background image

20

ENGLISH

DEFROSTING OPERATION (Available for heating only)

1.  Condition to start defrosting: Units will switch to defrosting 

mode when either of the following conditions is met.

a.  Unit  has  been  running  under T3  <  0ºC  for  40 

minutes and T3 < -3ºC for 3 minutes.

b.  Unit has been running at high temperature protection 

mode*  for  90  minutes.  (*High  temperature 

protection mode: when coil temperature of indoor 

unit reaches 55°C, outdoor unit will turn off external 

unit fan but still keep compressor running).

2.  Condition to stop defrosting: Units will switch back to 

heating mode when either of the following conditions 

is met.

a.  Unit has been running at defrosting mode for 10 

minutes.

b.  T3 > 20

 

ºC

Remark:

 T3 is coil temperature of outdoor units.

T3 (°C)

3 min

40 min

Heating mode

Defrosting mode

Time 

Elapsed 

(min)

Starting Defrosting Mode under condition a.

SERVICE AND MAINTENANCE

The units are designed to operate for long periods of time with a minimum of maintenance. However, the following 

operations must be performed regularly.

COMPONENT

MAINTENANCE OPERATIONS

RECOMMENDED FREQUENCY

Air filter

1 -  Clean  with  a  vacuum  cleaner  or  tap  gently 

then wash in warm water (40°C) with a mild 

detergent.

2 -  Rinse and dry before replacing on unit.

3 -  Never use petrol, alcohol or any other chemi-

cal product.

Every month or more often if

necessary.

Unit casing

1 -  Remove dust from the front panel with a soft 

duster or wipe a damp cloth with a mild soap 

solution.

2 -  Never use petrol, alcohol or any other chemi-

cal product.

Every month or more often if

necessary.

Drain pan and evacu-

ation piping

1 -  Clean and check for obstructions.

Each season before start up.

Indoor / Outdoor coils

1 -  Check  condition  and  remove  dust  from  be-

tween coil fins.

Each season before start up.

Compressor

1 -  No maintenance required.

J368-EN.indd   20

2/1/07   9:41:36 AM

Summary of Contents for YUKC 07-18

Page 1: ...Installation Owner s Manual MODELS YUHC 18 60 YUKC 07 18 MINISPLIT AIR BLOWER EN 035M00065 000 J368 EN indd 1 2 1 07 9 40 52 AM...

Page 2: ...tomers with consistent reli ability in product service and support through superior quality service culture and distinctive technology Standard Refrigerant R 410A Model 18 24 30 60 Set YUHCxxFUAAAR YU...

Page 3: ...le or spill water or liquids on unit DANGER To prevent electric shock turn off the power or disconnect the power supply plug before beginning any cleaning or other routine maintenance Follow the direc...

Page 4: ...anual are for explanation purpose only They may be sightly different from the air conditioner you purchased The actual shape shall prevail OUTDOOR UNIT INDOOR UNIT DISPLAY PANEL I Infrared signal rece...

Page 5: ...Ph 1 1 1 1 1 1 Fan Air ow m3 h 1 160 1 460 2 070 2 070 2 400 2 800 Input Power W 117 170 118 118 118 227 Running Current A 0 53 0 77 0 54 0 54 0 54 1 03 Dimension Height mm 300 300 300 300 300 320 Wi...

Page 6: ...52 Material Type Innergroove tube Coil length x height x width mm 800 254 66 800 254 66 1 150 254 66 1 150 254 66 1 150 305 66 Indoor air ow Hi Me Lo m3 h 1 020 870 700 1 275 1 170 1 030 2 070 1 950 1...

Page 7: ...5 650 560 930 830 660 Indoor coil Number of rows 2 2 2 2 Fin spacing mm 1 5 1 5 1 5 1 7 Fin type Hydrophilic aluminium Tube outside dia mm 7 7 7 9 53 Tube Material Innergroove tube Coil length x heigh...

Page 8: ...27 000 30 000 W 2 638 4 103 6 155 2 900 4 100 7 000 7 900 8 792 Input W 1 300 1 600 2 038 1 300 1 600 2 100 2 750 2 739 Rated current A 6 3 7 8 11 0 6 3 7 8 11 0 13 2 13 2 Max input W 3 200 3 200 Max...

Page 9: ...NS 845 990 624 181 4 336 4 400 1 245 360 940 650 695 960 360 235 860 330 125 335 351 2 135 560 1 141 5 313 300 895 590 163 301 5 YUJC 18 YUJC 24 YUJC 30 36 YUJC 48 60 RRJC 18 27 310 300 520 688 790 J3...

Page 10: ...Installation place The indoor unit must be installed such that there is no short circuit of the cool discharge Comply to the installation clearance recommended Do not put the indoor unit where there i...

Page 11: ...t of refrigerant pipe Connecting point of drain pipe Gas side F Ceiling hole 470 450 Panel 500 Dust proof net Additional purchase Canvas air passage Additional purchase Panel Additional purchase 298 1...

Page 12: ...205 300 I I Back panel layout A 250 320 127 N 250x393 8 Main body 800 300 720 630 Connecting point of cold medium pipe Air side F Connecting point of drain pipe Ceiling hole 470 450 Panel 500 Dust pr...

Page 13: ...ibed in the installation chart does not mean that the same is applicable to the situation of an airtight Leave open two of three directions A B C CAUTIONS Chart 1 NECESSARY ROOM FOR INSTALLATION AND M...

Page 14: ...s or other objects Do not lean it more than 45 and do not lay it sidelong Please fasten the feet of this unit with bolts rmly to prevent it from collapsing in case of earthquake or strong wind Make co...

Page 15: ...lude a large number of oil traps it may be necessary to adjust to compressor charge NOTES Unit size 18 24 30 36 48 60 m 30 30 30 30 30 30 REFRIGERANT PIPING CONNECTIONS Refrigerant charge to be added...

Page 16: ...4 0 0 1 5 0 0 1 0 5 0 4 0 3 0 6 0 P a 9 0 8 0 7 0 m 3 1 5 0 0 1 6 0 0 1 7 0 0 1 8 0 0 2 0 1 9 0 0 2 0 0 0 1 0 5 0 4 0 3 0 6 0 P a 9 0 8 0 7 0 m 3 1 8 0 0 1 9 0 0 2 0 0 0 2 1 0 0 2 0 2 2 0 0 2 3 0 0 1...

Page 17: ...ctions do apply for products like washing machines air conditioner or electrical ovens 4 For power details of the air conditioner refer to the rating plate of the product 5 For any question contact yo...

Page 18: ...18 ENGLISH YUKC 07 YUKC 09 YUKC 12 YUKC 18 RRJC 18 RRJC 27 A F IPM PFC J368 EN indd 18 2 1 07 9 41 26 AM...

Page 19: ...INDOOR UNIT L N Power supply Power supply For 18 000 24 000 Btu h 1 Phase 1 Phase 380 415V 5 core cable 5x2 5mm 2 3 core sheild cable OUTDOOR UNIT Power supply 3 Phase 220 240V 3 core cable 3x2 5mm 2...

Page 20: ...ing Defrosting Mode under condition a SERVICE AND MAINTENANCE The units are designed to operate for long periods of time with a minimum of maintenance However the following operations must be performe...

Page 21: ...unit This is a normal condition when the air conditioner has not been used for a long time or during rst use of the unit 5 A peculiar smell comes out from the indoor unit This is caused by the indoor...

Page 22: ...you started the sys tem 1 Remove charge repair evacu ate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs con tinuously 1 Thermostat ad...

Page 23: ...move all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be reused if appropriate or returned to the manufactu...

Reviews: