FORM 160.81-O1 (1020)
ISSUE DATE 10/05/2020
101
JOHNSON CONTROLS
SECTION 4 - PRINTERS
4
FIGURE 36 -
SAMPLE PRINTOUT (SETPOINT REPORT)
YORK SETPOINTS
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 21 Jun 1999 1:27:39 PM
Software Versions
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Controls = C.MLM.05.02.102
BIOS = C.MLM.00.03
Kernel = 0.18 GUI = 0.32
SIO = 0.22
GPIC = 0.05
SSS [Skip if Motor Type is not Serial SSS] = C.SSS.01.01
System Information
–––––––––––––––––––––––––––––––––––––––––––––––––––––
System Language
= English
Data Display Mode
= English
Control Source
= Local
Remote Analog Input Range
= 0 – 10 Volts
Clock
= Enabled
Flow Switch
= Analog
Jumper Settings
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Chilled Liquid Pump Operation
= Standard
Anti-Recycle
= Enabled
Power Failure Restart
= Auto
Liquid Type
= Water
Motor Type
= EM
Printer Setup
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Automatic Printer Logging
= Disabled
Log Start Time
= 12:00 am
Output Interval
= 60 Min
Printer Type
= Okidata
Baud
= 9600 Baud
Data Bits
= 8 Bits
Parity
= None
Stop Bits
= 1 Bit
COM 2 Setup
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Baud
= 19200 Baud
Data Bits
= 8 Bits
Parity
= Odd
Stop Bits
= 1 Bit
Evaporator
–––––––––––––––––––––––––––––––––––––––––––––––––––––
Leaving Chilled Local Setpoint
= 45.0 ~F
Leaving Chilled ISN Setpoint
= 45.0 ~F
Leaving Chilled Modem Setpoint
= 45.0 ~F
Leaving Chilled Analog Setpoint
= 45.0 ~F
Leaving Chilled Digital Setpoint
= 45.0 ~F
Period
= 10 Sec
Error
= 1.5 ~F
Rate
= 2.5 ~F/S
Max Load Pulse
= 1.5 Sec
Max Unload Pulse
= 1.5 Sec
Remote Range
= 10.0 ~F
Restart Offset
= 0.0 ~F
Restart Setpoint
= 45.0 ~F
Shutdown Offset
= 4.0 ~F
Shutdown Setpoint
= 41.0 ~F
Brine Low Evaporator Cutout
= 25.0 Psig
Ice Storage
= Off
Offset
= 0
Condenser
––––––––––––––––––––––––––––––––––––––––––––––––––––––
High Pressure Warning Threshold
= 44.9 Psig
Drop Leg
= Enabled Freeze
Warning
= Disabled
Freeze Time
= 30 Min
[Skip the following section if Hot Gas Bypass is not enabled]
Hot Gas
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Hot Gas
= Disabled Off
Setpoint
= 2.0 ~F
On Setpoint
= 1.0 ~F
Oil Sump
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Auto Zero
= Enable
Compressor
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Maximum Load Temperature
= 70.0 ~F
Maximum Load FLA
= 60 %
Motor FLA Limit
= 15 %
Liquid Injection Threshold
= 130.0 ~F
[Skip the following section if Liquid Level is not enabled] Refrigerant
Level Control
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Level Control
= Enabled
Setpoint
= 50 %
Valve Preset Time
= 45 Sec
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
[Skip the following section if Motor Type is not Mod A SSS] Liquid-
Cooled Solid State Starter
––––––––––––––––––––––––––––––––––––––––––––––––––––––
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %