background image

JOHNSON CONTROLS

4

NOTES:
1.  kW

o =.

Unit kW Cooling Capacity Output

2

.  kW

i = 

Compressor kW Input

3.  COP = Coefficient of Performance (Based upon compressor and fan input kW)

4.  LCWT = Leaving Chilled Water Temperature
5.  Ratings based upon 0.15L/s cooler water per kW

Ratings - 

R-407C (SI Units)

YCAL0050EB 

COP=4.03

YCAL0060EB    

COP=4.26

YCAL0064EB    

COP=4.01

YCAL0070EB    

COP=4.05

 AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

(°C)

25°C

30°C

35°C

40°C

45°C

50°C

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

5.0

178.1 48.7

3.3

169.3 54.2

2.8

160.1 60.1

2.4

150.7 66.7

2.1

105.8 50.7

1.9

71.2

36.2

1.7

6.0

184.2 49.1

3.4 175°F  54.5

2.9

165.5 60.6

2.5

155.9 67.1

2.1

109.5 51.0

1.9

73.7

36.5

1.8

7.0

190.3 49.4

3.5

180.9 54.9

3.0

171.1 61.0

2.6

161.2 67.6

2.2

113.4 51.3

2.0

76.6

36.6

1.8

8.0

196.5 49.8

3.6

186.8 55.3

3.1

176.8 61.4

2.6

166.6 68.1

2.3

117.5 51.6

2.1

79.4

36.7

1.9

9.0

202.9 50.2

3.6

192.9 55.7

3.2

182.6 61.8

2.7

172.1 68.6

2.3

121.6 51.9

2.1

82.3

36.9

1.9

10.0 209.3 50.6

3.7

199.1 56.1

3.2

188.5 62.3

2.8

177.7 69.1

2.4

125.8 52.2

2.2

85.2

37.1

2.0

11.0 216.0 51.1

3.8

205.4 56.6

3.3

194.6 62.8

2.9

183.5 69.6

2.4

130.1 52.5

2.2

88.3

37.2

2.1

 AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

(°C)

25°C

30°C

35°C

40°C

45°C

50°C

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

5.0

196.2 50.8

3.5

187.6 56.1

3.0

178.0 62.4

2.6

168.4 69.1

2.3

158.1 76.8

1.9

79.2

38.3

1.8

6.0

202.9 51.1

3.6

193.3 56.8

3.1

183.4 63.2

2.7

173.3 70.1

2.3

162.7 77.9

2.0

82.2

38.4

1.9

7.0

209.8 51.4

3.7

199.9 57.1

3.2

189.7 63.5

2.7

179.2 70.5

2.4

168.4 78.2

2.0

85.2

38.5

1.9

8.0

216.7 51.7

3.8

206.5 57.5

3.3

196.0 63.9

2.8

185.2 70.9

2.4

174.2 78.6

2.1

88.2

38.7

2.0

9.0

223.8 52.0

3.9

213.3 57.8

3.4

202.5 64.2

2.9

191.4 71.4

2.5

180.0 79.1

2.1

91.4

38.8

2.1

10.0 230.9 52.4

4.0

220.2 58.2

3.5

209.1 64.7

3.0

197.7 71.8

2.6

185.9 79.7

2.2

94.7

38.9

2.1

11.0 238.2 52.7

4.1

227.2 58.6

3.5

215.8 65.1

3.1

204.1 72.3

2.6

104.5 35.1

2.6

98.0

39.1

2.2

 AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

(°C)

25°C

30°C

35°C

40°C

45°C

50°C

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

5.0

219.1 59.7

3.3

207.5 66.4

2.8

195.8 73.8

2.4

183.9 81.9

2.1

172.3 90.5

1.8

113.0 61.6

1.7

6.0

226.5 60.1

3.4

214.6 66.9

2.9

202.5 74.3

2.5

190.4 82.4

2.1

178.4 91.2

1.8

116.9 62.2

1.7

7.0

233.9 60.5

3.5

221.7 67.3

3.0

209.3 74.9

2.6

196.9 83.0

2.2

155.5 72.0

2.0

121.2 62.5

1.8

8.0

241.5 61.0

3.6

229.1 67.8

3.1

216.3 75.4

2.6

203.6 83.6

2.3

161.0 72.4

2.0

125.7 62.8

1.8

9.0

249.4 61.5

3.7

236.6 68.3

3.2

223.4 76.0

2.7

210.3 84.2

2.3

166.6 72.8

2.1

130.3 63.1

1.9

10.0 257.4 61.9

3.7

244.1 68.8

3.2

230.7 76.5

2.8

217.3 84.9

2.4

172.4 73.2

2.2

135.0 63.4

1.9

11.0 265.5 62.5

3.8

251.9 69.4

3.3

238.2 77.1

2.8

224.4 85.5

2.4

178.3 73.7

2.2

139.8 63.7

2.0

 AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

(°C)

25°C

30°C

35°C

40°C

45°C

50°C

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

5.0

244.4 65.2

3.4

231.7 72.5

2.9

218.6 80.7

2.5

205.2 89.5

2.1

191.8 98.9

1.8

125.9 67.3

1.7

6.0

252.6 65.7

3.5

239.6 73.0

3.0

226.1 81.2

2.6

212.3 90.1

2.2

198.7 99.5

1.9

130.6 67.7

1.8

7.0

261.1 66.2

3.6

247.6 73.5

3.1

233.7 81.8

2.6

219.7 90.7

2.3

205.7 100.2

1.9

135.4 68.1

1.8

8.0

269.7 66.7

3.7

255.8 74.1

3.2

241.6 82.3

2.7

227.2 91.3

2.3

212.9 100.9

2.0

139.5 69.1

1.8

9.0

278.5 67.2

3.8

264.2 74.6

3.2

249.6 82.9

2.8

234.8 92.0

2.4

220.2 101.7

2.0

144.7 69.4

1.9

10.0 287.5 67.8

3.9

272.8 75.2

3.3

257.8 83.6

2.9

242.6 92.7

2.4

160.5 63.1

2.3

150.0 69.8

2.0

11.0 296.7 68.4

3.9

281.6 75.8

3.4

266.2 84.2

2.9

250.7 93.4

2.5

166.2 63.4

2.4

155.5 70.1

2.0

Summary of Contents for YCAL0014

Page 1: ...FORM 150 62 EG1 507 AIR COOLED SCROLL CHILLERS STYLE C YCAL0014 YCAL0134 13 130 TON 46 456 kW 60 Hz R 22 on select models only R 407C on all models...

Page 2: ...glish 48 Dimensions YCAL0024 YCAL0034 English 50 Dimensions YCAL0040 YCAL0060 English 52 Dimensions YCAL0064 YCAL0080 English 54 Dimensions YCAL0090 YCAL0094 English 56 Dimensions YCAL0104 English 58...

Page 3: ...s using central station air handling or terminal units They are completely self contained and are designed for outdoor roof or ground level installation Each unit includes hermetic scroll compressors...

Page 4: ...cooler is equipped with a heater controlled by a separate thermostat The heater provides freeze pro tection for the cooler down to 20o F 29 C ambient The cooler is covered with 3 4 flexible closed ce...

Page 5: ...f compressors Low liquid temperature cutout Low suction pressure cutout High discharge pressure cutout Anti recycle timer compressor start cycle time Anti coincident timer delay compressor starts UNIT...

Page 6: ...ue to AC powered failure battery discharge Programmed setpoints are retained in lithium battery backed RTC memory for 5 years minimum POWER PANEL Each panel contains Compressor power terminals Compres...

Page 7: ...ompliance with N E C Article 440 14 can be supplied to isolate the power voltage for servicing This option includes the Single Point Power connection CONTROL TRANSFORMER Converts unit power volt age t...

Page 8: ...installed on only refrigerant system 1 on two circuited units Factory mounted DX COOLER 300 21 bar PSIG DWP WATERSIDE The waterside will be of 300 PSIG 21 bar instead of the stan dard 150 PSIG DWP 300...

Page 9: ...t Consists of welded wire mesh guards mounted on the exterior of the unit Pre vents unauthorized access yet provides free air flow Factory mounted WIRE LOUVERED PANELS Consists of welded wire mesh pan...

Page 10: ...JOHNSON CONTROLS 10 This page intentionally left blank...

Page 11: ...refrigeration TR 2 Entering and Leaving Liquid Temperatures 3 Outside ambient air temperature in degrees F 4 GPM of chilled liquid Determine capacity requirements from the following formula GPM TR x 2...

Page 12: ...p 6 5 x 1 096 or 7 1 Ft H2 O 10 YCAL0040 is suitable 3 From the Ratings on pages 16 46 SELECT YCAL0050 English Units 53 1 Tons 48 7 Compressor kW 11 7 Unit EER 4 Calculate Compressor kW at 50 Tons kW...

Page 13: ...4 40 55 60 325 0 125 0050 40 55 60 325 0 125 0060 40 55 60 325 0 125 0064 40 55 100 350 0 125 0070 40 55 100 350 0 125 0074 40 55 100 350 0 125 0080 40 55 100 400 0 125 0090 40 55 138 525 0 125 0094 4...

Page 14: ...um and maximum water flow ranges See page 13 for minimum and maximum flow points ENGLISH MODEL YCAL COOLER CURVE 0014 0020 A 0024 B 0030 0034 C 0040 0042 0044 0050 0060 D 0064 0070 0074 E 0080 F 0090...

Page 15: ...imum and maximum water flow ranges See page 13 for minimum and maximum flow points SI MODEL YCAL COOLER CURVE 0014 0020 A 0024 B 0030 0034 C 0040 0042 0044 0050 0060 D 0064 0070 0074 E 0080 F 0090 009...

Page 16: ...85 6 11 4 85 8 90 6 10 6 83 6 95 7 9 8 81 2 101 2 9 0 46 0 93 8 76 9 13 5 91 7 81 3 12 5 89 5 86 0 11 6 87 2 91 0 10 7 84 9 96 2 9 9 82 6 101 7 9 1 48 0 96 9 77 7 13 8 94 7 82 1 12 8 92 4 86 9 11 8 9...

Page 17: ...6 7 2 48 0 79 9 6 6 45 0 78 9 106 9 8 3 76 4 112 8 7 7 74 0 119 0 7 1 50 4 75 9 7 3 48 8 80 1 6 7 46 0 80 2 107 4 8 4 77 7 113 3 7 8 75 2 119 6 7 1 51 3 76 1 7 4 49 5 80 4 6 8 48 0 82 8 108 4 8 6 80...

Page 18: ...26 2 99 8 13 3 123 4 104 9 12 4 120 7 110 3 11 6 117 8 116 1 10 8 115 0 122 3 10 1 112 0 128 9 9 4 48 0 130 5 101 0 13 6 127 7 106 1 12 7 124 8 111 5 11 9 121 9 117 3 11 1 118 9 123 5 10 4 115 9 130 2...

Page 19: ...9 7 9 100 8 151 0 7 3 97 4 159 7 6 7 94 0 168 9 6 2 46 0 109 0 136 0 8 7 105 9 143 6 8 0 102 6 151 7 7 4 99 2 160 4 6 8 66 9 104 0 6 8 48 0 112 8 137 3 8 9 109 6 144 9 8 3 106 2 153 1 7 6 102 8 161 8...

Page 20: ...2 3 0 293 9 107 3 2 6 277 8 118 2 2 2 184 8 78 4 2 2 10 0 348 6 80 3 4 0 333 9 88 7 3 5 318 6 98 0 3 0 302 7 108 3 2 6 286 0 119 2 2 3 190 6 78 9 2 2 11 0 358 5 81 1 4 1 343 6 89 5 3 6 327 9 98 9 3 1...

Page 21: ...0 2 135 9 2 7 379 6 149 9 2 3 357 8 165 6 2 0 10 0 470 4 104 1 4 0 451 8 113 8 3 5 432 6 124 8 3 1 412 7 137 1 2 7 391 7 151 1 2 4 369 3 166 9 2 0 11 0 484 8 105 2 4 1 465 6 114 9 3 6 445 9 125 9 3 2...

Page 22: ...2 22 1 11 7 23 6 23 3 10 8 22 9 24 7 10 0 22 1 26 2 9 2 21 4 27 8 8 4 46 0 25 4 21 0 12 8 24 7 22 2 11 9 24 0 23 5 11 0 23 3 24 8 10 1 22 6 26 3 9 3 21 8 27 9 8 5 48 0 26 3 21 1 13 2 25 6 22 3 12 2 24...

Page 23: ...2 26 8 6 2 7 9 12 4 6 2 7 6 13 3 5 7 45 0 16 6 23 9 7 4 16 0 25 4 6 8 15 5 26 9 6 3 8 0 12 5 6 3 7 7 13 3 5 8 46 0 16 9 24 0 7 6 16 3 25 5 6 9 15 8 27 0 6 4 8 2 12 5 6 4 7 9 13 3 5 9 48 0 17 5 24 2 7...

Page 24: ...0 4 34 1 12 2 38 8 37 2 10 9 37 7 39 5 10 0 37 0 40 9 9 5 35 8 43 5 8 8 46 0 42 3 32 2 13 4 41 2 34 2 12 4 39 6 37 1 11 1 38 4 39 5 10 2 37 7 41 0 9 7 36 5 43 6 8 9 48 0 43 9 32 3 13 9 42 7 34 4 12 8...

Page 25: ...7 2 31 8 51 9 6 6 16 0 25 1 6 3 15 5 26 6 5 8 45 0 34 7 46 2 8 0 33 5 49 0 7 4 32 4 52 0 6 7 16 4 25 1 6 4 15 8 26 7 5 9 46 0 35 4 46 3 8 2 34 2 49 1 7 5 33 0 52 1 6 9 16 7 25 1 6 5 16 1 26 7 6 0 48 0...

Page 26: ...9 2 53 3 12 1 57 6 56 5 11 1 56 0 60 0 10 2 54 3 63 6 9 4 52 7 67 4 8 7 46 0 61 8 50 4 13 2 60 2 53 5 12 2 58 6 56 7 11 3 57 0 60 1 10 4 55 3 63 8 9 6 53 7 67 6 8 8 48 0 64 1 50 7 13 6 62 4 53 8 12 6...

Page 27: ...2 46 7 79 9 6 5 24 3 37 6 6 7 23 4 39 9 6 2 45 0 51 0 71 4 8 0 49 3 75 6 7 3 25 7 35 5 7 5 24 8 37 7 6 9 23 8 39 9 6 3 46 0 51 9 71 7 8 1 50 2 75 9 7 4 26 2 35 6 7 6 25 3 37 7 7 0 24 3 40 0 6 4 48 0...

Page 28: ...84 4 89 3 10 5 81 9 94 7 9 7 79 4 100 4 8 9 76 8 106 5 8 1 46 0 90 8 79 8 12 6 88 3 84 7 11 6 85 9 89 7 10 7 83 4 95 2 9 8 80 8 100 9 9 0 78 2 107 0 8 3 48 0 93 9 80 6 12 9 91 4 85 5 11 9 88 9 90 6 11...

Page 29: ...81 0 6 3 44 4 85 7 5 8 45 0 74 2 112 8 7 4 71 6 119 5 6 8 49 0 76 6 7 1 47 2 81 2 6 4 45 3 86 0 5 9 46 0 75 6 113 3 7 5 62 3 96 2 7 3 50 0 76 8 7 2 48 1 81 4 6 5 46 2 86 3 6 0 48 0 78 3 114 4 7 8 53 8...

Page 30: ...46 0 124 5 102 5 12 8 121 3 108 2 11 9 117 8 114 3 11 0 114 3 120 7 10 2 110 6 127 8 9 3 106 8 135 6 8 5 48 0 129 1 103 6 13 1 125 7 109 3 12 2 122 2 115 4 11 3 118 6 121 9 10 4 114 8 129 0 9 6 110 9...

