34
9.
The ProSample will request a
Deadband
be entered.
If a High Setpoint is entered, Deadband is the value which the
mA signal must drop below before sampling no longer occurs.
As an example, if 10 mA is the High Setpoint and a Deadband
of 0.5 is entered, the mA signal must drop below 9.5 mA before
sampling no longer occurs.
If a Low Setpoint is entered, Deadband is the value which the
mA signal must rise above before sampling no longer occurs.
As an example, if 5 mA is the Low Setpoint and a Deadband
of 0.5 is entered, the mA signal must rise above 5.5 mA before
sampling no longer occurs.
10. Trigger Channel 1
will be displayed. Highlight
Event
and press
the Enter key.
11.
Go back to the
Main Menu
by pressing the Back key a few
times.
12. Select Programs
g
Change
. Choose the program you would
like to modify by using the left and right arrow keys. In this
example, we will modify Program # 1. Press the Enter key to
begin modifying the program.
13.
Highlight
Event Time
and press the Enter key.
Programming: Analog Input Trigger