5370598-BIM-C-0518
Johnson Controls Ducted Systems
25
1. 1
st
Stage Capacity is 75% of Full Capacity.
2. 1
st
Stage Capacity is 70% of Full Capacity.
3. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
4. 2 In. Pleated, Optional, MERV 8.
5. 4 In. Pleated, Optional, MERV 13.
Optional Electric Heat
The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single point
terminal block.
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending in
to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. refer to Table 11 for
minimum CFM limitations and to Table 9 for electrical data.
CONDENSER FAN DATA
Quantity of fans
2
2
2
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct ECM
Direct ECM
Direct ECM
Quantity of motors
2
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
Var.
Var.
Var.
RPM
850
850
850
Nominal total CFM
7000
7000
7000
BELT DRIVE EVAP FAN DATA
Quantity
1
1
1
Fan Size (Inch)
12 x 9
12 x 9
12 x 9
Type
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VL40
1VL40
1VL34
1VL44
1VL40
1VM50
Blower Sheave
AK79
AK61
AK64
AK69
AK61
AK64
Belt
A47
A45
A47
A47
A45
A47
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
FILTERS
Quantity - Size
4 - (24 x 16 x 2)
3,4
4 - (24 x 16 x 2)
3,4
4 - (24 x 16 x 2)
3,4
4 - (24 x 16 x 4)
5
4 - (24 x 16 x 4)
5
4 - (24 x 16 x 4)
5
ZV-A3 thru -A5 (Continued)
Component
Models
ZV-A3
ZV-A4
ZV-A5
Nominal Tonnage
3.0
4.0
5.0
Table 11: Electric Heat Minimum Supply Air
Size
(Tons)
Model
Voltage
Minimum Supply Air (CFM)
Heater kW
3
6
9
15
20
24
-A3
(3)
ZV
208/230-3-60
960
960
1020
1000
-
-
460-3-60
980
960
960
960
-
-
600-3-60
-
-
960
960
-
-
-A4
(4)
ZV
208/230-3-60
-
1280
1420
1400
1400
-
460-3-60
-
1400
1400
1400
1400
-
600-3-60
-
-
1400
1400
1400
-
-A5
(5)
ZV
208/230-3-60
-
1600
1600
1600
1600
1600
460-3-60
-
1600
1600
1600
1600
1600
600-3-60
-
-
1600
1600
1600
1600