5725848-XIM-A-0319
22
Johnson Controls Ducted Systems
Indoor air quality
Indoor Air quality (indoor sensor input): Terminal AQ accepts a
+2 to +10 Vdc signal with respect to the (AQ1) terminal. When
the signal is below it's setpoint, the actuator is allowed to
modulate normally in accordance with the enthalpy and mixed
air sensor inputs. When the AQ signal exceeds it's setpoint
setting and there is no call for free cooling, the actuator is
proportionately modulated from the 2 to 10 Vdc signal, with 2
Vdc corresponding to full closed and 10 Vdc corresponding to
full open. When there is no call for free cooling, the damper
position is limited by the IAQ Max damper position setting.
When the signal exceeds it's setpoint (Demand Control
Ventilation Setpoint) setting and there is a call for free cooling,
the actuator modulates from the minimum position to the full
open position based on the highest call from either the mixed
air sensor input or the AQ voltage input.
• Optional CO
2
Space Sensor Kit Part # 2AQ04700324
• Optional CO
2
Unit Sensor Kit Part # 2AQ04700424
Replace the economizer access panel.
Jade Economizer interface overview
Units with Simplicity Lite Controls will have a field installed
(Jade) Economizer Kit Offered.
This section describes how to use the Economizer’s user
interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User interface
The user interface consists of an LCD display and a 4-button
keypad on the front of the Economizer module. The LCD is a 16
character by 2 line dot matrix display.
Figure 10: Economizer LCD and keypad layout.
Keypad
The four navigation buttons illustrated in Fig. 8 are used to
scroll through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Using the keypad with menus
To use the keypad when working with menus:
• Press the
button to move to the previous menu.
• Press the
button to move to the next menu.
• Press the
button (Enter) to display the first item in the
currently displayed menu.
• Press the
button (Menu up) to exit a menu’s item and
return to the list of menus.
C
COM
24 VAC common/0-5 VDC negative for the
building pressure sensor
Connects through circuit trace to 24V~ IN pin COM
BINARY INPUTS at right on lower edge of economizer board
IN9
PURGE
24 VAC hot input from the PURGE dry contact
Purge parameter reports input status (False with 0 VAC input-
True with 24 VAC input). When Purge status is True, heating and
cooling operation is prevented, the indoor blower and power
exhaust fan operate, the economizer actuator is positioned to
100%.
24V~
24 VAC hot supplied for the purge dry contact
Connects through circuit trace to 24V~ IN pin HOT
IN10
EX VFD
FLT
24 VAC hot input from the power Exhaust
Variable Frequency Drive Fault contact
ExFanVFDFlt parameter reports input status (Normal with 0 VAC
input-Alarm with 24 VAC input) when ExFType selection is
Variable Frequency Fan. When ExFanVFDFlt status is Alarm,
EX-FAN fan output is prevented.
24V~
24 VAC hot supplied for the power exhaust
variable frequency drive fault contact
Connects through circuit trace to 24V~ IN pin HOT
1. When wiring unit and other devices using the SA Bus and FC Bus, see Table 29.
Table 5: Smart Equipment™ Economizer Board details (continued)
Board
Label
Cover
Label
Description
Function & Comments
MENU UP
(EXIT)
BUTTON
SCROLL
(UP/DOWN)
BUTTONS
SELECT (ENTER)
BUTTONS
2 LINE
LCD