5567611-BIM-B-1218
80
Johnson Controls Ducted Systems
Table 40: ZV-10 charging table - system 1
Table 41: ZV-10 charging table - system 2
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
124
50
261
77
31
80
49
85
127
49
305
86
30
80
50
95
129
51
354
96
28
80
52
300 CFM/ton
80/67
75
137
59
261
78
26
80
54
85
140
58
305
87
25
80
55
95
143
59
355
96
24
80
56
300 CFM/ton
80/72
75
149
66
266
79
21
80
59
85
153
65
311
89
20
80
60
95
156
66
359
97
19
80
61
300 CFM/ton
75/62
75
124
51
260
76
26
75
49
85
128
50
306
86
25
75
50
95
129
52
352
96
23
75
52
400 CFM/ton
80/62
75
133
55
259
77
27
80
53
85
155
63
297
90
20
80
60
95
139
54
350
96
25
80
55
400 CFM/ton
80/67
75
145
63
263
78
22
80
58
85
148
61
307
88
21
80
59
95
151
60
356
98
20
80
60
400 CFM/ton
80/72
75
154
70
267
77
17
80
63
85
160
69
310
87
16
80
64
95
165
68
358
98
15
80
65
400 CFM/ton
75/62
75
132
55
259
77
22
75
53
85
135
54
304
86
21
75
54
95
138
53
349
96
20
75
55
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
126
52
260
76
31
80
49
85
130
52
304
85
30
80
50
95
133
54
354
94
28
80
52
300 CFM/ton
80/67
75
138
59
261
77
26
80
54
85
142
59
305
86
25
80
55
95
145
59
354
95
24
80
56
300 CFM/ton
80/72
75
150
65
267
76
21
80
59
85
154
65
310
87
20
80
60
95
158
66
358
96
19
80
61
300 CFM/ton
75/62
75
127
52
260
75
26
75
49
85
130
52
305
85
25
75
50
95
132
53
354
94
23
75
52
400 CFM/ton
80/62
75
135
57
260
76
27
80
53
85
157
63
296
91
20
80
60
95
142
56
351
95
25
80
55
400 CFM/ton
80/67
75
144
62
264
76
22
80
58
85
149
61
308
86
21
80
59
95
152
61
359
96
20
80
60
400 CFM/ton
80/72
75
155
68
272
74
17
80
63
85
160
68
313
85
16
80
64
95
164
68
362
95
15
80
65
400 CFM/ton
75/62
75
133
55
260
75
22
75
53
85
137
55
305
84
21
75
54
95
140
55
354
94
20
75
55