JOHNSON CONTROLS
96
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
SECTION 7 – UNIT CONTROLS
UNIT SWITCH
A unit ON/OFF switch is just underneath the keypad.
This switch allows the operator to turn the entire unit
“OFF” if desired. The switch must be placed in the
“ON” position for the unit to operate.
DISPLAY
The 40 Character Display (2 lines of 20 characters) is
a liquid crystal display used for displaying system pa-
rameters and operator messages.
The display in conjunction with the keypad, allows the
operator to display system operating parameters as well
as access programmed information already in memory.
The display has a lighted background for night viewing
and for viewing in direct sunlight.
When a key is pressed, such as the OPER DATA key,
system parameters will be displayed and will remain
on the display until another key is pressed. The system
parameters can be scrolled with the use of the ↑ (
UP)
and ↓ (
DOWN) arrow keys. The display will update all
information at a rate of about 1 a second.
Display Messages may show characters indicating
“greater than” (>) or “less than” (<). These characters
indicate the actual values are greater than or less than
the limit values which are being displayed.
KEYPAD
The 12 button non-tactile keypad allows the user to
retrieve vitals system parameters such as system pres-
sures, temperatures, compressor running times and
starts, option information on the chiller, and system
setpoints. This data is useful for monitoring chiller op-
eration, diagnosing potential problems, troubleshoot-
ing, and commissioning the chiller.
It is essential the user become familiar with the use of the
keypad and display. This will allow the user to make full
use of the capabilities and diagnostic
features available.
BATTERY BACK-UP
The Microprocessor Board contains a Real Time Clock
integrated circuit chip with an internal battery backup.
The purpose of this battery backup is to assure any
programmed values (setpoints, clock, cutouts, etc.) are
not lost during a power failure regardless of the time
involved in a power cut or shutdown period.
TRANSFORMER
A 40 VA, 120/24VAC 50/60Hz transformer is provided
to supply power to the Microprocessor Board, which
in turn rectifies, filters, and regulates as necessary to
supply power to the display, sensors, and transducers.
SINGLE SYSTEM SELECT AND
PROGRAMMING NUMBER OF
COMPRESSORS
The control software is common between single (1)
and dual (2) system units. A jumper is installed be-
tween terminals 13 and 17 on the user terminal block
to configure a unit for a single system. Dual (2) sys-
tem units do not have a jumper installed. The jumper is
only checked by the micro on power-up.
The total number of compressors is programmable un-
der the Program Key. Single (1) system units can have
2 or 3 compressors. Dual (2) system units can have 4,
5, or 6 compressors.
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...