York YCIV 0157-0397 60Hz Start-Up Checklist Download Page 9

FORM 201.23-CL1 (309)

JOHNSON CONTROLS 

9

CHECkIng SUBCOOLIng anD SUPERHEat

The  subcooling  should  always  be  checked  when 

charging  the  system  with  refrigerant  and/or  before 

checking the superheat. The subcooling measurement 

should  always  be  taken  with  the  system  loaded,  the 

economizer solenoid energized, and the level in the flash 

tank reasonably stable with a level of approximately 

35%. 

It may be desirable to check subcooling 

with one compressor running to allow 

the compressor to operate at full speed 

for a period of time to stabilize system 

temperatures and pressures.

When  the  refrigerant  charge  is  correct,  there  will  be 

no  bubbles  in  the  liquid  sight  glass  with  the  system  

operating under full load conditions, and there will be 

5 - 7°F (2.77 - 3.78°C) subcooled liquid leaving the 

condenser.  Subcooling should be set at 10°F (5.56°C). 

An  overcharged  system  should  be  guarded  against. 

Evidence of overcharge

 is as follows

:

a.  If a system is overcharged, the discharge pressure 

will be higher than normal. (Normal discharge/

condensing pressure can be found in the refrigerant 

temperature/pressure chart in IOM; use entering air 

tempe30°F (17°C) for normal condensing 

temperature.

b.  The temperature of the liquid refrigerant out of the 

condenser should be about 5-7°F 

(2.77 - 3.78°C)

 less 

than the condensing temperature (The temperature  

corresponding to the condensing pressure from the 

refrigerant temperature/pressure chart).

The subcooling temperature of each system should be 

calculated by recording the temperature of the liquid 

line  at  the  outlet  of  the  condenser  and  subtracting  it 

from the recorded liquid line pressure at the liquid stop 

valve, converted to temperature from the temperature/

pressure chart in IOM.  

DatE/tImE, DaILY SCHEDULE, anD CLOCk 

JUmPER

12. Set the Date and Time.
13. Program the Daily Schedule start and stop times.
14. Place the panel in Service mode and turn on each 

fan stage one by one.  Assure the fans rotate in the 

correct direction, so air flow exits the top of the 

chiller.

15. Remove the cap on the fill tube and run the glycol 

pump to verify the level in the fill tube.  Assure 

the glycol level in the VSD cooling system is 9-15 

inches (23-28 cm) from the top of the fill tube 

while running.  The pump can be run by placing the 

chiller in the SERVICE mode.  Be sure to re-install 

the cap before stopping the glycol pump to avoid 

overflowing the fill tube when the glycol pump 

is turned off.  The glycol system holds about 3.5 

gallons of coolant on the largest chiller model.

InItIaL StaRt-UP

After the control panel has been programmed and the 

compressor heaters have been energized for at least 8 

hours (ambient temperature > 96ºF (36ºC)) or 24 hours 

(ambient temperature < 86ºF (30ºC)), the chiller may 

be placed in operation.

1.  Turn  on  the  UNIT  SWITCH  and  program  the 

System Switches on the Keypad to the "ON" posi-

tion.

2.  If cooling demand permits, the compressor(s) will 

start and a flow of refrigerant will be noted in the 

sight glass, after the anti recycle timer times out and 

the precharge of the DC Bus is completed. After 

several minutes of operation, the bubbles in the 

sight glass will disappear and there will be a solid 

column of liquid when the drain and feed valves 

stabilize the flash tank level.  

3.  Allow the compressor to run a short time, being 

ready to stop it immediately if any unusual noise or  

adverse conditions develop. Immediately at start-

up, the compressor may make sounds different from 

its normal high-pitched sound. This is due to the 

compressor coming up to speed and the initial lack 

of an oil film sealing the clearances in the rotors. 

This should be of no concern and lasts for only a 

short time.

4.  Check the system operating parameters. Do this 

by selecting various displays such as pressures and  

temperatures.  Compare  these  to  test  gauge  

readings.

Summary of Contents for YCIV 0157-0397 60Hz

Page 1: ...denser coils with the full operating charge as given in the Technical Data Section Service and Oil Line Valves Open each compressor suction economizer and discharge service valve If valves are of the back seat type open them fully counterclockwise then close one turn of the stem to ensure operating pressure is fed to pressure transducers Open the liquid line service valve and oil return line ball ...

Page 2: ...fore placing the unit back in service valves should be opened and power must be switched on if power is removed for more than 8 hours for at least 8 hours 24 hours if ambient temperature is below 86 F 30 C before the unit is restarted Flow Switch Verify a chilled water flow switch is correctly fitted in the customer s piping on the cooler outlet and wired into the control panel correctly using shi...

Page 3: ...rigerant will be seen in the liquid line sight glass After several minutes of operation and provided a full charge of refrigerant is in the system the bubbles will disappear and be replaced by a solid column of liquid Loading Once the unit has been started all operations are fully automatic After an initial period at minimum capacity the control system will adjust the unit load depending on the ch...

Page 4: ... the sight glass If subcooling is out of range add or remove refrigerant as required to clear the sight glass Do not overcharge the unit Subcooling should be checked with a flash tank level of approximately 35 with a clear sight glass General Operation After completion of the above checks for System 1 switch OFF the SYS 1 switch on the keypad and repeat the process for each subsequent system When ...

Page 5: ...properly charged and there are no piping leaks 4 Open each system suction service valve discharge service valve economizer service valve liquid line stop valve and oil line ball valve 5 The oil separator oil level s should be maintained so that an oil level is visible in either of the oil sepa rator sight glasses when a compressor is running at high speeds for 10 to 15 minutes An oil level may not...

Page 6: ...ss the cooler Excessive flow may cause catastrophic damage to the evaporator 7 Check the control panel to ensure it is free of foreign material wires metal chips tools documents etc 8 Visually inspect wiring power and control Wiring MUST meet N E C and local codes 9 Check tightness of the incoming power wiring inside the power panel and inside the motor ter minal boxes 10 Check for proper size fus...

Page 7: ...d using the arrow keys scroll to the compressor overload settings Verify the Fac tory Set overload potentiometer s on the VSD logic board are set correctly In the unlikely event that they are not set correctly adjust the potenti ometers until the desired values are achieved The VSD is powered up and live High voltage exists in the area of the cir cuit board on the bus bars VSD Pole Assemblies and ...

Page 8: ... CONTACT YORK REPRESENTATIVE Programmed Values 10 Program the required operating values into the micro for cutouts safeties etc and record them in the chart below Suction Press Cutout ________________________ PSIG kPa Low Ambient Cutout ________________________ F C Leaving Chilled Liquid Temp Cutout ________________________ F C Motor Current Limit ________________________ FLA Pulldown Current Limi...

Page 9: ...e Daily Schedule start and stop times 14 Place the panel in Service mode and turn on each fan stage one by one Assure the fans rotate in the correct direction so air flow exits the top of the chiller 15 Remove the cap on the fill tube and run the glycol pump to verify the level in the fill tube Assure the glycol level in the VSD cooling system is 9 15 inches 23 28 cm from the top of the fill tube ...

Page 10: ...e entering the compressor and the temperature corresponding to the suction pressure as shown in a standard pressure temperature chart SUPERHEAT Example Suction Temp 46 F 8 C minus Suction Press 30 PSIG converted to Temp 35 F 1 C 11 F 6 C The suction temperature should be taken 6 13 mm before the compressor suction service valve and the suction pressure is taken at the compressor suction service va...

Page 11: ...FORM 201 23 CL1 309 JOHNSON CONTROLS 11 notes ...

Page 12: ... 861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2009 ALL RIGHTS RESERVED Form 201 23 CL1 309 Supersedes Nothing ...

Reviews: