510667-YTG-B-0509

2

Johnson Controls Unitary Products

All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.

Physical and Electrical Data

MODEL

YHJF18

S41S1

YHJF24

S41S1

YHJF30

S41S1

YHJF36

S41S1

YHJF42

S41S1

YHJF48

S41S1

YHJF60

S41S1

Unit Supply Voltage

208-230V, 1



 60Hz

Normal Voltage Range 

1

187  to 252

Minimum Circuit Ampacity

11.9

17.6

17.3

23.7

26.1

28.8

35.3

Max. Overcurrent Device Amps 

2

20

30

30

40

45

50

60

Min. Overcurrent Device Amps 

3

15

20

20

25

30

30

40

Compressor Type 

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Compressor Amps

Rated Load

9.0

13.4

12.8

17.9

19.8

28.8

35.3

Locked Rotor

48.0

58.3

64.0

96.7

115.0

115.0

118.0

Crankcase Heater

No

No

No

No

No

No

No

Fan Motor Amps

Rated Load

0.7

0.8

1.3

1.3

1.3

1.3

1.3

Fan Diameter Inches

24

22

24

24

24

24

24

Fan Motor

Rated HP

1/10

1/8

1/4

1/4

1/4

1/4

1/4

Nominal RPM

825

1075

850

850

850

850

850

Nominal CFM

2000

2000

3900

3900

3900

3800

3800

Coil

Face Area Sq. Ft.

15.72

19.17

23.58

23.58

23.58

23.58

23.58

Rows  Deep

1

1

1

1

1

2

2

Fin / Inches

22

22

22

22

22

18

18

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

3/4

7/8

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 

4

6 – 15

7 – 14

9 – 14

10 – 9

10 – 9

14 – 2

14 – 2

Charge Per Foot, Oz.

0.62

0.62

0.62

0.62

0.67

0.67

0.75

Operating Weight Lbs.

145

145

176

193

198

248

290

1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add 

or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

B

C

A

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

1

1. Including Fan Guard.

B

C

Liquid

Vapor

18

28

34

34

3/8”

3/4”

24

40

29

29

30

40

34

34

36

40

34

34

42

40

34

34

7/8”

48

40

34

34

60

40

34

34

Summary of Contents for YHJF18

Page 1: ...made of pre painted steel The pre treated galvanized steel provides a better paint to steel bond which resists corrosion and rust creep Special primer formulas and matted textured finish insure less f...

Page 2: ...FM 2000 2000 3900 3900 3900 3800 3800 Coil Face Area Sq Ft 15 72 19 17 23 58 23 58 23 58 23 58 23 58 Rows Deep 1 1 1 1 1 2 2 Fin Inches 22 22 22 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8...

Page 3: ...door Unit YHJF18 S41S1 YHJF24 S41S1 YHJF30 S41S1 YHJF36 S41S1 YHJF42 S41S1 YHJF48 S41S1 YHJF60 S41S1 Required Orifice or TXV 1 2 051 1TVM4F1 059 1TVM4G1 063 1TVM4G1 071 1TVM4H1 075 1TVM4J1 1TVM4J1 1TV...

Page 4: ...YHJF18S41S1 AHX30 17 640 18 0 13 3 15 00 12 50 YHJF24S41S1 AHX30 17 800 22 8 17 1 15 00 12 50 F6FP030 17 850 22 8 17 3 14 50 12 00 F6FP036 21 855 22 8 17 4 15 00 12 50 AHX36 21 820 23 0 17 4 15 00 12...

Page 5: ...17 5 15 00 12 50 T 9X C20 FC MC PC43C 21 790 23 2 17 4 15 00 12 50 Y 8 L C A12 FC MC PC32A 14 775 22 8 17 1 14 50 12 00 Y 8 L C B12 FC MC PC35B 17 760 22 6 16 7 15 00 12 50 Y 8 L C C16 FC MC PC35C 21...

Page 6: ...00 YHJF48S41S1 T 8 L X C16 FC MC62D 21 1610 48 0 36 2 14 50 12 00 T 8 L X C20 FC MC62D 21 1665 48 0 36 2 14 50 12 00 T 9X C16 FC MC62D 21 1550 48 0 36 0 14 50 12 00 T 9X C20 FC MC62D 21 1595 48 0 36 2...

Page 7: ...79 15 1 2 42 1 83 8 20 F6FP036 22 2 3 68 1 77 15 0 2 46 1 79 8 50 AHX36 22 4 3 70 1 77 15 1 2 46 1 80 8 50 YHJF30S41S1 AHX36 30 0 4 00 2 20 18 7 2 76 1 99 9 00 F6FP042 30 0 4 00 2 20 18 7 2 76 1 99 9...

Page 8: ...X C20 FC MC PC43C 22 0 3 74 1 72 14 9 2 50 1 75 8 50 Y 8 L C A12 FC MC PC32A 22 2 3 62 1 80 15 0 2 42 1 82 8 50 Y 8 L C B12 FC MC PC35B 22 0 3 56 1 81 14 9 2 40 1 82 8 50 Y 8 L C C16 FC MC PC35C 22 2...

Page 9: ...2 2 95 26 2 2 74 2 80 9 00 T 9X D20 FC MC62D 40 5 4 02 2 95 26 0 2 76 2 76 9 00 Y 8 L C C16 FC MC62D 41 0 3 96 3 03 26 4 2 70 2 86 9 00 Y 8 L C C20 FC MC62D 41 0 4 00 3 00 26 2 2 74 2 80 9 00 Y 9C T 9...

Page 10: ...llation refer to the UPGNET Low Voltage Wiring Diagram document to select and apply controls HEATING CAPACITY With High Efficiency Motor Furnaces UNIT MODEL VARIABLE SPEED FURNACE MODEL COIL MODEL1 HE...

Page 11: ...2 69 4 71 4 73 2 71 2 61 1 57 6 52 8 74 7 19 09 Heating Mode High Stage 71 6 72 7 69 6 71 3 72 4 63 4 61 5 57 4 75 0 19 05 THERMOSTAT SEAL OPENING S WITH PERMAGUM OR EQUIVALENT TO INDOOR COIL TO FURN...

Page 12: ...1 2 1 2 1 2 1 2 1 2 1 3 1 3 1 3 1 3 1 3 1 3 95 T C 15 0 16 1 16 1 18 1 19 6 16 9 17 4 17 0 19 0 20 4 18 8 18 8 18 0 19 8 21 3 S C 14 7 13 7 11 6 11 8 9 7 16 5 16 0 13 9 13 9 10 9 18 4 18 4 16 2 16 0...

Page 13: ...5 18 2 18 1 13 5 KW 1 9 1 9 1 9 1 9 2 0 2 0 2 0 1 9 2 0 2 0 2 1 2 1 2 0 2 1 2 1 115 T C 16 5 16 4 16 4 18 7 20 9 17 9 17 9 17 0 19 3 21 6 19 4 19 4 17 7 20 0 22 2 S C 16 3 16 1 13 4 13 5 10 8 17 7 17...

Page 14: ...6 29 3 31 5 28 2 27 3 27 3 30 1 32 0 S C 25 1 24 4 20 4 20 4 16 5 26 7 26 1 22 6 22 4 17 3 28 2 27 3 24 7 24 4 18 1 KW 2 0 2 0 2 0 2 0 2 1 2 1 2 1 2 1 2 1 2 1 2 2 2 1 2 1 2 2 2 2 105 T C 23 7 23 8 23...

Page 15: ...1 6 31 6 31 5 35 1 38 3 33 3 32 4 32 4 36 0 38 9 S C 29 9 30 7 29 1 29 2 23 4 31 6 31 6 31 5 31 5 24 6 33 3 32 4 32 4 33 9 25 8 KW 2 7 2 7 2 7 2 8 2 8 2 8 2 8 2 8 2 9 2 9 2 9 2 9 2 9 2 9 2 9 105 T C 2...

Page 16: ...8 2 8 2 8 2 9 2 9 2 9 2 9 2 9 3 0 3 0 3 0 2 9 3 0 3 1 95 T C 33 7 34 8 34 7 38 8 42 3 35 6 35 3 35 4 39 6 43 2 37 4 35 8 36 1 40 3 44 1 S C 33 7 33 3 27 7 27 7 22 2 35 6 34 7 29 8 29 7 23 2 37 4 35 8...

Page 17: ...4 3 4 3 4 3 4 3 5 3 5 3 5 3 5 3 6 3 6 95 T C 40 5 41 1 41 2 45 9 50 5 42 5 42 0 42 0 46 8 51 3 44 4 42 8 42 8 47 7 52 1 S C 40 5 39 2 32 7 32 6 26 0 42 5 41 0 34 7 34 6 27 1 44 4 42 8 36 8 36 5 28 2 K...

Page 18: ...2 30 5 26 1 26 1 21 7 35 5 33 5 28 3 28 3 22 9 37 8 36 5 30 4 30 4 24 0 KW 2 7 2 7 2 8 2 7 2 8 2 8 2 8 2 8 2 8 2 8 2 9 2 9 2 9 2 9 2 9 95 T C 34 1 36 0 36 0 39 9 43 6 36 2 37 3 37 1 41 1 45 0 38 3 38...

Page 19: ...1 5 48 0 40 3 40 1 32 2 53 2 50 7 42 4 42 0 33 2 54 9 53 4 44 4 43 9 34 3 KW 4 2 4 2 4 2 4 3 4 4 4 3 4 3 4 3 4 4 4 5 4 4 4 4 4 4 4 5 4 6 95 T C 50 2 51 6 51 2 56 5 61 7 51 8 52 3 52 1 57 3 62 4 53 3 5...

Page 20: ...3 30 60 14 6 3 1 1 2 15 1 3 2 1 2 15 5 3 4 1 1 70 14 2 2 7 1 4 14 6 2 9 1 3 15 0 3 0 1 2 80 13 7 2 4 1 5 14 1 2 5 1 4 14 4 2 6 1 3 17 60 11 7 2 6 1 2 12 0 2 6 1 1 12 3 2 7 1 1 70 11 2 2 2 1 3 11 6 2...

Page 21: ...NET KBTUH WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP AHX36 1 01 1 02 0 99 AV 36 0 99 1 02 0 97 F6FP030 1 00 1 00 1 00 F6FP036 1 00 1 01 0 99 MV12B FC MC35...

Page 22: ...80 23 0 2 6 2 3 23 4 2 7 2 2 23 8 2 7 2 1 17 60 19 9 2 8 1 8 20 1 2 8 1 7 20 4 2 9 1 7 70 18 8 2 4 2 0 19 2 2 4 2 0 19 6 2 5 1 9 80 17 8 2 0 2 3 18 3 2 1 2 2 18 8 2 2 2 1 10 60 17 1 2 4 1 8 17 4 2 4...

Page 23: ...31 7 2 9 2 7 80 31 0 2 4 3 4 31 2 2 5 3 2 31 4 2 6 3 1 17 60 25 3 2 6 2 5 25 4 2 6 2 4 25 4 2 6 2 3 70 24 2 2 2 2 9 24 7 2 3 2 8 25 2 2 3 2 6 80 23 1 1 9 3 2 24 1 2 0 3 1 25 0 2 1 3 0 10 60 21 6 2 3 2...

Page 24: ...37 7 3 2 2 9 30 60 33 3 3 4 2 4 33 4 3 4 2 4 33 5 3 4 2 3 70 32 7 3 0 2 7 32 8 3 1 2 6 32 9 3 1 2 5 80 32 0 2 7 3 0 32 2 2 8 2 9 32 3 2 8 2 8 17 60 26 7 2 9 2 2 26 9 2 9 2 2 27 2 2 8 2 2 70 25 2 2 5...

Page 25: ...60 40 1 2 9 3 6 40 2 2 9 3 5 40 3 2 9 3 3 70 38 9 2 7 3 8 39 3 2 7 3 8 39 6 2 6 3 7 80 37 8 2 5 4 0 38 3 2 4 4 0 38 8 2 4 4 1 17 60 30 2 2 6 2 8 31 3 2 8 2 8 32 4 2 9 2 7 70 28 7 2 4 3 0 29 5 2 4 3 0...

Page 26: ...7 4 69 40 60 56 20 3 64 3 93 56 47 3 70 3 80 56 74 3 76 3 69 70 55 47 3 24 4 42 55 62 3 30 4 27 55 76 3 35 4 13 80 54 75 2 92 4 90 54 77 2 96 4 75 54 79 3 02 4 57 30 60 49 33 3 30 3 78 49 52 3 33 3 70...

Reviews: