1.6.3 Physical data
Physical data, YLCA units
Physical data
YLCA (M and MC)
YLCA (T and TC)
Characteristics
5
7
9
7
9
12
15
20
27
Cooling capacity
kW
5,38
7,13
9,05
7,13
9,05
12,4
14,5
19,52
25,6
Capacity control
%
Power supply
V/ph
230.1.50
400.3.50
Max. unit power supply consumption
kW
2,57
3,61
4,36
3,61
4,36
5,68
8
9,17
12,09
Max. unit current amperage
A
11,75
17,1
23
7,6
8,25
11,6
15,8
18,1
23
EER
2,87
2,76
2,79
2,76
2,81
2,97
2,52
2,81
2,81
Compressor
Compressor power
kW
1,73
2,41
3,2
2,41
3,2
3,8
5,38
6,57
8,73
Compressor amperage
A
7,8
11,7
16
3,9
5,3
6,36
8,9
13
16,7
No. of compressors
1
Compressor type
SCROLL
Oil charge
l
1,1
1,25
1,95
1,66
2,51
3,25
Oil type
POLYOL ESTER OIL
Compressor start-up
current
A
60
82
97
35
48
51
74
95
118
Evaporator unit type
PLATES
Fan
No. of fans
1
2
Fan diameter
mm
450
560
Fan power
W
140
170
2 x 185
2 x 175
Fan amperage
A
0,6
0,8
2 x 0,87
2 x 0,85
Total air flow rate
m³/h
2900
3150
6150
6300
7200
Sound power
dB(A)
70
70
71
70
71
73
73
74
78
Sound pressure at 5 m
dB(A)
44
44
45
44
45
47
47
48
51
Sound pressure at
10 m
dB(A)
40
40
41
40
41
43
43
44
48
Available static pres‐
sure at nominal flow
rate (without filter) (2)
kPa
51
80
78
80
75
115
152
134
191
Available static pres‐
sure at nominal flow
rate (with filter) (3)
kPa
49
75,5
71
75,5
67,5
113
149
129,5
182
Coolant
Coolant type
R-410A
Coolant charge
kg
2,08
2,55
2,25
2,55
2,15
3,17
3,1
5
7,8
No. of coolant circuits
Water circuit
Nominal water flow rate
l/h
925
1225
1430
1225
1475
2065
2530
3360
4405
Min water volume inst.
(1)
l
15
20
25
20
25
35
45
55
75
Water connection, fe‐
male
1"
1 1/4"
water filter, female
1"
1 1/4"
No. of pumps
1
Pump power
W
160
210
400
490
390
755
Pump amperage
A
0,65
0,95
1,8
2,15
1,1
1,34
Unit water content
l
1
1,1
1,2
1,1
1,2
1,5
2
2,8
3,2
Volume of expansion
vessel
l
1
2
5
8
Safety valve
setting
MPa
(bar)
0,6
(6)
Dimensions
and weight
Weight (4)(5)
kg
75
99
100
99
100
146
160
220
290
Length
mm
905
1430
1876
Width
mm
460
502
Height
mm
762
965
1270
(1)
Minimum volume of water in installation: In installations with smaller volumes, and under low load conditions, the function "Omission of inertia tank" is automatically
activated. As a result, the water temperature becomes less accurate as the total volume of water in the installation is reduced.
(2)
Please enquire before applying values lower than those shown.
(3)
Static pressure available, Eurovent certified. Pressure with clean filter.
(4)
Weights for the empty unit.