5167821-YTG-K-1118
Johnson Controls Ducted Systems
71
75°F
85°F
2500
77
60.6
4.3
-
-
-
-
-
-
57.8
4.5
-
-
-
-
-
-
72
53.9
4.1
6.5
4.5
2.4
0.3
-
-
50.2
4.3
3.6
1.9
0.2
-
-
-
67
47.1
3.9
18.8
16.7
14.6
12.5
10.5
-
42.7
4.2
15.1
13.4
11.7
10.0
8.3
-
62
43.2
3.8
31.9
27.3
22.7
20.6
18.6
16.5
39.2
4.1
27.4
23.4
18.5
16.8
15.1
13.4
3000
77
62.1
4.2
-7.1
-10.1
-13.2
-
-
-
58.6
4.4
-
-
-
-
-
-
72 55.1
4.0
9.4
6.3
3.2
0.1
-
-
50.9
4.3
6.1
3.4
0.7
-2.1
-
-
67 48.2
3.8
25.8
22.7
19.6
16.6
13.5
-
43.2
4.1
22.2
19.5
16.7
14.0
11.3
-
62 44.2
3.8
36.7
33.6
30.5
27.5
24.4
21.3
39.7
4.0
31.9
29.1
26.4
23.7
21.0
18.3
57 41.2
3.8
34.7
31.6
28.5
25.4
22.4
19.3
36.3
4.0
28.8
26.1
23.4
20.7
17.9
15.2
3500
77
63.5
4.2
-
-
-
-
-
-
59.4
4.4
-
-
-
-
-
-
72 56.4
4.0
12.2
8.1
4.0
0.0
-
-
51.6
4.2
8.6
4.8
1.1
-
-
-
67 49.4
3.8
32.8
28.7
24.7
20.6
16.5
-
43.8
4.1
29.3
25.6
21.8
18.1
14.3
-
62 45.2
3.7
41.5
39.9
38.3
34.3
30.2
26.1
40.2
4.0
36.3
34.9
34.4
30.7
26.9
23.2
57 42.1
3.7
38.9
37.3
35.8
31.7
27.6
23.6
36.7
4.0
33.0
31.6
30.6
26.8
23.1
19.3
4000
77
64.9
4.1
-
-
-
-
-
-
60.2
4.3
-
-
-
-
-
-
72 57.7
3.9
15.0
9.9
4.8
-0.2
-
-
52.2
4.2
11.1
6.3
1.5
-
-
-
67 50.5
3.7
39.8
34.7
29.7
24.6
19.5
-
44.3
4.0
36.4
31.7
26.9
22.1
17.4
-
62 46.3
3.7
46.3
46.3
46.2
41.1
36.0
30.9
40.7
3.9
40.7
40.7
40.7
37.6
32.8
28.1
57 43.1
3.7
43.1
43.1
43.1
38.0
32.9
27.9
37.2
3.9
37.2
37.2
37.2
33.0
28.2
23.4
4500
72 59.1
3.9
17.3
11.4
5.6
-
-
-
53.6
4.1
13.2
7.6
2.0
-
-
-
67 51.7
3.7
46.1
40.3
34.4
28.6
22.8
-
45.5
4.0
43.1
37.5
31.9
26.3
20.7
-
62 47.4
3.7
47.4
47.4
47.3
41.5
35.7
29.9
41.8
3.9
41.8
41.8
41.8
37.0
31.4
25.8
57 44.1
3.7
44.1
44.1
44.1
38.3
32.5
26.7
38.1
3.9
38.1
38.1
38.1
32.8
27.2
21.6
5000
72 60.5
3.9
19.5
13.0
6.4
-
-
-
55.0
4.1
15.3
8.9
2.5
-
-
-
67 52.9
3.7
52.3
45.8
39.2
32.7
26.1
-
46.6
4.0
46.6
43.4
37.0
30.5
24.1
-
62 48.5
3.6
48.5
48.5
48.5
41.9
35.4
28.8
42.9
3.9
42.9
42.9
42.9
36.4
30.0
23.6
57 45.2
3.6
45.2
45.2
45.2
38.6
32.1
25.5
39.1
3.9
39.1
39.1
39.1
32.7
26.2
19.8
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT120 (10 ton) reheat (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F)
Return dry bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65