18
JOHNSON CONTROLS
FORM 155.19-EG3 (1011)
Nozzle Arrangement 14SC
TOWER WATER NOZZLE ARRANGEMENTS
NOZZLE SIZES
*Number of passes refers to the number of absorber passes only. The condenser is always one pass with nozzle sizes that match the absorber.
NOTES:
1. Choose desired nozzle arrangement – water boxes are not interchangeable.
2. Standard water nozzles are furnished as welding stub-outs with Victualic grooves, allowing the option of welding, flanges, or the use of Victualic
couplings. Factory installed, class 150 (ANSI B16.5, round slip on, forged carbon steel with 1/16” raised face), water flanged nozzles are optional.
Companion flanges, nuts, bolts, and gaskets are not furnished.
3. Connected piping should allow for removal of compact water box for tube access and cleaning.
4. Tower water must enter the absorber first for proper performance.
EVAPORATOR NOZZLE ARRANGEMENTS
STEAM INLET
OPPOSITE END
ABSORB. (IN)
COND. (OUT)
1,3
C1
E
F
C2
H
G
2
C3
E
G
C4
H
F
NO. OF ABS.
PASSES
NOZZLE
ARRANGEMENT
NO. OF PASSES
(IN)
(OUT)
3
E1
A
D
E4
C
B
2,4
E5
A
B
E7
C
D
NOZZLE
ARRANGEMENT
YPC-ST
EVAPORATOR
ABS./COND.
NUMBER OF PASSES
2
3
4
1*
2*
3*
14SC
6”
6”
4”
6”
6”
4”