2.2.11 Water pump control
A: Water pump will be electrified when indoor unit enters non-heating mode until indoor unit stops. 5 minutes
later after indoor unit stops, water pump will stop.
B: When indoor unit is in heating mode, water pump will not operate.
C: In OFF state and in any mode, once float switch signal is measured, indoor unit will send OFF signal to
outdoor and send the failure code of drainage system to the wired controller, then the water pump will work until
the float switch signal is cancelled. After water pump is forced to run for 5 minutes, indoor unit will be back to
normal state.
2.2.12 Compulsory defrosting operation
A: After indoor receives the compulsory defrosting signal, it will send continously the signal to outdoor for 10
times, in this period, indoor unit will work normally and it will enter defrosting operation until it receives the enter-
defrost signal from outdoor unit.
B: Wired control type: In heating mode, make a jumper for D2 to enter compulsory defrosting.
C: Remote control type: In heating mode, high speed, 30
o
C, press SLEEP button 6 times, and the buzzer will
sound 3 times, then enter the manual defrosting.
2.2.13 Trial operation
A: Enter condition
a: Wired control type: In OFF state of COOL or HEAT mode, press ON/OFF button for over 5 seconds to enter
the cooling or heating trial operation;
b: Remote control type: In OFF state, keep pressing ON/OFF button until 5 seconds later, the buzzer sounds
twice, then enter the cooling or heating trial operation;
B: Response in trial operation
a: Cooling trial operation: indoor sends S-CODE=SD to outdoor, indoor: at high speed, set temp: 16
o
C;
b: Heating trial operation: indoor sends S-CODE=SF to outdoor, indoor: at high speed, set temp: 30
o
C;
c: In this period, anti-freezed and overheat functions are invalid.
C: Quit condition
a: Receiving the signal of cancelling trial operation from wired controller or remote controller;
b: After trial operation has run for 20 minutes, it will quit trial operation automatically and enter the normal mode
with the set temp.: 24
o
C.
2.2.14 Timer operation
A: Wired control type: wired controller will control the unit ON/OFF;
B: Remote control type: indoor unit will confirm the unit ON or OFF according to the current clock and the timer
clock set by remote controller. When setting timer function, the timer LED will be ON.
2.2.15 SLEEP function
A: Wired control type unit is without sleep function;
B: Remote control type unit consists of cooling sleep and heating sleep, after the sleep is set, the unit will
change mode; the sleep will begin to count.
a: In cooling/dry mode, after running for 1 hour, the set temp. will increase 1
o
C, another 1 hour later, the
set temp. will increase 1
o
C again, then 6 hours (or set time-2) later , it will stop.
b: In heating mode, after running for 1 hour, the set temp. will reduce 2
o
C, another 1 hour later, the set temp. will
reduce 2
o
C again, then 3 hours later, the set temp. will increase 1
o
C, and another 3 hours(or set time-5), it will
stop.
c: When setting sleep function, indoor motor is forced at low speed.
2.2.16
Healthy negative ion function
When receiving the healthy signal from the wired controller or remote controller, if fan motor is running, the
negative ion will work;
216
Summary of Contents for YHKMXH009BARX-FX
Page 23: ...3 Dimension 21 ...
Page 24: ...22 ...
Page 25: ...4 Piping diagram Liquid pipe Gas pipe Filter Filter EEV Fan Indoor heat exchanger 23 ...
Page 37: ...9 Installation 35 ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...
Page 41: ...39 ...
Page 42: ...40 ...
Page 43: ...41 ...
Page 56: ...3 Piping diagram Liquid pipe Gas pipe Filter Filter EEV Fan Indoor heat exchanger 54 ...
Page 67: ...7 Installation YHFMXH012 24BARX FX 65 ...
Page 68: ...66 ...
Page 69: ...67 ...
Page 70: ...68 ...
Page 71: ...69 ...
Page 72: ...70 ...
Page 73: ...71 ...
Page 74: ...72 ...
Page 75: ...28K 60K 73 ...
Page 76: ...74 ...
Page 77: ...75 ...
Page 78: ...76 ...
Page 79: ...77 ...
Page 80: ...78 ...
Page 104: ...3 Dimension 102 ...
Page 105: ...YHGJXH048BARX GX S YHGJXH060BARX GX S 103 ...
Page 106: ...3 Piping diagram Liquid pipe Gas pipe Filter Filter EEV Fan Indoor heat exchanger 104 ...
Page 123: ...7 Installation For AD09 24LS1ERA AD09 24SS1ERA 121 ...
Page 124: ...122 ...
Page 125: ...123 ...
Page 126: ...124 ...
Page 127: ...125 ...
Page 128: ...126 ...
Page 129: ...YHEJXH028BARX GX S YHEJXH036BARX GX S YHEJXH048BARX GX S 127 ...
Page 130: ...128 ...
Page 131: ...129 ...
Page 132: ...130 ...
Page 133: ...131 ...
Page 134: ...For YHGJXH048BARX GX YHGJXH060BARX GX 132 ...
Page 135: ...133 ...
Page 136: ...134 ...
Page 137: ...135 ...
Page 138: ...136 ...
Page 139: ...137 ...
Page 146: ...2 Dimension 144 ...
Page 156: ...4 Wiring connection YJU3YH019BARXA X 154 ...
Page 186: ...9 Maintenance WARNING CAUTION 184 ...
Page 187: ...185 ...
Page 188: ...186 ...
Page 189: ...187 ...
Page 190: ...Items to Be Checked 188 ...
Page 191: ...189 ...
Page 192: ...190 ...
Page 194: ...192 ...
Page 195: ...193 ...
Page 196: ...194 ...
Page 197: ...195 ...
Page 199: ...197 ...
Page 200: ...198 ...
Page 201: ...199 ...
Page 202: ...For YJU3YH019BARXA X YJU4YH025BARXA X YJU4YH030BARXA X YJU5YH034BARXA X YJU5YH045BARXA X 200 ...
Page 203: ...201 ...
Page 204: ...202 ...
Page 205: ...203 ...
Page 206: ...M 204 ...
Page 207: ...205 ...
Page 208: ...206 ...
Page 209: ...R 207 ...
Page 210: ... 25 40 0 208 ...
Page 211: ...209 ...
Page 213: ...PCB 0151800175 YH3MXH009BARX GX YH3MXH012BARX GX YH3MXH018BARX GX YH3MXH024BARX GX 211 ...
Page 221: ...PCB 0011800241C 219 ...
Page 222: ...PCB 0151800054A 220 ...
Page 223: ...PCB 0151800076 PCB 0151800075 221 ...
Page 224: ...Power module 0010400352C Power module 0150400908 222 ...
Page 225: ...Power module 0150400644A Power module 0150400939 223 ...
Page 226: ...Power module 0151800105 224 ...
Page 227: ...Power module 0150400643B Filter board 0150400699 225 ...
Page 228: ...Filter board 0010452726 Filter board 0150400567 Dip switch setting 226 ...