5567611-BIM-B-1218
34
Johnson Controls Ducted Systems
Evaporator coil data
Face area (sq. ft.)
29
29
29
47.5
47.5
Rows
3
4
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
0.375
0.375
0.375
0.375
0.375
Circuitry type
Intertwined
Intertwined
Intertwined
Intertwined
Intertwined
Refrigerant control
TXV
TXV
TXV
TXV
TXV
Reheat option coil data
Face area (sq. ft.)
10
10
10
10
10
Rows
1
2
2
2
2
Fins per inch
13
13
13
13
13
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Condenser fan data
Quantity of fans
4
4
4
4
4
Fan diameter (inches)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Quantity of motors
4
4
4
4
4
Motor HP each
1/3
1/3
1/3
1/3
1/3
No. speeds
2
2
2
2
2
1st speed/2nd speed RPM
850/600
850/600
850/700
850/700
900/700
1st speed/2nd speed total CFM
14000/9500
14000/9500
14000/11000
14000/11000
15000/11000
Belt drive evap. fan data
Quantity
1
1
1
1
1
Fan size (inches)
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
Type
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor sheave
1VL40
1VM50
1VL40
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower sheave
AK74
AK74
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A53
A54
A52
A54
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
56
56
56
184T
Filters
Quantity - size
4 - (24 x 20 x 2)
5,6
4 - (24 x 20 x 2
5, 6
4 - (24 x 20 x 2)
5, 6
4 - (24 x 20 x 2)
5, 6
4 - (24 x 20 x 2)
5, 6
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
1. Gas units
2. Cooling only, electric
3. 1st stage 60% of 2nd stage
4. ZV-06, ZV-07, ZV-08, ZV-10, and ZV-12 have crankcase heaters as standard.
5. 2 in. throwaway, standard, MERV (Minimum Efficiency Reporting Value) 3.
6. 2 in. pleated, optional, MERV 8.
7. 4 in. pleated, optional, MERV 13.
ZV-06 through -12 (Continued)
Component
Models
ZV-06
ZV-07
ZV-08
ZV-10
ZV-12
Nominal tonnage
6.5
7.5
8.5
10
12.5