background image

5

                                            ■

EPDT-049a

 

 

7. Maintenance 

 

7.1 Precaution for installation 

          Caution 

1.  When installing, check the direction of the product so that the fluid flowing and the arrow marked on 

the product are in the same direction. 
* Setting the product in wrong directions prevents the product from performing as intended. 

2.  When installing, secure the space to remove the screen. 

* Failure to follow this notice hampers cleaning of the screen.   

3.  Do not apply excessive load, torque or vibration to the product. 

* Failure to follow this notice may result in fluid leakage. 

 

4.  Clogging inside the product can be known from the differential pressure measured, when pressure 

gauges are installed in upstream and downstream of the product.   
[See Fig. 1 in “9. Piping Example.”] 

5.  The product shall be installed with its cover faced downward.   

* If drainage or similar problem occurs in a steam line, incline the product to the position at which the 
cover is kept horizontally. 

6.  If the product can only be installed to run the fluid from the bottom to the top, make sure to install a 

blow valve in order to remove the scale accumulated at the bottom of the riser pipe. 
[See Fig. 2 in “9. Piping Example.”] 

 
 

7.2 Precaution for operation 

          Warning 

1.  When the product is used for hot fluid, do not touch the product with bare hands. 

* Failure to follow this notice may result in scalds or injury. 

2.  Do not retighten the cover after leading fluid into the product. 

* Failure to follow this notice may damage the gasket and cause outside leakage.   
* Failure to follow this notice may result in scalds or injury. 

 

           

Caution 

Use  the  product  under  a  maximum  pressure  loss  below  0.1  MPa.    Periodically 
clean the screen. 
* Failure to follow this notice may damage the screen.

 

 

 

Summary of Contents for SY-10 Series

Page 1: ...erious injury Caution This symbol indicates a hazardous situation that if not avoided may result in minor or moderate injury or may result in only property damage Table of Contents 1 Overview 1 2 Feat...

Page 2: ...ss 150 300 flanged as standard specifications 2 The standard product has a stainless steel screen of 80 mesh with perforation 3 Specifications Model SY 10 10 SY 10 20 SY 10 30 SY 10 150 SY 10 300 Appl...

Page 3: ...165 56 120 R 1 2 50A 275 170 56 120 R 1 2 65A 300 185 73 125 R 1 2 65A 310 188 73 125 R 1 2 80A 320 210 88 145 R 1 2 80A 345 215 88 145 R 1 2 100A 380 270 108 200 R 1 2 100A 395 275 108 200 R 1 2 125A...

Page 4: ...reases to generate disturbances possibly resulting in pipe wear noise and or vibration If the nominal pipe size is too large not only the costs of piping and equipment but also the thermal loss increa...

Page 5: ...4 EPDT 049a 6 3 Pressure Loss Chart Model SY 10 Strainer Screen 6 8P perforations with 80 mesh filter Nominal size P Pressure loss MPa V Flow rate L min...

Page 6: ...ct shall be installed with its cover faced downward If drainage or similar problem occurs in a steam line incline the product to the position at which the cover is kept horizontally 6 If the product c...

Page 7: ...to the residual pressure 2 After checking the pressure gauge to make certain there is no pressure inside the body 1 remove the cover 2 and screen 3 Clean up the screen 3 by compressed air or water 8...

Page 8: ...improvement without any prior notice After the discontinuation of the product Yoshitake supplies the repair parts for 5 years otherwise individually agreed 3 This warranty does not cover the damage d...