3.2 Outdoor unit control
3.2.1 Outdoor frequency control
A. Compressor running frequency range: unitary:
30-91RPS YJU3YH019BARXA-X:20-100RPS, the others are 20~95RPS
B. defination of high-efficiency operation and its frequency control
In order to meet the cooling request at a high ambient temperature and the heating request at low ambient
temperature, we set the high-efficiency operation.
Entering condition: cooling mode, Tao≥33
o
C( E), heating mode, Tao≤5
o
C( E)
3.2.2 Electronic expansion valve (EEV) control
A: Electronic characteristic
Max. open angle
500 pulse
Driving speed
PPS
B: Initialization of EEV
EEV driving speed: open direction: 32MS; close direction: 32MS
C: Open angle limitation of EEV
Unitary
Unit stop
Adjustable upper limit
Cool/dry
250(E)
480(E)
heat
250(E)
480(E)
Unit stop
Adjustable upper limit
Thermostat ON
Thermostat OFF
Adjustable lower
limitation
Cool/ dry
5(E)
450(E)
standard open
angle+tolerance
5(E)
80(E)
Heat
60(E)
450(E)
standard open
angle+tolerance
60(E)
80(E)
D: Standard open angle control
Unitary: In Cool/Dry mode, standard open angle: outdoor ambient temp.≥22
o
C, 260pulse (E);Outdoor ambient
temp.≤22
o
C, 210pulse (E);
In heat mode, standard open angle: outdoor ambient temp.≥6
o
C, 240pulses (E) ;Outdoor ambient
temp. ≤6
o
C, 160pulse (E)
Multi: In Cool/Dry mode, standard open angle: outdoor ambient temp.≥20
o
C, 250 pulse(E);Outdoor ambient
temp.<20
o
C, 210 pulse(E);
In Heat mode, standard open angle: outdoor ambient temp.≥10
o
C, pulse (E);outdoor ambient
temp.<10
o
C, 210 pulse (E).
F: When discharging temp. Td is too high or too low, modify the EEV angle Unitary
mode
Modification process
Max. modification
Cooling
If TD>106 degree and -1 degree /2 minutes, open angle keeps between 106-50 . -3
Cooling
If TD<50 degree and +1 degree /2 minutes, open angle keeps between 50-106. +3
Heating
If TD>100 degree and -1 degree /2 minutes, open angle keeps between 100-50 . -3
Heating
If TD<50 degree and +1 degree /2 minutes, open angle keeps between 50-100
+3
Multi: In order to cooperate the compressor discharging temp. over high protection, the system will enlarge
the EEV open angle. Within 5 minutes after compressor starts up, it will not modify. The detecting period is 30
seconds.
229
Summary of Contents for YHKMXH009BARX-FX
Page 23: ...3 Dimension 21 ...
Page 24: ...22 ...
Page 25: ...4 Piping diagram Liquid pipe Gas pipe Filter Filter EEV Fan Indoor heat exchanger 23 ...
Page 37: ...9 Installation 35 ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...
Page 41: ...39 ...
Page 42: ...40 ...
Page 43: ...41 ...
Page 56: ...3 Piping diagram Liquid pipe Gas pipe Filter Filter EEV Fan Indoor heat exchanger 54 ...
Page 67: ...7 Installation YHFMXH012 24BARX FX 65 ...
Page 68: ...66 ...
Page 69: ...67 ...
Page 70: ...68 ...
Page 71: ...69 ...
Page 72: ...70 ...
Page 73: ...71 ...
Page 74: ...72 ...
Page 75: ...28K 60K 73 ...
Page 76: ...74 ...
Page 77: ...75 ...
Page 78: ...76 ...
Page 79: ...77 ...
Page 80: ...78 ...
Page 104: ...3 Dimension 102 ...
Page 105: ...YHGJXH048BARX GX S YHGJXH060BARX GX S 103 ...
Page 106: ...3 Piping diagram Liquid pipe Gas pipe Filter Filter EEV Fan Indoor heat exchanger 104 ...
Page 123: ...7 Installation For AD09 24LS1ERA AD09 24SS1ERA 121 ...
Page 124: ...122 ...
Page 125: ...123 ...
Page 126: ...124 ...
Page 127: ...125 ...
Page 128: ...126 ...
Page 129: ...YHEJXH028BARX GX S YHEJXH036BARX GX S YHEJXH048BARX GX S 127 ...
Page 130: ...128 ...
Page 131: ...129 ...
Page 132: ...130 ...
Page 133: ...131 ...
Page 134: ...For YHGJXH048BARX GX YHGJXH060BARX GX 132 ...
Page 135: ...133 ...
Page 136: ...134 ...
Page 137: ...135 ...
Page 138: ...136 ...
Page 139: ...137 ...
Page 146: ...2 Dimension 144 ...
Page 156: ...4 Wiring connection YJU3YH019BARXA X 154 ...
Page 186: ...9 Maintenance WARNING CAUTION 184 ...
Page 187: ...185 ...
Page 188: ...186 ...
Page 189: ...187 ...
Page 190: ...Items to Be Checked 188 ...
Page 191: ...189 ...
Page 192: ...190 ...
Page 194: ...192 ...
Page 195: ...193 ...
Page 196: ...194 ...
Page 197: ...195 ...
Page 199: ...197 ...
Page 200: ...198 ...
Page 201: ...199 ...
Page 202: ...For YJU3YH019BARXA X YJU4YH025BARXA X YJU4YH030BARXA X YJU5YH034BARXA X YJU5YH045BARXA X 200 ...
Page 203: ...201 ...
Page 204: ...202 ...
Page 205: ...203 ...
Page 206: ...M 204 ...
Page 207: ...205 ...
Page 208: ...206 ...
Page 209: ...R 207 ...
Page 210: ... 25 40 0 208 ...
Page 211: ...209 ...
Page 213: ...PCB 0151800175 YH3MXH009BARX GX YH3MXH012BARX GX YH3MXH018BARX GX YH3MXH024BARX GX 211 ...
Page 221: ...PCB 0011800241C 219 ...
Page 222: ...PCB 0151800054A 220 ...
Page 223: ...PCB 0151800076 PCB 0151800075 221 ...
Page 224: ...Power module 0010400352C Power module 0150400908 222 ...
Page 225: ...Power module 0150400644A Power module 0150400939 223 ...
Page 226: ...Power module 0151800105 224 ...
Page 227: ...Power module 0150400643B Filter board 0150400699 225 ...
Page 228: ...Filter board 0010452726 Filter board 0150400567 Dip switch setting 226 ...