York YCIV 0157-0397 60Hz Start-Up Checklist Download Page 6

FORM 201.23-CL1 (309)

6

 

JOHNSON CONTROLS

    Sight glasses will vary in type depending upon 

the manufacturer of the separator. One type will 

have balls that float in the sight glasses to indicate 

level. Another type will have a bulls' eye glass.  The 

bulls' eye glass will tend to appear to lose the lines 

in the bulls' eye when the level is above the glass. 

Oil level should not be above the top sight glass. 

In the rare situation where oil levels are high, drain 

oil to lower the level to the bottom of the top sight 

glass. 

    Oil levels in the oil separators above the top sight 

glass in either oil separator should be avoided and 

may cause excessive oil carryover in the system.  

High oil concentration in the system may cause  

nuisance  trips  resulting  from  incorrect  readings 

on  the  level  sensor  and  temperature  sensors.   

Temperature  sensor  errors  may  result  in  poor  

refrigerant control and liquid overfeed to the com-

pressor.

    In the unlikely event it is necessary to add oil, con-

nect a YORK oil pump to the charging valve on the 

oil separator, but do not tighten the flare nut on the 

delivery tubing. With the bottom (suction end) of 

the pump submerged in oil to avoid entrance of air, 

operate the pump until oil drips from the flare nut 

joint, allowing the air to be expelled, and tighten the 

flare nut. Open the Compressor oil charging valve 

and pump in oil until it reaches the proper level as 

described above.

When oil levels are high, adding oil 

may not visibly increase the level in the 

separators during operation.  This may 

be an indication the level is already too 

high and the oil is being pumped out 

into the system where it will cause heat 

transfer and control problems.

6.  Ensure  water  pumps  are  on.  Check  and  adjust  

water pump flow rate and pressure drop across the 

cooler.

Excessive flow may cause catastrophic 

damage to the evaporator.

 

7.  Check  the  control  panel  to  ensure  it  is  free  of  

foreign  material  (wires,  metal  chips,  tools,  

documents, etc.).

8.  Visually inspect wiring (power and control). Wiring 

MUST meet N.E.C. and local codes

.

9.  Check  tightness  of  the  incoming  power  wiring  

inside the power panel and inside the motor ter-

minal boxes.

10.  Check for proper size fuses in control circuits.

11.  Verify that field wiring matches the 3-phase power 

requirements of the chiller. 

12.  Be certain all water temperature sensors are inserted 

completely in their respective wells and are coated 

with heat conductive compound.

13.  Ensure the suction line temperature sensors are 

strapped onto the suction lines at 4 or 8 O’clock 

positions.

14.  Assure the glycol level in the VSD cooling system 

is 9-15 inches (23-28 cm) from the top of the fill 

tube. This check should be performed prior to run-

ning the pump. 

15.  Check to assure the remote start/stop for Sys #1 

on Terminals 2 to 15 and Sys #2 on Terminals 2 to 

16 are closed on the User Terminal Block 1TB to  

allow the systems to run.  If remote cycling devices 

are not utilized, place a wire jumper between these 

terminals.

Never  run  the  glycol  pump  without 

coolant!    Running  the  glycol  pump 

without coolant may damage the pump 

seals.

Always fill the system with approved 

YORK coolant to avoid damage to the 

pump seals and the chiller.

16.  Ensure that the CLK jumper JP2 on the Chiller 

Control Board is in the ON position.

17.  Assure  a  flow  switch  is  connected  between  

Terminals 2 and 13 on the User Terminal Block 

1TB in the panel.  Throttle back flow to assure 

the flow switch opens with a loss of flow.  It is 

 

recommended  that  auxiliary  pump  contacts  be 

placed in series with the flow switch for additional 

protection, if the pump is turned off during chiller 

operation.  Whenever the pump contacts are used, 

the coil of the pump starter should be suppressed 

with an RC suppressor (031-00808-000). 

Summary of Contents for YCIV 0157-0397 60Hz

Page 1: ...denser coils with the full operating charge as given in the Technical Data Section Service and Oil Line Valves Open each compressor suction economizer and discharge service valve If valves are of the back seat type open them fully counterclockwise then close one turn of the stem to ensure operating pressure is fed to pressure transducers Open the liquid line service valve and oil return line ball ...

Page 2: ...fore placing the unit back in service valves should be opened and power must be switched on if power is removed for more than 8 hours for at least 8 hours 24 hours if ambient temperature is below 86 F 30 C before the unit is restarted Flow Switch Verify a chilled water flow switch is correctly fitted in the customer s piping on the cooler outlet and wired into the control panel correctly using shi...

Page 3: ...rigerant will be seen in the liquid line sight glass After several minutes of operation and provided a full charge of refrigerant is in the system the bubbles will disappear and be replaced by a solid column of liquid Loading Once the unit has been started all operations are fully automatic After an initial period at minimum capacity the control system will adjust the unit load depending on the ch...

Page 4: ... the sight glass If subcooling is out of range add or remove refrigerant as required to clear the sight glass Do not overcharge the unit Subcooling should be checked with a flash tank level of approximately 35 with a clear sight glass General Operation After completion of the above checks for System 1 switch OFF the SYS 1 switch on the keypad and repeat the process for each subsequent system When ...

Page 5: ...properly charged and there are no piping leaks 4 Open each system suction service valve discharge service valve economizer service valve liquid line stop valve and oil line ball valve 5 The oil separator oil level s should be maintained so that an oil level is visible in either of the oil sepa rator sight glasses when a compressor is running at high speeds for 10 to 15 minutes An oil level may not...

Page 6: ...ss the cooler Excessive flow may cause catastrophic damage to the evaporator 7 Check the control panel to ensure it is free of foreign material wires metal chips tools documents etc 8 Visually inspect wiring power and control Wiring MUST meet N E C and local codes 9 Check tightness of the incoming power wiring inside the power panel and inside the motor ter minal boxes 10 Check for proper size fus...

Page 7: ...d using the arrow keys scroll to the compressor overload settings Verify the Fac tory Set overload potentiometer s on the VSD logic board are set correctly In the unlikely event that they are not set correctly adjust the potenti ometers until the desired values are achieved The VSD is powered up and live High voltage exists in the area of the cir cuit board on the bus bars VSD Pole Assemblies and ...

Page 8: ... CONTACT YORK REPRESENTATIVE Programmed Values 10 Program the required operating values into the micro for cutouts safeties etc and record them in the chart below Suction Press Cutout ________________________ PSIG kPa Low Ambient Cutout ________________________ F C Leaving Chilled Liquid Temp Cutout ________________________ F C Motor Current Limit ________________________ FLA Pulldown Current Limi...

Page 9: ...e Daily Schedule start and stop times 14 Place the panel in Service mode and turn on each fan stage one by one Assure the fans rotate in the correct direction so air flow exits the top of the chiller 15 Remove the cap on the fill tube and run the glycol pump to verify the level in the fill tube Assure the glycol level in the VSD cooling system is 9 15 inches 23 28 cm from the top of the fill tube ...

Page 10: ...e entering the compressor and the temperature corresponding to the suction pressure as shown in a standard pressure temperature chart SUPERHEAT Example Suction Temp 46 F 8 C minus Suction Press 30 PSIG converted to Temp 35 F 1 C 11 F 6 C The suction temperature should be taken 6 13 mm before the compressor suction service valve and the suction pressure is taken at the compressor suction service va...

Page 11: ...FORM 201 23 CL1 309 JOHNSON CONTROLS 11 notes ...

Page 12: ... 861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2009 ALL RIGHTS RESERVED Form 201 23 CL1 309 Supersedes Nothing ...

Reviews: