background image

TROUBLESHOOTING GUIDE

Problem

Probable cause

Remedy

A.

The air conditioner does not run.

1.

Power Failure.

2.

Fuse blown or circuit breaker open.

3.

V

oltage is too low

.

4.

Faulty contactor or relay

.

5.

Electrical connections loose.

6.

Thermostat adjustment too low (in heating mode) or too high 

(in cooling mode).

7.

Faulty Capacitor

.

8.

Incorrect wiring, terminal loose.

9.

Pressure switch tripped.

1.

W

ait for Power resume.

2.

Replace the fuse or reset the breaker

.

3.

Find the cause and fix it.

4.

Replace the faulty component.

5.

Retighten the connection.

6.

Check

Thermostat setting.

7.

Find the cause then replace Capacitor

.

8.

Check and retighten.

9.

Find the cause b

efore reset.

B.

The outdoor fan runs but

the

compressor will not start.

1.

Motor winding cut or grounded.

2.

Faulty Capacitor

.

1.

Check the wiring and the compressor winding resistance.

2.

Fin

d the cause then replace Capacitor

.

C.

There is insufficient heating or

cooling.

1.

There is a gas leak.

2.

Liquid and gas line insulated together

.

3.

The room was probably very hot (cool) when you started the system.

1.

Remove charge, repair

, evacuate and recharge.

2.

Insulate them separately

.

3.

W

ait while unit ha

s enough time to cool the room.

D.

The compressor run continuously

.

1.

Thermostat adjustment too low (in heating mode) or too high

(in cooling mode).

2.

Faulty fan.

3.

Refrigerant charge too low

, leak.

4.

Air or incondensables in refrigerant circuit.

1.

Check

Thermostat setting.

2.

Check condenser air circulation.

3.

Find leak, repair and recharge.

4.

Remove

charge, evacuate and recharge.

E.

The compressor starts but

shuts

down quickly

.

1.

Too much or too little refrigerant.

2.

Faulty compressor

.

3.

Air or incondensables in refrigerant circuit.

4.

Changeover valve damaged or blocked open (h

eat pump unit).

1.

Remove charge, evacuate and recharge.

2.

Determine the cause and replace compressor

.

3.

Remove charge, evacuate and recharge.

4.

Replace it.

F.

Clicking sound is heard from

the

air conditioner

.

In heating or cooling operation any plastic parts may expand or

shrink due to a 

sudden temperature change in this event, a clicking sound may occur

.

In heating or cooling operation any plastic parts may expand

or shrink due to a sudden temperature change in this event,

a clicking sound may occur

.

Maximum Piping Lengths

: See T

echnical Specification

Note

 : 

Where the difference in elevation between the indoor unit and the outdoor 

unit

is greater than

5 meters, install an oil trap every 5 meters.

The suction line must have a 2% gradient up to the compressor on horizontal

sections.

Where piping lengths are unusually long and include a large number of oil

traps, it may be necessary to adjust to compressor charge.

Refrigerant Piping Connections (FLARE Connections)

To

avoid

alteration

of

unit

capacities,

check

that

piping

lengths

and

changes

in

elevation are kept to a strict minimum.

Before

connection

the

refrigerant

lines,

follow

the

procedures

below

(if

precharged

connection lines are not supplied):

Select copper pipe diameters according to the size of unit to be installed.

Install

the

refrigeration

lines,

checking

that

no

foreign

bodies

get

inside

the

piping.

Install the flare connectors and flare the ends of the pipes.

Refrigerant charge to be added per extra metre of piping length when

more than 7 meters.

TEST OPERA

TION

CHECK THIS ITEM BEFORE ST

ART OPERA

TION

Outdoor

Check the fl

are nut connections, valve stem cap connections and service cap 

connections for gas leak with a leak detector or soap water

.

Indoor

Check the unit is firmly fixed.

Check the connecting pipes are tighten securely

.

Check the pipe insulation.

Check the drainage.

Check the connection of the grounding wire.

This unit is shipped complete with a charge of R-22/R-407C refrigerant that will 

be suffi

cient for an interconnecting piping length of 7 meters.

Unit size

12

18

24

36

48

60

g/m

15

40

40

40

60

60

Low Pressure

Gas

Valve

Liquid

Valve

Pressure

Ta

p

Manifold

High Pressure

Indoor

Unit

Outdoor

Unit

Gas Line

Liquid Line

R-22/R-407C

J422_EN.indd   4

10/30/07   11:04:20 AM

YOEA36FS-AFH

H

F

A-

S

F

6

3

A

J

O

Y

H

F

A-

S

F

6

3

A

K

O

Y

H

F

A-

S

F

6

3

A

D

O

Y

H

F

A-

S

F

8

4

A

K

O

Y

H

F

A-

S

F

8

4

A

D

O

Y

H

F

A-

S

F

8

4

A

E

O

Y

H

F

A-

S

F

0

6

A

D

O

Y

H

F

A-

S

F

0

6

A

E

O

Y

H

F

A-

S

F

8

4

A

J

O

Y

H

F

A-

S

F

0

6

A

J

O

Y

H

F

A-

S

F

0

6

A

K

O

Y

H

D

A-

S

F

4

2

A

E

O

Y

H

D

A-

S

F

4

2

A

D

O

Y

Not

e

 : M

a

tching with Air handler

, must c

onnec

t    1    wir

e

M

a

tching with c

eilling and floor

, r

emo

v

e

    1   wir

e

Isolation

Epaisseur minimale 6 mm

Pompe à

chaleur

Liquide

Refroidissement

Pompe

à chaleur

(décharge)

Refroidissement (aspiration)

Pompe à chaleur

(décharge)

Pompe à

chaleur

Liquide

Refroidissement

GAZ

Refroidissement

(aspiration)

BLACK

WHITE

202075590238

Summary of Contents for YOCA-YOHA 12-60

Page 1: ...sive environments such as coastal areas Places where sulfide gas occurs such as hot springs The drain from the outdoor unit must be discharged to a place of good drainage CONSIDER NUISANCE TO YOUR NEIGHBOURS FROM NOISES For installation choose a place as described below A place solid enough to bear the weight of the unit and which does not amplify the operation noise or vibration A place from wher...

Page 2: ...ly over the roof beam then install the hanging screw bolts Refer to Chart 1 Inlaying or embedding the screw bolts Refer to Chart 2 Use embedding screw bolt Refer to Chart 3 Install and use directly the supporting angle steel Refer to chart 4 Timber over the beam Roof beam Ceiling Hanging screw bolts Chart 1 Chart 2 Blade shape insertion Slide insertion Steel bar Embedding screw bolt Pipe hanging a...

Page 3: ...GRRU HDWLQJ QGRRU RROLQJ 2XWGRRU HDWLQJ 2XWGRRU RROLQJ 2XWGRRU HDWLQJ 2XWGRRU RROLQJ 2XWGRRU HDWLQJ 2XWGRRU 3K RROLQJ 2XWGRRU 3K RROLQJ 2XWGRRU 3K HDWLQJ 2XWGRRU 3K HDWLQJ 2XWGRRU RROLQJ 2XWGRRU HDWLQJ 2XWGRRU RROLQJ 2XWGRRU HDWLQJ 2XWGRRU HDWLQJ QGRRU RROLQJ QGRRU HDWLQJ QGRRU RROLQJ QGRRU HDWLQJ QGRRU RROLQJ QGRRU B 1 LQGG 0 ...

Page 4: ...mum Piping Lengths See Technical Specification Note Where the difference in elevation between the indoor unit and the outdoor unit is greater than 5 meters install an oil trap every 5 meters The suction line must have a 2 gradient up to the compressor on horizontal sections Where piping lengths are unusually long and include a large number of oil traps it may be necessary to adjust to compressor c...

Page 5: ...WKH WLPH HODSVHG LV OHVV WKDQ PLQXWHV WKHQ WKH FRPSUHVVRU VWDUW XS ZLOO EH GHOD HG XQWLO PLQXWHV KDV SDVVHG LOWHU DUH DQG LOWHU ODUP 5HSODFH LU 3XULI LQJ ÀOWHU LI ÀWWHG 7KH ÀOWHUV VKRXOG EH FOHDQHG UHJXODUO L H RQFH D PRQWK RU PRUH IUHTXHQWO GHSHQGLQJ RQ FRQGLWLRQV 7KH FRQWURO LV HTXLSSHG ZLWK D ÀOWHU DODUP IWHU D FHUWDLQ QXPEHUV RI KRXUV RI RSHUDWLRQ ÁDVKLQJ OLJKWV ZLOO LQGLFDWH WKDW LW LV WLPH W...

Page 6: ...R OXPLQXP DOOR LDPHWHU PP 0RWRU 4XDQWLW 6SHHG USP 0D 6WDUWLQJ XUUHQW 5XQQLQJ XUUHQW QSXW 3RZHU 2XWSXW 3RZHU DSDFLWRU P 3URWHFWRU QQHU WKHUPDO 2YHUORDG 3URWHFWLRQ QVXODWLRQ ODVV 3 5DWLQJ 3 3 3 3 3 3 RPSUHVVRU 4XDQWLW 7 SH 6FUROO 6FUROO 6FUROO 6FUROO 6FUROO 6FUROO 2LO KDUJH FF DSDFLWRU P 0D 6WDUWLQJ XUUHQW 5XQQLQJ XUUHQW QSXW 3RZHU N 3URWHFWRU QQHU WKHUPDO 2YHUORDG 3URWHFWLRQ 9LEUDWLRQ VRODWRU 5XEEH...

Reviews: