1.2.14 Functions
Alarm reset
Pressing the UP ‑4- and DOWN ‑5- keys for 5 seconds cancels the alarms present in the memory. At
the same time, the alarm message disappears from the display and the alarm relay is deactivated.
Forced defrost (heat pumps)
Pressing the SEL ‑6- and UP ‑4- keys simultaneously for 5 seconds activates forced defrost of the unit.
Clearing hour counters
While reading compressor or pump (c10 and c15) op‐
erating hours, said counters can be cleared by press‐
ing the UP ‑4- and DOWN ‑5- keys simultaneously.
Pump operation
4 operating modes can be selected in accordance with the value given to parameter H5.
• H5=0 (pump disabled).
• H5= 1 (pump always on),
• H5= 2 (pump running under control of regulator or in parallel with the compressor),
• H5= 3 (pump stops and starts at regular intervals irrespective of the compressor operation (param‐
eters c17 and c18).
Calibration of probes
If necessary, probes can be calibrated by using parameters /13, /14, /15 y /16. See Table
Parameters
relating to probes
, see on page 13.
Remote ON/OFF
A remote ON/OFF inlet can be connected between terminals D5 and B on the connecting strip. To activate
said inlet, a value of 1 should be given to parameter H07 (H07= 1). With this inlet open the unit is OFF;
when closed, the unit is ON. This option does not disable the ON/OFF function of the keyboard.
Remote COOL/HEAT
A remote COOL/HEAT inlet can be connected between terminals D2 and B on the connecting strip. To
activate said inlet, a value of 1 should be given to parameter H06 (H06= 1). With this inlet open the unit
is in HEAT; when closed, the unit is in COOL. This function disables the COOL/HEAT function of the
keyboard.
1
2
3
4
5
6
7
8
9
10
11
11
12
13
User manual