5188235-YIM-B-1016
40
Johnson Controls Unitary Products
Jade Economizer Interface Overview
Units with Simplicity Lite Controls will have a field installed
(Jade) Economizer Kit Offered.
This section describes how to use the Economizer’s user
interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
The user interface consists of an LCD display and a 4-button
keypad on the front of the Economizer module. The LCD is a 16
character by 2 line dot matrix display.
Figure 20: Jade Economizer LCD and Keypad Layout.
Keypad
The four navigation buttons illustrated in Fig. 20 are used to
scroll through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Using the Keypad with Menus
To use the keypad when working with menus:
R
24V~
24 VAC hot supplied for the building pressure
sensor
Connects through circuit trace to 24V~ IN pin HOT
IN8
BLDG
PRES
0-5 VDC positive input from the Building
Pressure sensor
BldgPres parameter reports input status (-.250-.250”/w/-.062-
.062kPa). Used for modulating power exhaust functions when
ExFType selection is Modulating Damper or Variable Frequency
Fan.
C
COM
24 VAC common/0-5 VDC negative for the
building pressure sensor
Connects through circuit trace to 24V~ IN pin COM
BINARY INPUTS at right on lower edge of economizer board
IN9
PURGE
24 VAC hot input from the PURGE dry contact
Purge parameter reports input status (False with 0 VAC input-
True with 24 VAC input). When Purge status is True, heating and
cooling operation is prevented, the indoor blower and power
exhaust fan operate, the economizer actuator is positioned to
100%.
24V~
24 VAC hot supplied for the purge dry contact
Connects through circuit trace to 24V~ IN pin HOT
IN10
EX VFD
FLT
24 VAC hot input from the power Exhaust
Variable Frequency Drive Fault contact
ExFanVFDFlt parameter reports input status (Normal with 0 VAC
input-Alarm with 24 VAC input) when ExFType selection is
Variable Frequency Fan. When ExFanVFDFlt status is Alarm,
EX-FAN fan output is prevented.
24V~
24 VAC hot supplied for the power exhaust
variable frequency drive fault contact
Connects through circuit trace to 24V~ IN pin HOT
1. When wiring unit and other devices using the SA Bus and FC Bus, see Table 33.
Table 12: Smart Equipment™ Economizer Board Details (Continued)
Board
Label
Cover
Label
Description
Function & Comments
MENU UP
(EXIT)
BUTTON
SCROLL
(UP/DOWN)
BUTTONS
SELECT (ENTER)
BUTTONS
2 LINE
LCD