Outdoor unit

1.Connection of pipes

2.Attaching Drain-Elbow

To bend a pipe, give the roundness as large as possible not to crush the pipe

Connecting the pipe of gas side first makes working easier.

The max vertical distance between the indoor unit and the outdoor unit is 5 m.

 If the drain-elbow is used, please attach it as

 figure. (Note: Only for heat pump unit.)

Half union

Flare nut

Spanner

Torque wrench

4

Outdoor unit

Forced fastening without careful centering

may damage the threads and cause a

leakage of gas.

Be careful that matters, such as wastes of sands, etc. 

shall not enter the pipe.

3.Purging Method:

Push the air out of the indoor unit and piping as followes:

Tighten the caps on the valves with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 20g or 60g(only for 

 

24K) refrigerant shall be 

 added per exceeding meter. Charge according to the following list. 

Piping length

Additional amount

5m

7m

No need

40g

10m

100g

for  7K   9K  12K  18K

for  24K

Max. Length:       for 7K 9K

      : A=7m

                            for 12K              : A=10m

                            for 18K  24K      :  A=20m

Max.Elevation: for  7K 9K 12K

: B=5m

for 18K 24K        : B=10m

Piping length

Additional amount

5m

7m

No need

120g

10m

300g

20m

900g

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

B

A

C

Outdoor unit

Indoor unit

Oil trap

A

B

CAUTION

In case more than 5 metres

oil trap

should be installed every 5~7m.

C

Pipe Diameter   (     )

Liquid side  6.35mm(1/4")

Gas side  9.52mm(3/8")

Fastening torque

18N.m

40N.m

Gas side  12.7mm(1/2")

50N.m

Gas side  15.88mm(5/8")

60N.m

Liquid side  9.52mm(3/8")

 40N.m

Summary of Contents for YSCA07FSAADA

Page 1: ...INSTALLATION MANUAL Mini Split Air Conditioner YSCA YSHA07 24AADA ...

Page 2: ......

Page 3: ...ng insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the indoor unit and the floor should be more than 2m A G Attention must be paid to the rising up of drain hose m c 5 n a h t e r o m m c 0 1 n a h t e r o m m c 0 1 n a h t e r o m A C No Accessory parts Remote co...

Page 4: ...temporarily fasten the plate with one steel nail 2 Make sure once more the proper level of the plate by hanging a thread with a weight from the central top of the plate then fasten securely the plate with the attachment steel nail 3 Find the wall hole location A using a measuring tape Make a hole of 60 mm in diameter slightly descending to outside the wall Install piping hole cover and seal it off...

Page 5: ...re installing the indoor unit Insert the cable from the back side of the unit then pull it out on the front side Loosen the screws and insert the cable ends fully into terminal block then tighten the screws Pull the cable slightly to make sure the cables have been properly inserted and tightened After the cable connection never fail to fasten the connected cable with the wiring cover Note When con...

Page 6: ...es Tighten the caps on the valves with specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 20g or 60g only for 24K refrigerant shall be added per exceeding meter Charge according to the following list Piping length Additional amount 5m 7m No need 40g 10m 100g for 7K 9K 12K 18K for 24K Max Length for 7K 9K A 7m for 12K A 10m for 18K 24K A 20m Max ...

Page 7: ......

Page 8: ...www johnsoncontrols com Form No 035H00002 000 2010 Johnson Controls Inc Johnson Controls se reserva el derecho de cambiar las características del produc to sin previa notificación ...

Reviews: