Selection of pipe

To this unit, both liquid and gas pipes shall be insulated
as they become Iow temperature in operation.
Use optional parts for piping set or pipes covered with
equivalent insulation material.

2

Liquid pipe ( )

For   07K  09K 

6.35mm(1/4")

Gas pipe   (    )

9.52mm(3/8")

For 12K  18K  

12.7mm(1/2")

6.35mm(1/4")

07K , 09 K , 12 K

1.Fitting of the Mounting Plate and Positioning of the wall Hole

2.Making a Hole on the Wall and Fitting the Piping Hole Cover

When the mounting plate is first fixed

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be

   fixed against the wall, then temporarily fasten the plate with one steel nail.

2. Make sure once more the proper level of the plate, by hanging a thread with a weight from

    the central top of the plate, then fasten securely the plate with the attachment steel nail.

3. Find the wall hole location A using a measuring tape

Make a hole of 60 mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation

Indoor unit

(Section of wall hole)

Piping hole pipe

Outdoor side

Thickness

of wall

Indoor side

Wall hole

60mm

G

A=145mm

B= 60mm

30mm

60mm

30mm

30mm

Floor fixing dimensions

of the outdoor unit

(Unit:mm)

140

500

140

256

Floor fixing dimensions

of the outdoor unit

(Unit:mm)

140

140

415

280

15.88mm(5/8")

9.52mm(3/8")

For  24K

A=145mm

B= 60mm

A=145mm

B=

18 K

24 K

07K , 09 K , 12 K

18 K

24 K

Summary of Contents for YSCA07FSAADA

Page 1: ...INSTALLATION MANUAL Mini Split Air Conditioner YSCA YSHA07 24AADA ...

Page 2: ......

Page 3: ...ng insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the indoor unit and the floor should be more than 2m A G Attention must be paid to the rising up of drain hose m c 5 n a h t e r o m m c 0 1 n a h t e r o m m c 0 1 n a h t e r o m A C No Accessory parts Remote co...

Page 4: ...temporarily fasten the plate with one steel nail 2 Make sure once more the proper level of the plate by hanging a thread with a weight from the central top of the plate then fasten securely the plate with the attachment steel nail 3 Find the wall hole location A using a measuring tape Make a hole of 60 mm in diameter slightly descending to outside the wall Install piping hole cover and seal it off...

Page 5: ...re installing the indoor unit Insert the cable from the back side of the unit then pull it out on the front side Loosen the screws and insert the cable ends fully into terminal block then tighten the screws Pull the cable slightly to make sure the cables have been properly inserted and tightened After the cable connection never fail to fasten the connected cable with the wiring cover Note When con...

Page 6: ...es Tighten the caps on the valves with specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 20g or 60g only for 24K refrigerant shall be added per exceeding meter Charge according to the following list Piping length Additional amount 5m 7m No need 40g 10m 100g for 7K 9K 12K 18K for 24K Max Length for 7K 9K A 7m for 12K A 10m for 18K 24K A 20m Max ...

Page 7: ......