FORM 150.75-NM2
67
YORK INTERNATIONAL
This display shows the Low Ambient Cut-out pro-
grammed at the time of the fault.
This display shows the Low Pressure Cut-out pro-
grammed at the time of the fault.
This message indicates which system of the Master
Module was in the lead at the time of the fault.
This MUST always be in the Remote Mode. See page
39.
This message indicates the type of chilled water con-
trol selected at the time of the fault. LCHWT = Leaving
Water Control. ECHWT = Entering or Return Water
Control. LCHWT MUST always be selected. See page
51.
This display shows the Cooling Range (CONTROL
RANGE, CR) which was selected at the time of the fault.
This message indicates whether Compressor 1 was ON
or OFF at the time of the fault.
This message indicates SYS 1 motor current at the time
of the fault.
This message informs the operator of the nature of the
fault which occurred, if it is on the SLAVE Module.
This message indicates the Return Water Temperature
to the MASTER Module at the time of the fault.
This message indicates the Return Water Temperature
to the SLAVE Module at the time of the fault.
This message indicates the Leaving Water Tempera-
ture from the MASTER Module at the time of the fault.
This message indicates the Leaving Water Tempera-
ture from the SLAVE Module at the time of the fault.
This message indicates the Mixed Leaving Water Tem-
perature at the time of the fault.
This display shows the Low Water Cut-out (Leaving)
which was programmed at the time of the fault.
This display shows the Setpoint Temp which was pro-
grammed at the time of the fault.
This message indicates the Outdoor Ambient Tempera-
ture at the time of the fault.
R E T U R N
W A T E R
T E M P
1
5 2 . 7
D E G F
L E A V I N G
W A T E R
T E M P
1
4 4 . 3
D E G F
L O W
W A T E R
C U T O U T
3 6 . 0
D E G F
S Y S # 3
N O
F A U L T S
S Y S # 4
N O
F A U L T S
R E T U R N
W A T E R
T E M P
2
5 2 . 7
D E G F
L E A V I N G
W A T E R
T E M P
2
4 4 . 3
D E G F
S E T P O I N T
T E M P
4 4 . 0
D E G F
O U T S I D E
A I R
T E M P
7 7 . 6
D E G F
L O W
A M B I E N T
C U T O U T
3 5 . 0
D E G F
L O W
P R E S S U R E
C U T O U T
4 4
P S I G
L E A D
S Y S T E M
S Y S
1
L O C A L
R E M O T E
S E T T I N G
R E M O T E
C O N T R O L
T Y P E
L C H W T
C O O L I N G
R A N G E
4 5 . 0
T O
4 7 . 0
D E G F
S Y S
1
C O M P R E S S O R
O N
S Y S
1
M O T O R
A M P S
7 4 % F L A
M I X E D
W A T E R
T E M P
4 4 . 2
D E G F