EPDT-072j

 

Caution 

1.    Before installing the product, remove foreign substances and scale from the piping. 

* Failure to follow this notice may hamper proper operation. 

2.    When  installing  the  product,  match  the  direction  of  fluid  flow  with  the  inlet  and  outlet  of  the 

product respectively. 

* Failure to follow this notice prevents the product from functioning properly. 

3.    Please  do  pipe  properly  that  is  not  given  the  excessive  load,  bending  and  vibration  to  the 

product. 

* There is a possibility of the malfunction, and the life time of the product is significantly shorter. 

4.    Inner  diameter  of  pipe  mount  and  exhaust  pipe  must  be  equal  to  or  more  than  those  of  each 

inlet and outlet of the product. 

* Failure to follow this notice may result in malfunction or insufficient amount of blowout. 

5.    There is no problem with this product becoming wet by rain water. However, if this product gets 

wetted by water all time, consider installation place to keep from water. 

6.    Connect the product to the pipes securely. 

* Improper connecting may cause fluid leakage from the piping joint when vibration is applied, or 

may cause scalds in case that fluid is hot. 

7.    Lead exhaust pipe to outside of buildings if there is a risk that fluid blowout causes alarm activation 

or contamination of the peripheral equipment. 

* Improper placement may cause contamination of the peripheral equipment. 

8.    If there is a risk that condensate or rain water accumulates in exhaust pipe, attach drain pipe with 

the product and/or the exhaust pipe in a position where they can be drained.   

* Failure to follow this notice may cause rust and result in malfunction. 

9.    Do  not  conduct  piping  with  dissimilar  metal  provoking  potential  difference.  Failure  to  follow  this 

instruction result in galvanic corrosion of this product or parts. 

10.    Pipe  mount  of  safety  valve  should  have  sufficient  strength  and  rigidity  against

 

compression, 

shear stress and bending stress caused by reaction force because the pipe amount is subject to 

the reaction which is caused along the center line of a blowout pipe connected to the safety valve 

in the direction contrary to the discharging direction. 

11.    Please  install  the  safety  valve  whose  valve  spindle  shaft  is  vertically,  and  it  should  be  mounted 

directly to the vessel as much as possible. In addition, please install it to the place where can do 

maintenance and inspection easily. 

12.    When  installing  an  exhaust  pipe,  the  inner  diameter  of  an  exhaust  pipe  should  be  as  larger 

possible than that of an outlet pipe of a safety valve and not to have an undue back pressure (It 

does not exceed 10% of the blowout pressure).

 

 