![background image](http://html2.mh-extra.com/html/york/ys/ys_owners-manual_4772859031.webp)
1
JOHNSON CONTROLS
FORM 160.80-EG1 (808)
S - S5 COMPRESSOR
R- & R-1a UNITS
(50 and 60 Hz)
Refer to Tables 6 and 7 on pages 26 & 27 for valid compressor/shell/motor combinations.
1. All dimensions are approximate. Certified dimensions are available on request.
2. Determine overall unit length by adding water box depth from table below to tube sheet length:
3. Unit height includes steel mounting plates under tube sheets. To determine overall installed height,
add 7/8” for neoprene isolators (1” for optional spring isolators).
NOTES:
dIMEnsIon
s4 CoMPrEssor
s4 and s5 CoMPrEssor
shELL CodEs (EVaPorator – CondEnsEr)
d-C
d-d
E-E
E-F
F-E
F-F
a
6’–2”
6’–2”
6’–2”
6’–4-1/2”
6’–6-1/2”
6’–9”
a
1
6’–9-7/8”
6’–9-7/8”
6’–9-7/8”
7’–0-3/8”
7’–3-5/8”
7’–2-5/8”
a
2
6’–3-3/8”
6’–3-3/8”
—
—
—
—
B – oVEraLL hEIGht
3
7’–9-1/8”
7’–9-1/8”
7’–9-1/8”
8’–2-1/4”
8’–2-1/4”
8’–2-1/4”
C – CooLEr C/L
1’–7-3/4”
1’–7-3/4”
1’–7-3/4”
1’–7-3/4”
1’–10”
1’–10”
d – CondEnsEr C/L
1’–5-1/4”
1’–5-1/4”
1’–5-1/4”
1’–6-1/2”
1’–5-1/4”
1’–6-1/2”
rEFrIGErant rELIEF VaLVE ConnECtIons
VEssEL
SIZE
EVaPorator
CondEnsEr
oIL sEParator
1” FPT SINGLE
1” FPT DUAL
1” FPT DUAL & 2” NOM RUPTURE DISK
EVaPorator CodE
CondEnsEr CodE
tYPE CoMPaCt WatEr BoX
d
E
F
d
E
F
RETURN BOX
WITH VICTAULIC CONN.
0’–5-1/2” 0’–5-1/2” 0’–7-3/4” 0’–5-1/4” 0’–5-1/4” 0’–7-5/8”
1’–1-7/8” 1’–1-7/8” 1’–3-1/8” 1’–1-7/8” 1’–1-7/8” 1’–3-1/8”
WITH FLANGED CONN.
1’–2-3/8” 1’–2-3/8” 1’–3-5/8” 1’–2-3/8” 1’–2-3/8” 1’–3-5/8”