Yoshitake AF-5 Product Manual Download Page 4

-3- 

EPDT-072j

 

 

4

Operation

 

 

(1) 

Blowout operation 

As  inlet  pressure  approaches  the  blowout  pressure,  the  force  of  fluid  pushing  up  the  valve  [5] 
approaches the force of the spring [9] pressing down the valve. The safety valve commences to 
blow when the inlet pressure reaches around 3% below the blowout pressure. 
The fluid starts to leak by simmering and accumulates gradually on the valve holder 

A

. When the 

fluid pressure reaches the blowout pressure the valve pops. 
 

(2) Closing operation 

Since  the  inlet  pressure  of  the  safety  valve  decreases  when  the  fluid  is  released  into  the 
atmosphere  by  the  pop  action  of  the valve  [5],  the  force  of fluid  lift is  lowered.  At this point,  the 
repelling force of the spring [9] becomes larger than the force of fluid lift and thus the valve closes. 
In addition, since the safety valve blows, the pressure of fluid entering into the back of the valve 
holder (back pressure) adds to the closing force. 
 

(3) Lift lever mechanism

 

Warning 

1.   

Do not touch the product/pipes or the lever [14] with bare hands. 

* Failure to follow this notice may result in scalds or injury in case that fluid is hot. 

2.   

When checking the operation of  the product, wear  earplugs and stand clear of exhaust pipe end 

during inspection. Do not look down or touch the open end of the exhaust pipe. 
*  Failure  to  follow  this  notice  may  result  in  scalds  or  injury  due  to  blow-off.  Be  aware  that  the 
product makes a loud noise at start-up.

 

3.    Fluid is discharged from outlet and partly from the other parts.

 

      Due to lift lever mechanism a discharge inspection can be manually performed at more than 75% 

of the blowout pressure. 

 

5

Maintenance and inspection

 

 

5.1

 

Pre-warning and precaution for use 

Warning 

1.    Do not install any closing device such as a stop valve at inlet and outlet sides of the product. 
2.    Install an exhaust pipe on outlet side of the product, and lead it to a place where there is no risk of 

physical damage even if fluid blows out. 
* Failure to follow this notice may result in injury and scalds in case of fluid blow out. 

3.    Do not disassemble the product. 

*  Failure  to  follow  this  notice  may  prevent  the  product  from  functioning  properly  and  lead  to 
danger. 

4.    When installing the product, securely wrapped around the seal tape to the   

threaded portion, please tighten by applying a spanner to the hexagonal portion   
of the valve seat [1]. (Please never tighten against a pipe wrench or other tools on the spring 
chamber [2]). 

* It is dangerous because using fluid is blown out by cracking and loosening of the thread portion. 

5.    Regarding applicable fluid, viscous fluid that may make fixation of the valve and valve seat cannot 

be used. 

* Failure to follow this notice may make valve and valve seat fixed and prevent the product from 
functioning properly. 

6.   

Fluid is discharged from outlet and partly from the other parts.

 

7.    If the product is not operated for a long time, perform test working before starting operation.

 

 

 