The chilled liquid is glycol. The Cooling Setpoint can be
programmed from 10°F to 70°F (-12.2°C to 21.1°C).
Option 5 – Ambient Control Type
The low ambient cutout is adjustable from 25°F to 60°F
(-3.9°C to 15.6°C).
or
The low ambient cutout is programmable down to 0°F
(-17.8°C). A low ambient kit MUST be installed for this
option to be chosen.
Option 6 – Local/Remote Control Type
When programmed for LOCAL, an ISN or RCC control
can be used to monitor only. The micro panel will oper-
ate on locally programmed values and ignore all com-
mands from the remote devices. The chiller will com-
municate and send data to the remote monitoring de-
vices.
or
This mode should be selected when an ISN or RCC
control is to be used to control the chiller. This mode will
allow the ISN to control the following items: Remote
Start/Stop, Cooling Setpoint, Load Limit, and History
Buffer Request. If the unit receives no valid ISN trans-
mission for 5 minutes, it will revert back to the locally
programmed values.
Option 7 – Unit Control Mode
Unit control is based on return chilled liquid temp. It can
only be selected on units that have 4 or 6 compressors
(dual system units).
or
Unit control is based on leaving chilled liquid temp.
Refer to section on Capacity Control for details on load-
ing and unloading sequences.
L O C A L / R E M O T E
M O D E
R E M O T E
A M B I E N T
C O N T R O L
S T A N D A R D
C H I L L E D
L I Q U I D
G L Y C O L
A M B I E N T
C O N T R O L
L O W
A M B I E N T
L O C A L
/
R E M O T E
M O D E L
L O C A L
C O N T R O L
M O D E
R E T U R N
L I Q U I D
C O N T R O L
M O D E
L E A V I N G
L I Q U I D
Unit Controls
Summary of Contents for YCAL0080SC
Page 115: ...YORK INTERNATIONAL 115 FORM 150 62 NM1 This page intentionally left blank 4...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0034SC FIG 13 ELEMENTARY DIAGRAM Wiring Diagrams...
Page 119: ...YORK INTERNATIONAL 119 FORM 150 62 NM1 This page intentionally left blank 4...
Page 130: ...APPENDIX 1 DIMENSIONS FIG 19 TYPE CP 1 FIG 20 TYPE CP 2 LD03839 LD03840 Appendix 1 Isolators...
Page 135: ...YORK INTERNATIONAL 135 FORM 150 62 NM1 This page intentionally left blank...