![background image](http://html.mh-extra.com/html/york/ylca/ylca_technical-information_913542022.webp)
Correcting factors for other glycol concentrations
% in weight
Ethylene glycol
Propylene glycol
Capacity
Absorbed power
Capacity
Absorbed power
10
1,061
1,025
1,097
1,033
20
1,036
1,015
1,067
1,023
30
1,015
1,005
1,026
1,008
35
1
1
1
1
40
0,985
0,995
0,974
0,992
50
0,954
0'985
0,923
0,977
If it is necessary to select different glycol percentages, correct the capacity and absorbed power capaci‐
ties of tables 2 and 4 (35% ethylene glycol), multiplying them by the coefficients indicated in the table.
Altitude factors
Altitude
Capacity factor
compressor absorbed power factor
0
1
1
600
0,987
1,01
1200
0,973
1,02
1800
0,958
1,029
2400
0,943
1,038
Technical Information
1
Technical data
1.6
19
Summary of Contents for YLCA