Charging the unit
Charge unit by weight using name plate data or use charging tables.
Table 34: ZV-06 charging table - system 1
Table 35: ZV-06 charging table - system 2
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
124
53
267
76
29
80
51
85
127
53
306
86
28
80
52
95
131
55
350
95
26
80
54
300 CFM/ton
80/67
75
135
58
268
75
25
80
55
85
138
58
309
85
23
80
57
95
140
59
355
95
22
80
58
300 CFM/ton
80/72
75
147
64
269
75
20
80
60
85
151
64
310
85
19
80
61
95
153
64
355
95
17
80
63
300 CFM/ton
75/62
75
123
51
268
76
25
75
51
85
127
53
306
86
23
75
52
95
131
54
354
96
21
75
54
400 CFM/ton
80/62
75
135
58
258
76
26
80
54
85
137
58
303
85
25
80
55
95
140
59
354
97
24
80
56
400 CFM/ton
80/67
75
146
64
260
76
22
80
58
85
148
62
304
85
21
80
59
95
151
62
355
97
19
80
61
400 CFM/ton
80/72
75
155
70
271
77
17
80
63
85
161
69
305
86
16
80
64
95
164
68
354
97
15
80
65
400 CFM/ton
75/62
75
134
57
264
77
22
75
53
85
135
57
308
86
21
75
54
95
137
57
353
96
19
75
56
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
121
52
272
74
29
80
51
85
124
54
329
84
28
80
52
95
131
56
398
95
26
80
54
300 CFM/ton
80/67
75
133
57
276
75
25
80
55
85
137
58
329
85
23
80
57
95
140
59
416
95
22
80
58
300 CFM/ton
80/72
75
144
62
274
75
20
80
60
85
150
62
322
85
19
80
61
95
154
63
382
95
17
80
63
300 CFM/ton
75/62
75
121
52
272
73
25
75
51
85
124
54
329
84
23
75
52
95
130
54
374
94
21
75
54
400 CFM/ton
80/62
75
133
57
262
73
26
80
54
85
135
57
304
83
25
80
55
95
140
58
357
95
24
80
56
400 CFM/ton
80/67
75
144
60
260
73
22
80
58
85
147
61
303
84
21
80
59
95
152
61
352
95
19
80
61
400 CFM/ton
80/72
75
157
65
265
74
17
80
63
85
160
65
306
84
16
80
64
95
165
65
350
96
15
80
65
400 CFM/ton
75/62
75
131
55
261
74
22
75
53
85
134
56
305
83
21
75
54
95
137
55
359
94
19
75
56