5167821-YTG-K-1118
Johnson Controls Ducted Systems
67
75°F
85°F
1875
77
50.1
2.8
8.1
5.0
2.0
-
-
-
45.3
3.0
5.1
4.1
1.4
-
-
-
72
44.3
2.7
15.3
12.3
9.2
6.2
-
-
39.2
2.9
12.9
10.2
7.5
4.7
-
-
67
38.5
2.6
22.6
19.5
16.5
13.4
10.4
-
33.2
2.8
19.0
16.3
13.5
10.8
8.1
-
62
34.7
2.6
31.9
25.9
20.2
17.2
14.1
11.1
29.9
2.8
25.7
19.5
14.5
11.8
9.0
6.3
2250
77
51.9
2.8
10.6
6.6
2.5
-
-
-
47.2
3.0
9.5
5.7
2.0
-
-
-
72 45.9
2.7
19.9
15.9
11.9
7.8
-
-
40.9
2.9
17.9
14.1
10.4
6.6
-
-
67 39.8
2.6
29.2
25.2
21.2
17.2
13.1
-
34.5
2.8
26.3
22.5
18.7
15.0
11.2
-
62 36.0
2.5
34.1
30.0
26.0
22.0
18.0
13.9
31.2
2.8
28.3
24.3
20.5
16.7
13.0
9.2
57 34.3
2.5
33.4
29.3
25.3
21.3
17.3
13.2
29.4
2.8
28.1
24.3
20.5
16.7
13.0
9.2
2625
77 53.6
2.7
13.1
8.1
3.1
-
-
-
49.1
2.9
13.9
7.4
2.6
-
-
-
72 47.4
2.6
24.5
19.5
14.5
9.5
-
-
42.5
2.9
22.9
18.0
13.2
8.4
-
-
67 41.2
2.5
35.9
30.9
25.9
20.9
15.9
-
35.9
2.8
33.5
28.7
23.9
19.1
14.3
-
62 37.2
2.5
36.2
34.2
31.8
26.8
21.8
16.8
32.4
2.8
31.0
29.0
26.5
21.7
16.9
12.1
57 35.4
2.5
35.0
33.0
31.0
26.0
21.0
16.0
30.6
2.8
30.0
28.0
26.4
21.6
16.8
12.0
3000
77 55.4
2.7
15.6
9.6
3.7
-
-
-
50.9
2.9
18.3
9.0
3.1
-
-
-
72 49.0
2.6
29.1
23.1
17.1
11.2
-
-
44.1
2.8
27.8
22.0
16.1
10.3
-
-
67 42.5
2.5
42.5
36.6
30.6
24.7
18.7
-
37.3
2.7
37.3
35.0
29.1
23.2
17.4
-
62 38.4
2.5
38.4
38.4
37.6
31.6
25.7
19.7
33.7
2.8
33.7
33.7
32.5
26.6
20.8
14.9
57 36.6
2.5
36.6
36.6
36.6
30.6
24.7
18.7
31.8
2.7
31.8
31.8
31.8
26.5
20.6
14.8
3375
72 49.2
2.6
32.8
26.0
19.2
12.5
-
-
43.8
2.8
31.8
25.0
18.1
11.3
-
-
67 42.7
2.5
42.7
39.7
34.4
27.6
20.9
-
37.0
2.7
37.0
37.0
32.8
25.9
19.1
-
62 38.6
2.5
38.6
38.6
38.2
31.4
24.6
17.9
33.4
2.7
33.4
33.4
32.8
26.0
19.1
12.3
57 36.7
2.5
36.7
36.7
36.7
30.0
23.2
16.5
31.5
2.7
31.5
31.5
31.5
25.0
18.1
11.3
3750
72 49.4
2.6
36.5
28.9
21.4
13.8
-
-
43.4
2.8
35.8
28.0
20.2
12.4
-
-
67 42.9
2.5
42.9
42.9
38.2
30.6
23.0
-
36.6
2.7
36.6
36.6
36.4
28.6
20.8
-
62 38.7
2.5
38.7
38.7
38.7
31.1
23.6
16.0
33.1
2.7
33.1
33.1
33.1
25.3
17.5
9.7
57 36.9
2.5
36.9
36.9
36.9
29.3
21.8
14.2
31.2
2.7
31.2
31.2
31.2
23.4
15.6
7.8
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT090 (7.5 ton) reheat (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F)
Return dry bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65