Table 19: Airflow performance - bottom duct application
ZR078 (6.5 ton) bottom duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP and field supplied drive
Standard 1.5 HP and drive
High static 2 HP and drive
1800
801
0.45
874
0.65
946
0.82
1018
0.97
1090
1.11
1163
1.25
1238
1.38
1315
1.52
1395
1.68
1477
1.86
2000
831
0.59
903
0.78
975
0.95
1047
1.10
1119
1.24
1193
1.38
1267
1.51
1344
1.66
1424
1.81
1507
1.99
2200
867
0.74
940
0.93
1012
1.10
1084
1.25
1156
1.39
1229
1.53
1304
1.66
1381
1.81
1461
1.96
1543
2.14
2400
910
0.91
983
1.10
1055
1.27
1126
1.43
1199
1.57
1272
1.70
1347
1.84
1424
1.98
1503
2.14
-
-
2600
957
1.10
1030
1.30
1102
1.47
1174
1.62
1246
1.76
1320
1.89
1394
2.03
1471
2.17
-
-
-
-
2800
1009
1.32
1082
1.51
1154
1.69
1225
1.84
1298
1.98
1371
2.11
1446
2.25
-
-
-
-
-
-
3000
1064
1.56
1137
1.75
1208
1.92
1280
2.08
1353
2.22
-
-
-
-
-
-
-
-
-
-
3200
1122
1.82
1194
2.02
1266
2.19
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3400
1182
2.10
1254
2.30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2 HP and field supplied drive
ZR090 (7.5 ton) bottom duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP and
field supplied
drive
Standard 1.5 HP and drive
High static 3 HP and drive
2000
831
0.59
903
0.78
975
0.95
1047
1.10
1119
1.24
1193
1.38
1267
1.51
1344
1.66
1424
1.81
1507
1.99
2200
867
0.74
940
0.93
1012
1.10
1084
1.25
1156
1.39
1229
1.53
1304
1.66
1381
1.81
1461
1.96
1543
2.14
2400
910
0.91
983
1.10
1055
1.27
1126
1.43
1199
1.57
1272
1.70
1347
1.84
1424
1.98
1503
2.14
1586
2.31
2600
957
1.10
1030
1.30
1102
1.47
1174
1.62
1246
1.76
1320
1.89
1394
2.03
1471
2.17
1551
2.33
1634
2.51
2800
1009
1.32
1082
1.51
1154
1.69
1225
1.84
1298
1.98
1371
2.11
1446
2.25
1523
2.39
1602
2.55
1685
2.73
3000
1064
1.56
1137
1.75
1208
1.92
1280
2.08
1353
2.22
1426
2.35
1501
2.49
1578
2.63
1657
2.79
1740
2.96
3200
1122
1.82
1194
2.02
1266
2.19
1338
2.34
1410
2.48
1484
2.61
1559
2.75
1636
2.89
1715
3.05
1798
3.23
3400
1182
2.10
1254
2.30
1326
2.47
1398
2.62
1471
2.76
1544
2.90
1619
3.03
1696
3.17
1775
3.33
-
-
3600
1244
2.41
1317
2.60
1389
2.77
1461
2.93
1533
3.07
1606
3.20
1681
3.33
-
-
-
-
-
-
3800
1308
2.73
1381
2.93
1453
3.10
1525
3.25
1597
3.39
-
-
-
-
-
-
-
-
-
-
3 HP and field supplied drive
ZR102 (8.5 ton) bottom duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP and field
supplied drive
Standard 2 HP and drive
High static 3 HP and drive
2200
715
0.72
768
0.85
818
0.98
867
1.09
914
1.21
960
1.32
1004
1.43
1047
1.53
1089
1.64
1131
1.75
2400
734
0.83
786
0.96
837
1.08
886
1.20
933
1.31
978
1.42
1022
1.53
1066
1.64
1108
1.75
1150
1.86
2600
755
0.95
808
1.08
858
1.20
907
1.32
954
1.44
1000
1.55
1044
1.65
1087
1.76
1129
1.87
1171
1.98
2800
779
1.09
832
1.22
882
1.35
931
1.46
978
1.58
1024
1.69
1068
1.80
1111
1.90
1153
2.01
1195
2.12
3000
806
1.25
859
1.38
910
1.51
958
1.63
1005
1.74
1051
1.85
1095
1.96
1138
2.07
1181
2.17
1222
2.28
3200
837
1.44
889
1.57
940
1.69
989
1.81
1036
1.93
1081
2.04
1125
2.14
1168
2.25
1211
2.36
1252
2.47
3400
870
1.65
922
1.78
973
1.90
1022
2.02
1069
2.13
1114
2.24
1158
2.35
1202
2.46
1244
2.57
1286
2.68
3600
906
1.88
959
2.01
1009
2.13
1058
2.25
1105
2.36
1150
2.47
1195
2.58
1238
2.69
1280
2.80
1322
2.91
3800
945
2.13
998
2.26
1048
2.38
1097
2.50
1144
2.61
1190
2.72
1234
2.83
1277
2.94
1319
3.05
1361
3.16
4000
987
2.40
1040
2.53
1090
2.66
1139
2.78
1186
2.89
1231
3.00
1276
3.11
1319
3.21
1361
3.32
1403
3.43
4200
1032
2.70
1084
2.83
1135
2.95
1184
3.07
1231
3.18
1276
3.29
1320
3.40
-
-
-
-
-
-
3 HP and field supplied drive