SPTM 5VL 2 8 Dimension SPTM 5VR...

Page 8: ...f the valve stroke Feedback lever connection with the pin of the actuator clamp should be installed in such a way that the valve stroke length coincides with the corresponding figure of mm marked on t...

Page 9: ...he connection pin at the number on the feedback lever which corresponds to the desired valve stroke To adjust mover the bracket or the connection pin or both 9 After installing the SPTM 5v operate the...

Page 10: ...ing type rug to protect against vibration or any other external impact Please use twisted cable with conductor section are 1 25mm2 and that is suitable for 600V complying to the conductor table of NEC...

Page 11: ...to output 12mA signal when the feedback lever is at 50 position In case of dislocation of the potentiometer please follow below procedure to re set the potentiometer Power must be turned off before ad...

Page 12: ...talled improperly please refer to the positioner s manual and re install the positioner C Set the positioner s zero and span Inaccurate zero and span setting can lower the accuracy and linearity D Che...

Page 13: ...eries Manufacturer Young Tech Co Ltd 3022 Hagun ri Yangchon myeon Kimpo si Kyeonggi do 415 843 South Korea Tel 82 31 986 8545 Fax 82 31 986 2683 Email ytc ytc co kr Copyright Young Tech Co Ltd All Rig...

Reviews: