251934-YTG-G-0708

Johnson Controls Unitary Products

9

can also be slab-mounted at ground level or set on steel beams 
above a finished roof. Cooling only, cooling with gas heat and 
cooling with electric heat models are available with a wide 
variety of factory-mounted options and field-installed 
accessories to make them suitable for almost every application. 
All units are self-contained and assembled on full perimeter 
base rails with holes in the four corners for overhead rigging. 
Every unit is completely piped, wired, charged and tested at the 
factory to simplify the field installation and to provide years of 
dependable operation. All models (including those with an 
economizer) are suitable for either bottom or horizontal duct 
connections. Models with power exhaust are suitable for bottom 
duct connections only. For bottom duct, remove the sheet metal 
panels from the supply and return air openings through the 
base of the unit. For horizontal duct, replace the supply and 
return air panels on the rear of the unit with a side duct flange 
accessory. All supply air blowers are equipped with a belt drive 
that can be adjusted to meet the exact requirements of the job. 

Each unit shall have 4 condenser fan motors. A high static drive 
option is available for applications with a higher CFM and/or 
static pressure requirement. All compressors include crankcase 
heat and internal pressure relief. Every refrigerant circuit 
includes an expansion valve, a liquid line filter-drier, a discharge 
line high pressure switch and a suction line with a freezestat 
and low pressure/loss of charge switch. The unit control circuit 
includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with two compressor lockout circuits, a terminal 
strip for thermostat wiring, plus an additional set of pin 
connectors to simplify the interface of additional field controls. 
All units have long lasting powder paint cabinets with 1000 hour 
salt spray test approval under ASTM-B117 procedures. All 208/
230, 460 and 575-volt models are CSA approved. All models 
include a 1-year limited warranty on the complete unit. 
Compressors and electric heater elements carry an additional 
4-year warranty. Aluminized steel tubular heat exchangers 
carry an additional 9-year warranty.

Description

ZJ units shall be factory-assembled, single packaged, ZJ***N 
Electric Cooling/Gas Heat, ZJ***C/E Electric Cooling/Optional 
Electric Heat, designed for outdoor mounted installation. The 15 
ton unit shall have a minimum EER rating of 12.4. The 17.5 ton 
unit shall have a minimum EER rating of 12.1. The 20 ton unit 
shall have a minimum EER rating of 11.6. The 25 ton unit shall 
have a minimum EER rating of 10.4.

ZR units shall be factory-assembled, single packaged, ZR***N 
Electric Cooling/Gas Heat, ZR***C/E Electric Cooling/Optional 
Electric Heat, designed for outdoor mounted installation. The 15 
ton unit shall have a minimum EER rating of 11.6.  The 20 ton 
unit shall have a minimum EER rating of 12.1. The 25 ton unit 
shall have a minimum EER rating of 10.5.

ZF units shall be factory-assembled, single packaged, ZF***N 
Electric Cooling/Gas Heat, ZF***C/E Electric Cooling/Optional 
Electric Heat, designed for outdoor mounted installation. The 15 
and 17.5 ton units shall have a minimum EER rating of 11.0.  
The 20 and 25 ton units shall have a minimum EER rating of 10.

They shall have built-in field convertible duct connections for 
down discharge supply/return or horizontal discharge supply/
return, and be available with factory installed options or field 
installed accessories. The units shall be factory wired, piped, 
charged with R-410A refrigerant and factory tested prior to 
shipment. All unit wiring shall be both numbered and color 
coded. All units shall be manufactured in a facility certified to 
ISO 9001 standards and the cooling performance shall be rated 
in accordance with DOE and ARI test procedures. Units shall 
be CSA listed, classified to ANSIZ21.47 standards, UL 1995/
CAN/CSA No. 236-M90 conditions.

Unit Cabinet

Unit cabinet shall be constructed of G90 galvanized steel, 
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hours salt spray test per ASTM-
B117 standards. Indoor blower section shall be insulated 
with a minimum 1/2" thick insulation, coated on the airside. 
Aluminum foil faced insulation shall be used in the furnace 
compartment and be fastened with ridged fasteners to 
prevent insulation from entering the air stream. Cabinet 
panels shall be "large" size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 2" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1" or 2" filters. Fan 
performance measuring ports shall be provided on the 
outside of the cabinet to allow accurate air measurements of 
evaporator fan performance without removing panels or 
creating air by-pass of the coils. Condensate pan shall be 
internally sloped and conform to ASHRAE 62-89 self-
draining standards. Condensate connection shall be a 
minimum of 1" I.D. female and be a ridged mount connection. 
Unit shall incorporate a fixed outdoor air damper with an 
outdoor air intake opening covered with a bird screen and a 
rain hood painted to match the exterior of the unit.

Indoor (Evaporator) Fan Assembly

Fan shall be a belt drive assembly and include an adjustable- 
pitch motor pulley. Job site selected (B.H.P.) brake horsepower 
shall not exceed the motors nameplate horsepower rating, plus 
the service factor. Units shall be designed not to operate above 
service factor. Fan wheel shall be double-inlet type with 
forward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume.

A variable air volume (VAV) option using a variable frequency 
drive (VFD) is available for applications requiring a constant 
supply duct static pressure. Units equipped for VAV shall be 
controlled by a duct pressure transducer with a 0 - 5” WC 
pressure range. The pressure transducer shall provide a 0 - 5 
VDC output signal to a VAV control board which, in turn shall 
provide a 2 - 10 VDC speed reference signal to the VFD. The 
VAV control board shall operate using factory-installed Supply 
Air, Return Air and Outside Air Temperature Sensors. Units 

Summary of Contents for ZF 180 Series

Page 1: ...n steel beams above a finished roof All ZJ ZR ZF units are self contained and assembled on rigid full perimeter base rails allowing for overhead rigging Every unit is completely charged wired piped and tested at the factory to provide a quick and easy field installation All models including those with an economizer are convertible between bottom and horizontal duct connections ZJ ZR ZF units are a...

Page 2: ...e of Contents Description 1 Table of Contents 2 Component Location 3 Nomenclature 4 Features and Benefits 5 Guide Specifications 8 Physical Data 15 Capacity Performance 21 Airflow Performance 49 Sound Performance 69 Electrical Data 70 Weights and Dimensions 96 ...

Page 3: ...or Motor Electric Heater Location Optional Electric Electric Units Belt Drive Blower Motor 14 Gauge Base Rails with Lifting Holes Filter Drier Solid Core Thermal Expansion Valve Copper Tube Aluminum Fin Evaporator Coils 2 Disposable Filters 4 Filters Optional Slide In Plug In Internal Economizer Optional 1 NPT Condensate Drain Location of VFD Optional Location of VFD Bypass Optional 4 High Efficie...

Page 4: ...Filter Door Tool Free Access Panels BE Phase Monitor Coil Guard Hinged Filter Door Tool Free Access Panels BF Phase Monitor Dirty Filter Switch Hinged Filter Door Tool Free Access Panels BG Coil Guard Dirty Filter Switch Hinged Filter Door Tool Free Access Panels BH Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Tool Free Access Panels 15 25 Ton Sunline Magnum Model Number Nomencl...

Page 5: ...nections the intake damper assembly should be mounted over the opening in the return air panel With horizontal ductwork it should be mounted on the return air duct System Protection Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running Every unit has solid...

Page 6: ...ee cooling operation Field installed humidity sensors for either outdoor air or outdoor return air streams are available for single enthalpy and differential enthalpy configurations respectively The rainhood is painted to match the basic unit and must be field assembled before installing Power Exhaust Our economizer options are available with power exhaust Whenever the outdoor air intake dampers a...

Page 7: ...S single zone change over bypass and VAV systems Smoke Detectors supply air return air The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment Coil Guard Customers can purchase a coil guard kit to protect the condenser coil from damage This is not a hail guard kit Stainless Steel Heat Exchanger For applications in co...

Page 8: ...uirements of the National Roofing Contractors Association NRCA and are shipped knocked down for field assembly They re designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports High Altitude Natural Gas Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6 000 feet Propane Burner orifices pilot orifi...

Page 9: ...Cooling Optional Electric Heat designed for outdoor mounted installation The 15 and 17 5 ton units shall have a minimum EER rating of 11 0 The 20 and 25 ton units shall have a minimum EER rating of 10 They shall have built in field convertible duct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed a...

Page 10: ...dard safety devices trip and shut off compressor c Loss of charge Low pressure switch 1 High pressure switch 2 Freeze protection thermostat evaporator coil If any of the above safety devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall incorporate AUTO RESET compressor over temperature over current protection e ...

Page 11: ...e for the outdoor air intake dampers shall not exceed 2 when dampers are fully closed and operating against a pressure differential of 0 5 IWG A unit mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation Whenever the indoor fan motor ...

Page 12: ... cooling mode Indoor blower operation is initiated upon a call for first stage cooling second stage cooling or dehumidification Anytime there is a call for 2 stages of cooling the unit will not operate in the reheat mode even if there is a call for dehumidification at HUM The unit will not operate in the reheat mode if there is any call for heating On units with economizers the unit will not opera...

Page 13: ...YTG G 0708 Johnson Controls Unitary Products 13 Reheat Control Board Reheat Controls Part 1 R Y1 Y2 G W1 OCC C W2 P4 P5 P6 P3 COM HGRR HGR HUM K1 K2 K4 K3 MODE SELECTION JUMPER DEHUMIDISTAT HARNESS CONNECTION ...

Page 14: ...Products Reheat Controls Part 2 UCB UNIT CONTROL BOARD RHB REHEAT CONTROL BOARD RHTB REHEAT TERMINAL BLOCK HUM HUMIDIFY TERMINAL RHR REHEAT RELAY REHEAT SOLENOID 3 REHEAT SOLENOID 1 REHEAT SOLENOID 2 RHB REHEAT CONTROL BOARD UCB UNIT CONTROL BOARD ...

Page 15: ...40 320 240 320 240 320 240 320 AFUE Steady state efficiency 80 80 80 80 80 80 80 80 No burners 6 8 6 8 6 8 6 8 No stages 2 2 2 2 2 2 2 2 Temperature Rise Range ºF 20 50 30 60 20 50 30 60 20 50 30 60 20 50 30 60 Gas Limit Setting ºF 195 195 195 195 195 195 195 195 Gas piping connection in 1 1 1 1 1 1 1 1 DIMENSIONS inches Length 180 19 32 Width 92 Height 52 5 8 OPERATING WT lbs 2609 2665 2697 2783 ...

Page 16: ...X 15 18 X 15 Type Centrifugal Centrifugal Centrifugal Centrifugal Motor Sheave 1VP65 1VP65 1VP60 1VP60 1VP60 1VP60 1VP60 1VP75X 1VP75X Blower Sheave BK110 BK090 BK110 BK090 BK110 BK090 1B5V94 1B5V110 1B5V94 Belt BX85 BX81 BX78 BX75 BX78 BX75 BX78 5VX840 5VX860 Motor HP each 5 5 5 7 5 5 7 5 7 5 10 15 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 184T 184T 184T 213T 184T 213T 213T 215T...

Page 17: ...burners 6 8 6 8 6 8 No stages 2 2 2 2 2 2 Temperature Rise Range ºF 20 50 30 60 20 50 30 60 20 50 30 60 Gas Limit Setting ºF 195 195 195 195 195 195 Gas piping connection in 1 1 1 1 1 1 DIMENSIONS inches Length 180 19 32 Width 92 Height 52 5 8 OPERATING WT lbs 2360 2660 2760 COMPRESSORS Type Scroll Scroll Scroll Quantity 2 2 2 Unit Capacity Steps 50 100 50 100 50 100 CONDENSER COIL DATA Face area ...

Page 18: ...15 18 X 15 18 X 15 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VP65 1VP65 1VP60 1VP60 1VP60 1VP75X 1VP75X Blower Sheave BK110 BK090 BK110 BK090 1B5V94 1B5V110 1B5V94 Belt BX85 BX81 BX78 BX75 BX78 5VX840 5VX860 Motor HP each 5 7 5 7 5 10 7 5 10 15 RPM 1725 1725 1725 1725 1725 1725 1725 Frame size 184T 213T 213T 215T 213T 215T 254T FILTERS Quantity Size 4 16 x 25 x 2 4 16 x 20 x 2 4 16 x ...

Page 19: ...80 80 80 80 80 No burners 6 8 6 8 6 8 6 8 No stages 2 2 2 2 2 2 2 2 Temperature Rise Range ºF 20 50 30 60 20 50 30 60 20 50 30 60 20 50 30 60 Gas Limit Setting ºF 195 195 195 195 195 195 195 195 Gas piping connection in 1 1 1 1 1 1 1 1 DIMENSIONS inches Length 125 1 4 136 1 4 136 1 4 136 1 4 Width 92 92 92 92 Height 48 5 8 52 5 8 52 5 8 52 5 8 OPERATING WT lbs 1870 2533 2006 2597 COMPRESSORS Type ...

Page 20: ...X78 BX75 BX78 BX75 BX78 5VX840 5VX860 Motor HP each 5 5 5 7 5 5 7 5 7 5 10 15 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 184T 184T 184T 213T 184T 213T 213T 215T 254T FILTERS Quantity Size 4 16 x 25 x 2 4 16 x 25 x 2 4 16 x 25 x 2 5 18 x 24 x 2 4 16 x 20 x 2 4 16 x 20 x 2 4 16 x 20 x 2 ZJ ZR ZF180 300 Unit Limitations Size Tons Unit Voltage Unit Limitations Applied Voltage Outdoor ...

Page 21: ...80 5 152 4 124 3 96 3 67 225 5 10 2 225 5 194 5 166 9 139 3 111 6 212 9 11 6 212 9 191 0 162 9 134 8 106 7 62 208 2 10 1 208 2 208 2 208 2 180 6 152 9 125 3 197 1 11 5 197 1 197 1 197 1 169 0 140 9 112 8 57 206 0 10 1 206 0 206 0 206 0 178 4 150 8 123 1 195 0 11 5 195 0 195 0 195 0 166 9 138 8 110 7 95 F 105 F 3750 77 207 2 13 4 98 7 80 5 62 3 193 7 15 3 88 6 74 0 56 0 72 192 8 13 3 123 6 105 4 87...

Page 22: ...5 106 7 80 9 157 0 18 1 157 0 152 6 126 8 100 9 75 1 62 158 1 16 3 158 1 158 1 162 5 136 7 110 9 85 1 145 8 18 0 145 8 145 8 145 8 129 5 103 6 77 8 57 159 3 16 3 159 3 159 3 157 2 131 4 105 6 79 8 148 6 18 1 148 6 148 6 146 4 120 5 94 7 68 8 6600 72 186 1 16 6 158 7 131 5 104 3 77 0 171 7 18 3 152 1 124 8 97 5 70 2 67 171 5 16 4 171 5 165 5 140 0 112 7 85 5 157 9 18 1 157 9 157 9 134 2 106 9 79 7 ...

Page 23: ... 7 12 0 262 7 234 8 201 5 168 1 134 8 246 5 13 5 246 5 229 7 195 7 161 8 127 8 62 227 5 11 7 227 5 227 5 227 5 194 2 160 8 127 5 224 9 13 4 224 9 224 9 224 9 190 9 157 0 123 0 57 239 2 11 8 239 2 239 2 239 2 205 9 172 6 139 3 227 5 13 4 227 5 227 5 227 5 193 6 159 6 125 6 95 F 105 F 5500 77 247 8 15 2 116 1 95 1 71 5 239 3 17 2 112 2 91 4 67 5 72 227 1 15 1 153 8 130 3 106 7 83 2 217 3 17 0 150 0 ...

Page 24: ...83 4 154 0 124 7 95 3 172 5 20 9 172 5 172 5 147 9 118 5 89 0 62 185 9 19 0 185 9 185 9 180 1 150 8 121 5 92 1 173 0 20 9 173 0 173 0 168 3 138 8 109 3 79 8 57 184 3 18 9 184 3 184 3 180 5 151 1 121 8 92 4 173 8 20 9 173 8 173 8 170 6 141 1 111 6 82 1 7875 72 217 1 19 1 186 2 154 2 122 3 90 3 202 0 21 0 180 5 148 5 116 5 84 5 67 192 6 19 0 192 6 190 3 165 2 133 2 101 2 176 6 20 9 176 6 176 6 158 7...

Page 25: ... 3 307 3 260 5 224 3 188 0 151 8 288 4 16 2 288 4 252 8 216 6 180 3 144 1 62 284 5 14 1 284 5 284 5 270 0 233 8 197 6 161 3 270 8 16 0 270 8 270 8 262 2 226 0 189 7 153 4 57 276 1 14 3 276 1 276 1 276 1 239 9 203 7 167 4 264 6 16 1 264 6 264 6 264 6 228 4 192 1 155 9 95 F 105 F 5000 77 279 8 18 1 123 4 100 8 77 9 266 3 20 4 113 1 96 4 73 6 72 257 3 18 0 158 7 135 9 113 1 90 2 242 4 20 3 153 2 130 ...

Page 26: ...07 8 175 3 142 8 110 3 198 3 24 8 198 3 198 3 167 8 134 9 102 0 62 209 0 22 5 209 0 209 0 208 4 175 9 143 4 110 9 192 7 24 8 192 7 192 7 192 7 163 9 131 0 98 1 57 208 1 22 5 208 1 208 1 206 8 174 3 141 8 109 3 193 2 24 8 193 2 193 2 192 9 160 0 127 1 94 2 8700 72 250 7 22 7 208 7 174 1 139 5 104 9 232 8 25 0 202 9 168 0 133 1 98 2 67 222 9 22 6 222 9 218 5 184 5 149 9 115 3 203 7 24 8 203 7 203 7 ...

Page 27: ...368 0 333 1 305 4 277 8 250 1 346 8 23 1 346 8 317 5 287 8 258 1 228 4 62 342 2 21 2 342 2 342 2 342 2 314 5 286 9 259 2 322 2 22 7 322 2 322 2 322 2 292 5 262 8 233 1 57 328 7 20 9 328 7 328 7 328 7 301 0 273 3 245 7 312 3 22 5 312 3 312 3 312 3 282 6 252 9 223 2 95 F 105 F 6250 77 350 8 24 4 158 2 131 2 104 2 332 2 27 0 148 2 122 8 95 7 72 323 9 24 0 198 5 171 5 144 5 117 5 306 0 26 7 190 4 163 ...

Page 28: ...5 276 5 249 3 215 6 182 0 148 4 253 4 32 1 253 4 240 5 207 3 174 1 140 9 62 258 6 28 9 258 6 258 6 267 4 233 8 200 1 166 5 238 2 31 6 238 2 238 2 238 2 224 8 191 6 158 4 57 254 7 29 0 254 7 254 7 282 7 249 0 215 4 181 8 235 4 31 7 235 4 235 4 235 4 235 4 203 3 170 1 11250 72 298 2 30 1 240 3 208 6 177 0 145 3 270 6 32 7 229 1 198 2 167 2 136 3 67 271 7 29 7 271 7 258 1 233 3 201 6 170 0 245 5 32 4...

Page 29: ...5 0 127 7 90 5 67 232 3 11 5 232 3 208 9 171 7 134 4 97 2 218 2 12 7 218 2 204 6 167 3 130 1 92 8 62 214 5 11 3 214 5 214 5 214 5 177 3 140 0 102 7 201 9 12 5 201 9 201 9 201 9 164 6 127 4 90 1 57 211 2 11 2 211 2 211 2 211 2 174 0 136 7 99 4 199 0 12 4 199 0 199 0 199 0 161 8 124 5 87 2 95 F 105 F 4500 77 224 8 14 1 111 4 90 0 68 6 208 7 15 6 103 5 82 1 60 7 72 208 3 13 9 142 7 121 3 99 9 78 5 19...

Page 30: ...7 161 2 16 8 161 2 161 2 157 7 128 5 99 4 70 2 150 2 18 4 150 2 150 2 146 3 117 1 88 0 58 8 6750 72 190 0 17 1 170 7 137 5 104 2 71 0 175 2 18 6 164 4 131 2 98 0 64 8 67 172 6 17 0 172 6 167 6 141 5 108 3 75 1 157 8 18 5 157 8 157 8 135 6 102 4 69 2 62 161 5 16 8 161 5 161 5 162 9 129 7 96 5 63 3 148 5 18 3 148 5 148 5 148 5 120 1 86 9 53 7 57 162 7 16 8 162 7 162 7 160 9 127 7 94 5 61 3 151 4 18 ...

Page 31: ...113 1 110 0 106 8 56 8 25 0 107 2 8 9 107 2 105 0 94 6 48 9 20 0 7500 72 156 9 10 2 146 7 10 8 67 141 0 9 4 92 8 55 6 18 3 131 8 10 0 87 8 50 6 13 3 62 122 5 8 5 112 9 110 0 85 0 65 0 115 1 9 2 107 4 130 0 75 0 50 0 57 118 3 8 4 118 3 118 3 81 1 78 0 45 0 111 8 9 1 111 8 111 8 74 5 25 8 35 0 55 F 65 F 4500 72 117 5 11 1 109 2 11 8 67 105 6 10 4 41 9 20 5 98 2 11 1 37 7 16 4 62 92 7 9 7 85 0 65 0 4...

Page 32: ...80 9 47 7 14 4 83 6 12 0 83 6 75 4 42 2 9 0 57 89 6 11 1 89 6 87 0 58 2 24 9 83 8 11 9 90 0 83 4 46 0 17 0 7500 72 115 9 12 5 105 7 13 1 67 104 3 11 9 72 8 35 5 95 1 12 5 67 8 30 5 62 92 9 11 3 91 0 85 0 45 0 5 0 85 5 12 0 85 5 70 0 35 0 57 92 2 11 2 92 2 92 2 55 0 17 7 85 7 11 9 85 7 85 7 48 4 15 0 1 These capacities are gross ratings For net capacity deduct air blower motor MBh 3 415 x kW Refer ...

Page 33: ...4 7 301 4 258 9 209 2 159 5 109 9 282 3 16 2 282 3 254 1 204 4 154 7 105 0 62 273 9 14 6 273 9 273 9 260 1 210 4 160 8 111 1 259 7 16 0 259 7 259 7 252 2 202 5 152 8 103 2 57 270 8 14 4 270 8 270 8 270 8 221 1 171 4 121 7 255 2 15 9 255 2 255 2 255 2 205 5 155 8 106 1 95 F 105 F 6000 77 290 7 17 9 140 6 112 1 83 6 269 2 19 8 129 8 101 2 72 7 72 267 8 17 7 179 9 151 4 122 8 94 3 247 9 19 6 170 7 14...

Page 34: ... 66 8 57 207 3 21 2 207 3 207 3 187 2 148 4 109 5 70 6 193 6 23 1 193 6 193 6 164 6 125 7 86 8 47 9 9000 72 244 2 21 5 217 3 173 0 128 8 84 5 223 8 23 3 207 9 163 6 119 4 75 1 67 223 2 21 3 223 2 220 7 181 3 137 0 92 7 204 5 23 2 204 5 204 5 174 6 130 3 86 0 62 206 6 21 1 206 6 206 6 204 2 159 9 115 7 71 4 188 3 22 9 188 3 188 3 187 1 142 8 98 6 54 3 57 209 4 21 2 209 4 209 4 191 7 147 4 103 2 58 ...

Page 35: ...49 1 11 0 149 1 148 4 104 1 59 8 15 6 139 5 11 8 139 5 138 7 94 4 50 1 5 8 10000 72 180 6 12 8 37 7 169 7 13 5 32 4 67 165 5 12 0 124 4 51 4 1 7 155 0 12 8 114 8 46 5 62 159 0 11 1 138 0 129 7 80 0 30 3 148 5 11 9 125 0 122 0 72 3 22 6 57 147 2 11 0 147 2 147 2 97 5 115 0 137 5 11 8 137 5 135 0 87 8 95 0 55 F 65 F 6000 72 122 2 12 7 4 5 125 4 14 2 7 9 67 109 1 12 0 51 5 22 9 112 5 13 5 47 0 18 5 6...

Page 36: ...119 5 14 4 98 0 95 2 50 9 6 6 109 1 15 2 95 0 89 4 45 1 0 8 57 110 7 14 3 110 7 109 5 65 2 20 9 101 1 15 1 101 1 99 8 55 5 11 2 10000 72 137 1 15 7 16 7 126 3 16 5 11 5 67 123 7 15 0 86 0 31 7 113 2 15 8 76 4 26 7 62 116 9 14 4 100 0 98 9 49 2 106 4 15 2 84 0 80 0 41 5 57 108 3 14 3 108 3 108 3 58 6 35 0 98 6 15 1 98 6 98 6 48 9 15 0 1 These capacities are gross ratings For net capacity deduct air...

Page 37: ...3 370 6 314 9 252 8 190 7 128 6 347 6 23 0 347 6 306 8 244 7 182 6 120 5 62 337 7 20 6 337 7 337 7 303 9 241 8 179 7 117 6 319 8 22 3 319 8 319 8 292 6 230 5 168 4 106 3 57 332 2 20 6 332 2 332 2 317 0 254 9 192 8 130 7 313 4 22 3 313 4 313 4 302 4 240 3 178 2 116 1 95 F 105 F 7500 77 369 4 23 3 189 1 153 4 117 8 342 9 26 5 167 4 131 8 96 1 72 337 6 23 4 230 5 194 8 159 2 123 5 313 5 26 3 214 9 17...

Page 38: ... 133 0 84 4 57 250 4 28 5 250 4 250 4 244 1 195 5 146 9 98 3 231 0 31 1 231 0 231 0 224 9 176 3 127 7 79 1 11250 72 307 0 29 9 263 0 207 6 152 3 96 9 283 0 32 7 246 1 190 8 135 4 80 1 67 278 3 29 5 278 3 271 3 216 0 160 6 105 3 256 7 32 0 256 7 256 7 206 7 151 4 96 0 62 258 8 29 1 258 8 258 8 247 7 192 3 137 0 81 6 238 7 31 8 238 7 238 7 232 2 176 8 121 5 66 1 57 252 6 29 0 252 6 252 6 246 3 190 9...

Page 39: ...8 9 25 3 159 9 16 0 150 0 141 8 83 9 21 9 12500 72 199 6 18 0 65 6 55 0 190 8 19 2 64 2 52 0 67 175 0 17 4 99 8 85 0 169 0 18 6 94 4 80 0 62 166 9 16 4 137 0 135 0 53 8 27 2 159 7 17 6 126 0 104 0 50 3 16 6 57 165 4 16 0 165 0 148 0 93 0 16 9 157 4 17 0 157 4 146 0 87 0 14 9 55 F 65 F 7500 72 177 9 17 9 44 2 8 6 165 2 19 2 40 5 4 8 67 160 0 17 4 54 5 25 0 150 1 18 7 50 7 15 1 62 149 0 16 5 80 6 30...

Page 40: ... 4 65 0 9 6 62 136 2 20 4 120 0 99 0 40 0 127 5 21 6 120 0 91 0 35 7 57 131 5 18 6 131 5 125 0 69 0 12 0 122 1 21 2 122 1 119 4 64 0 8 7 12500 72 164 4 23 0 60 0 43 0 155 7 24 2 58 6 40 0 67 151 0 22 3 78 0 65 0 145 0 23 5 72 5 60 0 62 137 9 21 4 114 0 100 0 40 0 130 7 22 7 110 0 98 7 36 6 57 133 2 19 6 133 2 128 0 69 0 9 0 125 1 22 3 125 1 122 0 63 0 7 0 1 These capacities are gross ratings For n...

Page 41: ... 2 126 4 99 6 67 227 8 11 7 227 8 194 4 167 5 140 6 113 7 212 2 12 9 212 2 194 0 167 2 140 4 113 6 62 208 0 11 4 208 0 208 0 208 0 181 1 154 2 127 3 194 3 12 7 194 3 194 3 194 3 167 5 140 7 113 9 57 264 8 11 0 264 8 264 8 264 8 237 9 211 0 184 2 223 7 12 5 223 7 223 7 223 7 196 9 170 1 143 3 95 F 105 F 3750 77 211 0 13 6 86 1 69 5 53 0 197 0 15 4 81 3 67 6 51 0 72 192 2 13 7 114 2 97 7 81 1 64 6 1...

Page 42: ...5 107 5 84 5 150 4 18 3 150 4 147 3 124 4 101 6 78 7 62 151 4 16 7 151 4 151 4 139 3 116 3 93 2 70 2 138 4 18 1 138 4 138 4 122 5 99 7 76 8 53 9 57 157 5 16 8 157 5 157 5 153 9 130 9 107 9 84 9 146 7 18 2 146 7 146 7 143 4 120 5 97 7 74 8 6750 72 184 3 17 1 153 1 128 5 104 0 79 5 168 5 18 7 147 1 122 8 98 6 74 3 67 166 0 16 9 166 0 160 5 140 4 115 9 91 4 151 6 18 3 151 6 150 8 133 2 108 9 84 7 62 ...

Page 43: ... 14 2 259 6 232 5 200 7 168 8 137 0 243 7 15 6 243 7 222 6 191 6 160 5 129 4 62 240 1 14 1 240 1 240 1 240 1 208 2 176 4 144 6 225 0 15 4 225 0 225 0 225 0 194 0 162 9 131 8 57 241 5 14 0 241 5 241 5 241 5 209 6 177 8 146 0 224 9 15 3 224 9 224 9 224 9 193 8 162 7 131 6 95 F 105 F 4375 77 238 5 17 2 104 0 84 9 65 9 222 3 19 0 92 0 77 9 59 4 72 220 9 17 0 135 9 116 9 97 9 78 9 205 9 18 7 128 5 110 ...

Page 44: ...55 4 127 1 98 7 179 4 21 7 179 4 179 4 150 5 121 4 92 3 62 185 5 19 9 185 5 185 5 180 8 152 4 124 1 95 7 174 5 21 6 174 5 174 5 168 7 139 6 110 5 81 4 57 184 0 19 9 184 0 184 0 183 1 154 7 126 3 97 9 173 2 21 6 173 2 173 2 171 8 142 7 113 6 84 5 7875 72 212 1 20 5 176 1 147 0 117 9 88 7 195 2 22 1 170 0 140 6 111 3 81 9 67 195 0 20 1 195 0 189 7 162 5 133 4 104 2 179 4 21 7 179 4 179 4 156 8 127 4...

Page 45: ...4 317 0 279 3 235 1 190 9 146 7 299 0 21 2 299 0 264 8 225 1 185 5 145 8 62 290 5 19 0 290 5 290 5 284 7 240 5 196 3 152 1 275 5 20 8 275 5 275 5 272 6 232 9 193 2 153 5 57 283 0 18 9 283 0 283 0 283 0 238 7 194 5 150 3 269 7 20 7 269 7 269 7 269 7 230 0 190 3 150 7 95 F 105 F 5000 77 300 4 23 6 122 6 101 7 80 9 280 0 26 0 115 7 95 0 74 3 72 277 6 23 2 160 1 139 3 118 4 97 5 260 0 25 4 153 5 132 7...

Page 46: ...213 3 184 5 155 6 126 8 230 3 29 1 230 3 207 4 178 5 149 7 120 8 62 227 6 26 5 227 6 227 6 223 7 194 9 166 0 137 2 212 0 28 6 212 0 212 0 212 0 185 7 156 8 127 9 57 228 7 26 6 228 7 228 7 225 1 196 2 167 4 138 5 215 7 28 8 215 7 215 7 211 6 182 7 153 8 124 9 9000 72 264 8 27 7 204 0 172 5 141 1 109 6 244 6 29 8 195 9 164 7 133 5 102 2 67 245 9 27 1 243 6 223 2 191 7 160 3 128 8 228 7 29 1 228 7 21...

Page 47: ...4 343 6 305 9 258 1 210 3 162 5 324 5 22 5 324 5 296 7 250 1 203 4 156 8 62 319 2 20 0 319 2 319 2 319 2 271 4 223 6 175 8 301 0 22 0 301 0 301 0 301 0 254 4 207 7 161 1 57 308 1 20 1 308 1 308 1 308 1 260 3 212 4 164 6 294 4 21 9 294 4 294 4 294 4 247 8 201 1 154 5 95 F 105 F 6250 77 303 0 25 1 125 0 96 6 68 2 287 2 27 1 154 1 129 0 101 8 72 281 7 24 6 167 8 139 3 110 9 82 5 267 0 26 8 184 2 157 ...

Page 48: ... 29 0 271 7 246 4 212 4 178 5 144 5 249 0 31 1 249 0 236 7 203 4 170 1 136 8 62 259 7 28 6 259 7 259 7 256 6 222 7 188 7 154 8 242 9 30 8 242 9 242 9 242 9 209 6 176 3 142 9 57 257 9 28 9 257 9 257 9 253 8 219 8 185 9 151 9 241 2 31 3 241 2 241 2 236 9 203 6 170 3 137 0 11250 72 286 6 29 7 271 2 238 8 198 7 158 5 261 6 32 0 261 6 252 8 212 7 172 7 67 264 8 29 6 264 8 252 2 216 2 176 0 135 9 241 6 ...

Page 49: ...ormance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 5 HP Field ...

Page 50: ... 4 85 6000 699 2 11 735 2 60 772 3 06 808 3 49 844 3 88 879 4 24 913 4 55 946 4 80 977 5 01 1007 5 15 1036 5 24 1062 5 25 6400 719 2 55 756 3 03 792 3 49 828 3 92 864 4 32 899 4 67 933 4 98 966 5 24 998 5 45 1028 5 59 1056 5 67 1083 5 68 6800 742 3 02 778 3 51 814 3 97 850 4 40 886 4 79 921 5 15 955 5 46 988 5 72 1020 5 92 1050 6 07 1078 6 15 1105 6 16 7200 765 3 54 802 4 03 838 4 49 874 4 92 910 ...

Page 51: ...97 14 35 1129 14 92 1160 15 47 1192 15 98 1223 16 47 1255 16 94 High Static 15 HP Drive Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 82 2 0 2 2 2 4...

Page 52: ...des gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 5 HP Field Supplied Driv...

Page 53: ... 53 1017 4 67 1045 4 74 1071 4 75 6000 734 2 25 770 2 70 806 3 13 841 3 53 877 3 90 911 4 23 944 4 52 977 4 77 1008 4 96 1038 5 09 1066 5 17 1092 5 18 6400 757 2 71 793 3 17 829 3 60 864 4 00 899 4 37 934 4 70 967 4 99 1000 5 23 1031 5 42 1060 5 56 1088 5 64 1114 5 65 6800 781 3 22 817 3 68 853 4 11 888 4 51 923 4 88 958 5 21 991 5 50 1024 5 74 1055 5 94 1085 6 07 1112 6 15 1139 6 16 7200 807 3 78...

Page 54: ... includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 82 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 10 HP Drive High Static 15 HP Drive 6600 1006 6 07 1039...

Page 55: ...Side Duct Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP ...

Page 56: ... 12200 1212 15 90 1244 16 34 1276 16 75 1308 17 14 High Static 15 HP Drive 15 HP Field Supplied Drive Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 ...

Page 57: ... 5 HP Field Supplied Drive ZR240 20 Ton Bottom Duct Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 ...

Page 58: ...8 10 48 1110 10 89 1141 11 28 1172 11 64 1203 11 99 1234 12 32 1265 12 64 1297 12 94 1330 13 24 1363 13 52 1398 13 79 1434 14 06 10600 1115 11 59 1147 12 00 1178 12 38 1209 12 75 1240 13 10 1271 13 43 1302 13 75 1334 14 05 1367 14 34 1400 14 62 1435 14 90 1472 15 17 11000 1153 12 75 1185 13 16 1216 13 55 1247 13 91 1278 14 26 1309 14 59 1340 14 91 1372 15 21 1405 15 51 1438 15 79 1473 16 06 1510 1...

Page 59: ...itional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 5 HP Field Supplied Drive Standard 5 HP Drive High Static 7 5 HP Drive 4400 636 0 65 672 1 14 709...

Page 60: ... 717 2 17 754 2 65 790 3 10 826 3 52 862 3 90 897 4 25 931 4 55 964 4 81 996 5 01 1026 5 15 1054 5 23 1081 5 24 6400 740 2 64 776 3 11 812 3 57 848 3 99 884 4 37 919 4 72 953 5 02 986 5 28 1018 5 48 1048 5 62 1076 5 70 1103 5 71 6800 763 3 15 800 3 63 836 4 08 872 4 50 908 4 88 943 5 23 977 5 53 1010 5 79 1042 5 99 1072 6 13 1100 6 21 1127 6 22 7200 789 3 71 825 4 18 861 4 63 898 5 05 933 5 44 968...

Page 61: ...35 1129 14 92 1160 15 47 1192 15 98 1223 16 47 1255 16 94 High Static 15 HP Drive Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 82 2 0 2 2 2 4 2 6 2...

Page 62: ...ional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 5 HP Field Supplied Drive Standard 5 HP Drive High Static 7 5 HP Drive 4400 661 0 74 697 1 19 733 1...

Page 63: ... 75 1089 4 76 6000 754 2 35 790 2 79 826 3 21 862 3 61 897 3 97 931 4 29 965 4 58 997 4 81 1028 5 00 1058 5 14 1086 5 21 1112 5 22 6400 779 2 85 814 3 29 850 3 71 886 4 11 921 4 47 955 4 79 989 5 08 1021 5 31 1052 5 50 1082 5 64 1110 5 71 1136 5 72 6800 804 3 39 840 3 84 876 4 26 912 4 65 947 5 01 981 5 34 1015 5 62 1047 5 86 1078 6 05 1108 6 18 1136 6 26 1162 6 27 7200 832 3 98 868 4 43 903 4 85 ...

Page 64: ...des gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 82 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 10 HP Drive High Static 15 HP Drive 6600 1006 6 07 1039 6 48 ...

Page 65: ...10 11 50 1VP60 BK090 905 950 990 1035 1075 1120 N A 300 25 ZR 7 5 8 63 1VP60 1B5V94 810 850 885 920 960 1000 N A 10 11 50 1VP75X 1B5V110 975 1005 1040 1070 1100 1135 1165 15 17 25 1VP75X 1B5V94 1140 1180 1215 1255 1290 1330 1365 Additional Static Resistance Size Tons Model CFM Cooling Only1 1 Add these values to the available static resistance in the respective Blower Performance Tables Economizer...

Page 66: ... HP motor is required 6 1150 RPM is within the range of the 30 40 HP drives but step 5 requires the 40 HP motor 7 Using the 40 HP motor and drive 5 5 turns open will achieve 1150 RPM Example Supply Air Blower Performance Air Flow CFM Available External Static Pressure IWG 3 0 3 4 3 8 4 2 4 6 5 0 5 4 5 8 6 2 6 6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 30 HP F...

Page 67: ...Air Size Tons Heat Size Supply Air CFM Cooling Heating Min Max Min Max 180 15 24 4500 7000 4500 7000 32 4500 7000 4500 7000 210 17 5 24 6000 8750 6000 8750 32 6000 8750 6000 8750 240 20 24 6000 9400 6000 9400 32 6000 9400 6000 9400 300 25 24 7500 12500 7500 12500 32 7500 12500 7500 12500 0 600 0 650 0 700 0 750 0 800 0 850 0 900 0 950 1 000 1 050 1 100 40 50 60 70 80 90 100 Air Temperature ºF Corr...

Page 68: ...0 4 1 BK110 BX85 5 1725 0 89 1 15 184T 5 2 6 4 1 1 8 1VP65 8 4 1 BK090 BX81 210 17 5 ZJ ZF 5 1725 0 89 1 15 184T 4 2 5 5 1 1 8 1VP60 10 4 1 3 16 BK110 BX78 7 5 1725 0 91 1 15 213T 4 2 5 5 1 3 8 1VP60 8 4 1 3 16 BK090 BX75 240 20 ZJ ZF 5 1725 0 89 1 15 184T 4 2 5 5 1 1 8 1VP60 10 4 1 3 16 BK110 BX78 7 5 1725 0 91 1 15 213T 4 2 5 5 1 3 8 1VP60 8 4 1 3 16 BK090 BX75 300 25 ZJ ZF 7 5 1725 0 91 1 15 21...

Page 69: ...sound propagation from a point source into the hemispheric free field The dBA values provided are to be used for reference only Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system This constitutes an exception to any specification or guarantee requiring a dBA value of sound data in any other form than sound power level r...

Page 70: ...0 1 1 7 2 0 0 None 44 3 50 E18 18 0 1 21 7 44 3 50 E36 36 0 2 43 3 63 1 70 E54 54 0 2 65 0 74 0 90 E72 72 0 2 86 6 95 6 110 575 3 60 6 4 40 10 0 0 9 5 9 0 0 None 36 7 40 E18 18 0 1 17 3 36 7 40 E36 36 0 2 34 6 50 7 60 E54 54 0 2 52 0 59 3 70 E72 72 0 2 69 3 76 7 90 210 17 5 208 3 60 16 7 120 26 0 2 1 15 4 0 0 None 94 8 110 E18 13 5 1 37 5 94 8 110 E36 27 0 2 74 9 112 9 125 E54 40 6 2 112 7 160 1 1...

Page 71: ...None 141 8 150 E18 13 5 1 37 5 141 8 150 E36 27 0 2 74 9 141 8 150 E54 40 6 2 112 7 175 9 200 E72 54 1 2 150 2 185 2 200 230 3 60 23 0 160 31 5 3 7 26 0 0 0 None 139 3 150 E18 18 0 1 43 3 139 3 150 E36 36 0 2 86 6 140 8 150 E54 54 0 2 129 9 162 4 175 E72 72 0 2 173 2 205 7 225 460 3 60 12 2 87 17 1 1 9 13 0 0 0 None 72 7 80 E18 18 0 1 21 7 72 7 80 E36 36 0 2 43 3 72 7 80 E54 54 0 2 65 0 81 2 90 E7...

Page 72: ... 8 110 E18 13 5 1 37 5 104 8 110 E36 27 0 2 74 9 125 4 150 E54 40 6 2 112 7 172 6 175 E72 54 1 2 150 2 181 9 200 230 3 60 16 7 120 26 0 2 1 14 4 10 0 None 103 8 110 E18 18 0 1 43 3 103 8 110 E36 36 0 2 86 6 138 8 150 E54 54 0 2 129 9 160 4 175 E72 72 0 2 173 2 203 7 225 460 3 60 8 7 60 15 5 1 1 7 2 5 0 None 53 6 60 E18 18 0 1 21 7 53 6 60 E36 36 0 2 43 3 69 4 70 E54 54 0 2 65 0 80 2 90 E72 72 0 2 ...

Page 73: ... 9 13 0 5 0 None 77 7 90 E18 18 0 1 21 7 77 7 90 E36 36 0 2 43 3 77 7 90 E54 54 0 2 65 0 87 5 90 E72 72 0 2 86 6 109 1 110 575 3 60 8 7 62 13 5 1 5 10 3 4 0 None 57 7 60 E18 18 0 1 17 3 57 7 60 E36 36 0 2 34 6 61 2 70 E54 54 0 2 52 0 69 8 70 E72 72 0 2 69 3 87 2 90 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZJ180 300 Standard Drive With Powered Convenience Outlet...

Page 74: ...00 2 110 E18 13 5 1 37 5 100 2 110 E36 27 0 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 16 7 120 26 0 2 1 20 0 0 0 None 100 2 110 E18 18 0 1 43 3 100 2 110 E36 36 0 2 86 6 133 3 150 E54 54 0 2 129 9 154 9 175 E72 72 0 2 173 2 198 2 225 460 3 60 8 7 60 15 5 1 1 10 0 0 0 None 51 7 60 E18 18 0 1 21 7 51 7 60 E36 36 0 2 43 3 66 6 70 E54 54 0 2 65 0 77 5 90 E72 72 0 ...

Page 75: ... 3 0 0 None 80 5 90 E18 18 0 1 21 7 80 5 90 E36 36 0 2 43 3 80 5 90 E54 54 0 2 65 0 89 1 100 E72 72 0 2 86 6 110 7 125 575 3 60 8 7 62 13 5 1 5 15 4 0 0 None 60 1 70 E18 18 0 1 17 3 60 1 70 E36 36 0 2 34 6 62 6 70 E54 54 0 2 52 0 71 2 80 E72 72 0 2 69 3 88 5 100 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZJ180 300 High Static Drive Without Powered Convenience Out...

Page 76: ...0 2 125 E18 13 5 1 37 5 110 2 125 E36 27 0 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 16 7 120 26 0 2 1 20 0 10 0 None 110 2 125 E18 18 0 1 43 3 110 2 125 E36 36 0 2 86 6 145 8 150 E54 54 0 2 129 9 167 4 175 E72 72 0 2 173 2 210 7 225 460 3 60 8 7 60 15 5 1 1 10 0 5 0 None 56 7 60 E18 18 0 1 21 7 56 7 60 E36 36 0 2 43 3 72 9 80 E54 54 0 2 65 0 83 7 90 E72 72 0 ...

Page 77: ...9 3 5 0 None 85 5 100 E18 18 0 1 21 7 85 5 100 E36 36 0 2 43 3 85 5 100 E54 54 0 2 65 0 95 3 110 E72 72 0 2 86 6 117 0 125 575 3 60 8 7 62 13 5 1 5 15 4 4 0 None 64 1 70 E18 18 0 1 17 3 64 1 70 E36 36 0 2 34 6 67 6 70 E54 54 0 2 52 0 76 2 90 E72 72 0 2 69 3 93 5 100 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZJ180 300 High Static Drive With Powered Convenience Ou...

Page 78: ...62 13 5 1 5 8 2 0 0 None 51 2 60 E18 18 0 1 17 3 51 2 60 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 ZJ300 Low Static Drive With Powered Convenience Outlet Size Tons Volt Compressors each OD Fan Motors each Supply Blower Motor Pwr Conv Outlet Electric Heat Option MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Dual Element Time Delay Type 3 HACR type...

Page 79: ...3 60 30 1 225 47 0 3 7 20 0 0 0 None 102 5 125 E18 13 5 1 37 5 102 5 125 E36 27 0 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 30 1 225 47 0 3 7 20 0 0 0 None 102 5 125 E18 18 0 1 43 3 102 5 125 E36 36 0 2 86 6 133 3 150 E54 54 0 2 129 9 154 9 175 E72 72 0 2 173 2 198 2 225 460 3 60 16 7 114 26 0 1 9 10 0 0 0 None 55 2 70 E18 18 0 1 21 7 55 2 70 E36 36 0 2 43 3 6...

Page 80: ... 1 225 47 0 3 7 20 0 10 0 None 112 5 125 E18 13 5 1 37 5 112 5 125 E36 27 0 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 30 1 225 47 0 3 7 20 0 10 0 None 112 5 125 E18 18 0 1 43 3 112 5 125 E36 36 0 2 86 6 145 8 150 E54 54 0 2 129 9 167 4 175 E72 72 0 2 173 2 210 7 225 460 3 60 16 7 114 26 0 1 9 10 0 5 0 None 60 2 70 E18 18 0 1 21 7 60 2 70 E36 36 0 2 43 3 72 9 8...

Page 81: ...30 1 225 47 0 3 7 28 0 0 0 None 109 1 125 E18 13 5 1 37 5 109 1 125 E36 27 0 2 74 9 126 9 150 E54 40 6 2 112 7 174 1 175 E72 54 1 2 150 2 183 4 200 230 3 60 30 1 225 47 0 3 7 26 6 0 0 None 109 1 125 E18 18 0 1 43 3 109 1 125 E36 36 0 2 86 6 141 5 150 E54 54 0 2 129 9 163 2 175 E72 72 0 2 173 2 206 5 225 460 3 60 16 7 114 26 0 1 9 13 3 0 0 None 58 5 70 E18 18 0 1 21 7 58 5 70 E36 36 0 2 43 3 70 8 8...

Page 82: ... 1 225 47 0 3 7 28 0 10 0 None 119 1 125 E18 13 5 1 37 5 119 1 125 E36 27 0 2 74 9 139 4 150 E54 40 6 2 112 7 186 6 200 E72 54 1 2 150 2 195 9 200 230 3 60 30 1 225 47 0 3 7 26 6 10 0 None 119 1 125 E18 18 0 1 43 3 119 1 125 E36 36 0 2 86 6 154 0 175 E54 54 0 2 129 9 175 7 200 E72 72 0 2 173 2 219 0 225 460 3 60 16 7 114 26 0 1 9 13 3 5 0 None 63 5 80 E18 18 0 1 21 7 63 5 80 E36 36 0 2 43 3 77 0 8...

Page 83: ...00 23 0 1 5 8 2 0 0 None 47 3 60 E18 18 0 1 17 3 47 3 60 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 ZR300 Low Static Drive With Powered Convenience Outlet Size Tons Volt Compressors each OD Fan Motors each Supply Blower Motor Pwr Conv Outlet Electric Heat Option MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Dual Element Time Delay Type 3 HACR type...

Page 84: ... 6 110 E18 13 5 1 37 5 85 6 110 E36 27 0 2 74 9 112 9 125 E54 40 6 2 112 7 160 1 175 E72 54 1 2 150 2 169 4 200 230 3 60 27 2 27 2 203 203 42 5 43 4 3 14 4 0 0 None 84 2 110 E18 18 0 1 43 3 84 2 110 E36 36 0 2 86 6 126 3 150 E54 54 0 2 129 9 147 9 175 E72 72 0 2 173 2 191 2 225 460 3 60 15 1 15 1 92 92 22 22 2 2 7 2 0 0 None 45 6 60 E18 18 0 1 21 7 45 6 60 E36 36 0 2 43 3 63 1 70 E54 54 0 2 65 0 7...

Page 85: ... 2 13 0 0 0 None 62 2 80 E18 18 0 1 21 7 62 2 80 E36 36 0 2 43 3 70 4 80 E54 54 0 2 65 0 81 2 90 E72 72 0 2 86 6 102 9 110 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 10 3 0 0 None 50 2 60 E18 18 0 1 17 3 50 2 60 E36 36 0 2 34 6 56 2 60 E54 54 0 2 52 0 64 8 70 E72 72 0 2 69 3 82 2 90 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZF180 300 Standard Drive Without Powered...

Page 86: ...0 E18 13 5 1 37 5 95 6 110 E36 27 0 2 74 9 125 4 150 E54 40 6 2 112 7 172 6 175 E72 54 1 2 150 2 181 9 200 230 3 60 27 2 27 2 203 203 42 5 43 4 3 14 4 10 0 None 94 2 110 E18 18 0 1 43 3 94 2 110 E36 36 0 2 86 6 138 8 150 E54 54 0 2 129 9 160 4 175 E72 72 0 2 173 2 203 7 225 460 3 60 15 1 15 1 92 92 22 22 2 2 7 2 5 0 None 50 6 60 E18 18 0 1 21 7 50 6 60 E36 36 0 2 43 3 69 4 70 E54 54 0 2 65 0 80 2 ...

Page 87: ...9 2 2 13 0 5 0 None 67 2 80 E18 18 0 1 21 7 67 2 80 E36 36 0 2 43 3 76 6 80 E54 54 0 2 65 0 87 5 90 E72 72 0 2 86 6 109 1 110 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 10 3 4 0 None 54 2 70 E18 18 0 1 17 3 54 2 70 E36 36 0 2 34 6 61 2 70 E54 54 0 2 52 0 69 8 70 E72 72 0 2 69 3 87 2 90 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZF180 300 Standard Drive With Powered...

Page 88: ...E18 13 5 1 37 5 90 2 110 E36 27 0 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 27 2 27 2 203 203 42 5 42 5 4 3 20 0 0 0 None 89 8 110 E18 18 0 1 43 3 89 8 110 E36 36 0 2 86 6 133 3 150 E54 54 0 2 129 9 154 9 175 E72 72 0 2 173 2 198 2 225 460 3 60 15 1 15 1 92 92 22 22 2 2 10 0 0 0 None 48 4 60 E18 18 0 1 21 7 48 4 60 E36 36 0 2 43 3 66 6 70 E54 54 0 2 65 0 77 5 ...

Page 89: ... 2 19 3 0 0 None 68 5 80 E18 18 0 1 21 7 68 5 80 E36 36 0 2 43 3 78 3 80 E54 54 0 2 65 0 89 1 100 E72 72 0 2 86 6 110 7 125 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 15 4 0 0 None 55 3 70 E18 18 0 1 17 3 55 3 70 E36 36 0 2 34 6 62 6 70 E54 54 0 2 52 0 71 2 80 E72 72 0 2 69 3 88 5 100 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZF180 300 Hi Static Drive Without Powe...

Page 90: ...E18 13 5 1 37 5 100 2 125 E36 27 0 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 27 2 27 2 203 203 42 5 42 5 4 3 20 0 10 0 None 99 8 125 E18 18 0 1 43 3 99 8 125 E36 36 0 2 86 6 145 8 150 E54 54 0 2 129 9 167 4 175 E72 72 0 2 173 2 210 7 225 460 3 60 15 1 15 1 92 92 22 22 2 2 10 0 5 0 None 53 4 60 E18 18 0 1 21 7 53 4 60 E36 36 0 2 43 3 72 9 80 E54 54 0 2 65 0 83 ...

Page 91: ... 2 2 19 3 5 0 None 73 5 90 E18 18 0 1 21 7 73 5 90 E36 36 0 2 43 3 84 5 90 E54 54 0 2 65 0 95 3 110 E72 72 0 2 86 6 117 0 125 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 15 4 4 0 None 59 3 70 E18 18 0 1 17 3 59 3 70 E36 36 0 2 34 6 67 6 70 E54 54 0 2 52 0 76 2 90 E72 72 0 2 69 3 93 5 100 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC ZF180 300 Hi Static Drive With Power...

Page 92: ...23 7 24 1 7 8 2 0 0 None 48 1 60 E18 18 0 1 17 3 48 1 60 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 ZF180 300 Low Static Drive With Powered Convenience Outlet Size Tons Volt Compressors each OD Fan Motors each Supply Blower Motor Pwr Conv Outlet Electric Heat Option MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Dual Element Time Delay Type 3 HACR ...

Page 93: ...2 4 Second stage heating not required on single stage heating units Jumper is required if there is no Smoke Detector circuit Jumper is required for any combination of R RC or RH 5 5 OCC is an output from the thermostat to indicate the Occupied condition X is an input to the thermostat to display Error Status conditions Y3 Y4 3 W2 Y1 G OCC P P1 Y2 X R SD C EXPANSION BOARD TERMINAL BLOCK W1 Y3 Y4 2 ...

Page 94: ...rammable Thermostat 2ET0770010024 includes subbase 2 Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back position 3 TO REMOTE SENSOR 2ET04701324 IF USED DEHUMIDISTAT Dehumidistat closes on rise in humidity RC RH Y1 Y2 G W1 W2 C C W2 W1 G Y2 Y1 R OCC RCB REHEAT CONTROL BOARD HUM TERMINAL BLOCK RH 1 1 2 3 4 1 DEHUMIDISTAT De...

Page 95: ...RMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage cooling units Jumper is required if there is no Smoke Detector circuit Jumper is required for any combination of R RC or RH 6 5 5 6 OCC is an output from the thermostat to indicate the Occupied condition X is an input to the th...

Page 96: ...28 313 210 17 5 ZJ 2670 2665 85 25 44 477 797 870 520 293 401 580 633 437 320 240 20 ZJ 2702 2697 85 05 44 485 805 878 529 298 406 585 638 443 326 300 25 ZJ 2788 2783 85 25 44 498 833 908 544 306 419 606 661 457 334 180 15 ZR 2365 2360 85 25 44 422 706 770 461 260 355 514 561 387 284 240 20 ZR 2665 2660 85 05 44 478 794 866 522 294 401 477 630 437 321 300 25 ZR 2765 2760 85 25 44 494 826 901 539 3...

Page 97: ...f tube heat exchangers available 8 tube 240 240 Double Wall 260 260 Motorized Damper 150 150 Barometric Damper 50 45 Econ Motorized Damper Rain Hood 60 55 Econ Power Exhaust Rain Hood 95 90 Wood Skid 220 220 Roof Curb 190 185 Hot Gas Bypass 10 10 Supply Fan VFD See Supply Fan VFD Weights Supply Fan VFD Weights in Lbs Supply Fan Motor 230V 460V 575V W O Manual Bypass 5 0 hp 25 25 30 7 5 hp 30 30 30...

Page 98: ...ED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS See detail Y 92 46 5 8 35 1 4 33 2 3 4 3 3 4 B POWER WIRING ENTRY BOTTOM SUPPLY AND RETURN AIR OPENINGS See Note A CONTROL WIRING ENTRY 21 1 2 11 1 8 D GAS SUPPLY ENTRY UNIT BASE RAILS Shown separately to illustrate RETURN AIR Bottom Duct openings Power and Gas Piping Connection location NOTE For curb mounted units refer to the curb hanger dimensi...

Page 99: ...LOCATION BLOWER COMPARTMENT ACCESS Auxiliary DOT PLUG For pressure Drop Reading FRONT VIEW CONTROL BOX ACCESS 21 5 9 3 4 11 1 2 2 3 4 21 1 2 33 35 5 7 8 46 5 8 7 1 8 6 3 8 VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD GAS HEAT ACCESS C GAS SUPPLY ENTRY 46 5 8 11 1 8 D GAS SUPPLY ENTRY RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Economizer 92 24 1 4 15 Ton 35 1 4 17 5 thru 25 Ton 125 1 4 15 Ton...

Page 100: ... the unit includes a power exhaust option The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air compartments with the accessory flange kit panels 2 Connect ductwork to the flanges on those panels Outdoor Air Supply Air Return Air 40 1 2 39 5 8 Outdoor Air...

Page 101: ...300 Unit Clearances Direction Distance in Direction Distance in Top1 1 Units must be installed outdoors Over hanging structure or shrubs should not obscure condenser air discharge outlet 72 With 36 Maximum Horizontal Overhang For Condenser Air Discharge Right 36 Front 36 Bottom2 2 Units may be installed on combustible floors made from wood or class A B or C roof covering materials 0 Rear 24 W O Ec...

Page 102: ... 1 The 2 space between the ducts allows for jumping an existing roof joist 2 The 58 1 2 overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside the curb ZJ ZR ZF180 300 Cut Away of Roof Curb 25 1 4 ...

Page 103: ...251934 YTG G 0708 Johnson Controls Unitary Products 103 ZJ ZR ZF180 300 Typical Installation Roof Jack Installation Roof Curb Installation Slab On Ground Installation ...

Page 104: ... change without notice Printed in U S A 251934 YTG G 0708 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 251934 YTG F 0807 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...