538605-UIM-B-1009

6

Johnson Controls Unitary Products

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the
Product Catalog Section.

 FIGURE 6: 

Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler

HP 27A

Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation)

O

Reversing Valve

Energized in Cool

C

24 – Volt Common

R

24 – Volt Hot

W1 OUT

First Stage Heat

W2 OUT

Second Stage Heat

Y2 OUT

Second Stage Compressor

Y1

Single Stage Compressor

X/L

Malfunction Light

Y2

Second Stage Compressor

W

Auxiliary Heat

BS

Bonnet Sensor

BSG

Bonnet Sensor

TWO STAGE

HEAT PUMP

C

24 – Volt Common

Y1

First Stage Compressor

L

Malfunction Light

Y2

Second Stage Compressor

G

Fan

*PP32U71124

*PP32U72124

THERMOSTAT

R

24 – Volt Hot

E/W1

First Stage Aux. Heat

W2

Second Stage Aux. Heat

DHM

Dehumidistat

HM

Humidistat

Step 1 of the Thermostat

Installer Table must be

set to Heat Pump

O

Reversing Valve

Energized in Cool

1

24VAC Humidifier

(Optional)

Part Numbers:

SAP =

Legacy

159481 = 031-09157

2

COM

24 – Volt Common

R

24 – Volt Hot

W1

First Stage Aux. Heat

W2

Second Stage Aux. Heat

Y1

Single Stage Compressor

Y/Y2

Second or Full

Stage Compressor

O

Reversing Valve

Energized in Cool

X/L

Malfunction Light

HUM

Humidity Switch

Open on Humidity Rise

VARIABLE SPEED

AIR HANDLER CONTROL

G

Fan

Move the MODE

jumper to “HP”

Move the HUM STAT

jumper to “YES”

if humidistat is to be used.

VARIABLE SPEED

AIR HANDLER

2

Part Numbers:

SAP =

Legacy

126768 = 031-09137

18395 = 031-01996
340512 = 031-09178

1

AV

ID MODELS

SV

MV

YZE

OD MODELS

YZH

H*5

H*8

YORKGUARD VI

CONTROL

24VAC

Electronic Air Cleaner

(Optional)

E2/P Switch must be in the

E2 position

Step 2 of the Thermostat

Installer Table must be

set to 2

Step 5 of Thermostat User

Configuration Menu must

be set to “ON” for

Dehumidification

EAC (24VAC out)

Electronic Air Cleaner

Refer to AH documentation

for W1 and W2 electric

heat staging options.

HUM OUT

(24VAC out)

Second stage auxiliary

heat will be controlled by

the thermostat, not the

heat pump control when

wired as shown.

Change Hot Heat Pump

jumper on the heat pump

control to “ON”

THJF060

YHJF060

CHJF060

LHJF060

GHJF060

Summary of Contents for YHJF060

Page 1: ...Refrigerant Line Length Part Number 036 61920 001 SECTION II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Underst...

Page 2: ...required that the outdoor unit indoor coil and metering device all be replaced The following steps should be performed in order to insure proper system operation and performance Line set change out is...

Page 3: ...por lines at least 1 every 20 feet toward the outdoor unit to facilitate proper oil return PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be taken not...

Page 4: ...pt when necessary for servicing the system 12 Release the refrigerant charge into the system Open both the liq uid and vapor valves by removing the plunger cap and with an allen wrench back out counte...

Page 5: ...he complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel 3 Replace the control box cover removed in Step 2 4 All field wiring to be i...

Page 6: ...rgized in Cool 1 24VAC Humidifier Optional Part Numbers SAP Legacy 159481 031 09157 2 COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2...

Page 7: ...ype must be set to 12 3 Heat 2 Heat Pump Thermostat Installer Setup 0190 Changeover Valve must be set to 0 O B terminal Energized in Cooling Thermostat Installer Setup 0200 Backup Heat Source must be...

Page 8: ...whenever additional refrigerant is required for the system charge A superheat charging method is not suitable for TXV equipped systems Measurement Method If a calibrated charging cylinder or accurate...

Page 9: ...thermostat demand to provide cooling as needed An attempt to start the compressor without at least 8 hours of crankcase heat will damage the compressor TABLE 1 R 410A Saturation Properties Temp F Pre...

Page 10: ...proper operation and maintenance of all other system components MAINTENANCE 1 Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit Clean as often as necessar...

Page 11: ...538605 UIM B 1009 Johnson Controls Unitary Products 11 SECTION VI WIRING DIAGRAM FIGURE 10 Wiring Diagram Single Phase 14 5 SEER 5 Ton...

Page 12: ...ge without notice Published in U S A 538605 UIM B 1009 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes 538605 UIM A 0909 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: