5835254-YIM-A-1119
Johnson Controls Ducted Systems
21
Table 10: Electrical data
ZZ15 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
MCA
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Max Fuse
/
Breaker
Size w/
Pwr Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW
Stages
Amps
15
(15)
208
25.0
164
39
2.1
9.6
5.5
None
-
-
-
74.3
79.8
90
90
E18
13.5
2
37.55
74.3
79.8
90
90
E24
18
2
50
74.3
79.8
90
90
E36
25.5
2
70.8
98.1
103.6
110
110
E54
40.6
2
112.7
150.5
156.0
175
175
230
25.0
164
39
2.1
9.6
5.5
None
-
-
-
74.3
79.8
90
90
E18
18
2
43.3
74.3
79.8
90
90
E24
24
2
57.7
81.7
87.2
90
90
E36
34
2
81.8
111.9
117.4
125
125
E54
54
2
129.9
172.0
177.5
190
190
460
12.2
100
19
1.26
4.7
2.2
None
-
-
-
37.1
39.3
45
50
E18
18
2
21.7
37.1
39.3
45
50
E24
24
2
28.9
40.8
43.0
45
50
E36
34
2
40.9
55.8
58.0
60
60
E54
54
2
65
86.0
88.2
90
90
ZZ15 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
MCA
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Max Fuse
/
Breaker
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW
Stages Amps
15
(15)
208
25.0
164
39
2.1
14
5.5
None
-
-
-
78.7
84.2
90
90
E18
13.5
2
37.55
78.7
84.2
90
90
E24
18
2
50
78.7
84.2
90
90
E36
25.5
2
70.8
102.5
108.0
110
110
E54
40.6
2
112.7
154.9
160.4
175
175
230
25.0
164
39
2.1
14
5.5
None
-
-
-
78.7
84.2
90
90
E18
18
2
43.3
78.7
84.2
90
90
E24
24
2
57.7
86.1
91.6
90
100
E36
34
2
81.8
116.3
121.8
125
125
E54
54
2
129.9
176.4
181.9
190
190
460
12.2
100
19
1.26
6.6
2.2
None
-
-
-
39.0
41.2
45
50
E18
18
2
21.7
39.0
41.2
45
50
E24
24
2
28.9
42.7
44.9
45
50
E36
34
2
40.9
57.7
59.9
60
60
E54
54
2
65
87.9
90.1
90
90