Page 31: ...6 7 152 9 6 9 92 4 163 1 6 2 88 0 174 4 5 6 59 6 113 8 5 6 46 0 102 8 144 1 7 8 98 6 153 4 7 1 94 3 163 6 6 4 89 7 174 9 5 7 60 9 114 0 5 7 48 0 106 7 145 2 8 0 102 5 154 5 7 3 98 0 164 7 6 6 93 4 175...

Page 32: ...9 0 73 7 17 3 3 7 69 9 19 3 3 2 66 0 21 5 2 7 62 3 23 9 2 3 58 6 26 6 2 0 29 7 12 9 1 9 10 0 76 1 17 4 3 8 72 2 19 4 3 3 68 3 21 6 2 8 64 4 24 1 2 4 60 6 26 7 2 1 30 8 12 9 2 0 11 0 78 6 17 5 3 9 74...

Page 33: ...3 33 2 4 0 144 6 37 6 3 4 136 8 42 0 2 9 130 5 45 9 2 5 122 9 51 2 2 2 60 7 25 8 1 9 10 0 158 4 33 3 4 1 149 8 37 6 3 5 141 8 42 0 3 0 133 8 46 9 2 6 127 2 51 4 2 2 62 9 25 8 2 0 11 0 163 7 33 4 4 2 1...

Page 34: ...2 0 3 9 213 3 57 8 3 4 202 5 64 2 2 9 191 4 71 4 2 5 180 0 79 1 2 1 91 4 38 8 2 1 10 0 230 9 52 4 4 0 220 2 58 2 3 5 209 1 64 7 3 0 197 7 71 8 2 6 185 9 79 7 2 2 94 7 38 9 2 1 11 0 238 2 52 7 4 1 227...

Page 35: ...2 2 167 7 83 4 1 9 9 0 328 0 82 6 3 7 312 0 91 7 3 2 295 3 101 9 2 7 278 1 113 2 2 3 185 8 75 6 2 3 173 4 83 9 1 9 10 0 338 2 83 3 3 8 321 7 92 5 3 2 304 6 102 8 2 8 286 9 114 1 2 4 192 1 76 1 2 3 17...

Page 36: ...7 2 5 364 7 161 6 2 1 334 9 181 4 1 7 11 0 480 7 108 2 3 9 457 5 119 1 3 4 432 6 131 4 3 0 405 9 145 8 2 5 377 4 162 6 2 1 347 0 182 3 1 8 AIR TEMPERATURE ON CONDENSER C LCWT C 25 0 30 0 35 0 40 0 45...

Page 37: ...JOHNSON CONTROLS 37 FORM 150 62 EG1 507 INTENTIONALLY LEFT BLANK...

Page 38: ...9 66 7 77 3 85 3 75 8 12 3 51 9 68 3 67 2 53 2 13 8 33 3 57 1 44 6 30 0 15 9 18 5 55 0 23 9 16 2 16 0 IPLV 13 5 EER YCAL0080EC DISPL AMBIENT DEG F TONS COMPR kW EER 100 0 95 0 82 2 95 3 9 7 83 3 87 5...

Page 39: ...3 20 66 7 25 2 300 1 75 8 3 62 51 9 20 2 236 3 53 2 4 03 33 3 14 0 156 9 30 0 4 67 18 5 12 8 84 1 16 2 4 68 IPLV 3 96 COP YCAL0080EC DISPL AMBIENT DEG C UNIT kWo COMPR kWi COP 100 0 35 0 289 0 95 3 2...

Page 40: ...8 66 7 80 3 44 4 38 0 11 9 52 2 70 2 34 5 28 1 13 2 33 3 59 6 24 1 14 3 16 4 18 8 55 0 13 1 7 9 16 4 IPLV 13 7 EER YCAL0020EB DISPL AMBIENT DEG F TONS COMPR kW EER 100 0 95 0 17 4 21 2 8 7 50 0 70 1...

Page 41: ...5 83 3 78 8 11 6 51 9 69 6 66 3 54 9 13 2 33 3 58 6 45 2 29 9 16 2 18 5 55 0 24 2 15 7 16 5 IPLV 13 3 EER YCAL0080EB DISPL AMBIENT DEG F TONS COMPR kW EER 100 0 95 0 78 0 100 0 8 8 83 3 88 0 68 9 73 6...

Page 42: ...156 3 38 0 3 49 52 2 21 2 121 4 28 1 3 85 33 3 15 3 84 8 14 3 4 79 18 8 12 8 46 0 7 9 4 80 IPLV 4 01 COP YCAL0020EB DISPL AMBIENT DEG C UNIT kWo COMPR kWi COP 100 0 35 0 61 1 21 2 2 55 50 0 21 2 35 8...

Page 43: ...93 1 78 8 3 41 51 9 20 9 233 3 54 9 3 87 33 3 14 8 159 1 29 9 4 75 18 5 12 8 84 9 15 7 4 84 IPLV 3 91 COP YCAL0080EB DISPL AMBIENT DEG C UNIT kWo COMPR kWi COP 100 0 35 0 274 4 100 0 2 57 83 3 31 1 24...

Page 44: ...rs per circuit 2 2 2 2 3 2 2 2 Compressors per unit 2 2 2 2 3 4 4 4 Nominal Tons per compressor 7 5 10 13 15 13 10 10 13 10 13 13 Condenser Total Face Area ft2 47 2 47 2 66 1 66 1 66 1 128 0 128 0 128...

Page 45: ...829 7001 7222 7809 7888 8867 10751 11039 11427 2 2 3 3 3 3 2 2 3 2 3 3 3 4 4 6 6 6 6 4 4 5 6 6 6 15 13 15 15 13 10 13 13 15 13 15 15 25 20 25 25 20 25 20 20 25 20 25 25 128 0 128 0 149 3 149 3 149 3 1...

Page 46: ...Compressors per circuit 2 2 2 2 3 2 2 2 Compressors per unit 2 2 2 2 3 4 4 4 Nominal kWo per compressor 26 35 46 53 46 35 35 46 35 46 46 Condenser Total Face Area meters2 4 4 6 6 6 12 12 12 Number of...

Page 47: ...3069 3147 3247 3542 3578 4022 4881 5011 5187 2 2 3 3 3 3 2 2 3 2 3 3 3 4 4 6 6 6 6 4 4 5 6 6 6 53 46 53 53 46 35 46 46 53 46 53 53 88 70 88 88 70 88 70 70 88 70 88 88 12 12 14 14 14 14 16 0 16 0 18 0...

Page 48: ...maintenance Site restrictions may compromise minimum clearances indicated below resulting in unpredictable airflow patterns and possible diminished performance YORK s unit controls will optimize opera...

Page 49: ...ter of Gravity in X Y Z 0014 45 4 24 2 28 8 0020 45 4 24 2 28 8 37 68 3 8 1 1 2 1 1 2 51 1 2 9 1 4 10 5 16 78 7 16 B A D C 9 24 1 4 29 3 10 1 2 62 14 11 16 80 7 16 105 1 8 X Z C G SIDE VIEW HOLES EACH...

Page 50: ...s may compromise minimum clearances indicated below resulting in unpredictable airflow patterns and possible diminished performance YORK s unit controls will optimize operation without nuisance high p...

Page 51: ...l YCAL0024 Refers to Model YCAL0030 and YCAL0034 ALUMINUM COPPER YCAL Center of Gravity in X Y Z 0024 45 0 24 4 35 3 0030 45 0 24 4 34 9 0034 45 0 25 5 33 8 YCAL Center of Gravity in X Y Z 0024 45 8 2...

Page 52: ...eration without nuisance high pressure safety cutouts however the system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than o...

Page 53: ...A 3 4 DIA 80 1 2 TOP VIEW C G Y X 50 1 1 2 HOLES TYP MOUNTING 15 1 4 1 1 2 POWER PANEL CONTROL PANEL ORIGIN 1 266 9 3 4 99 1 2 1 204 ALUMINUM COPPER YCAL Center of Gravity in X Y Z 0040 58 7 40 2 41...

Page 54: ...afety cutouts however the system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum c...

Page 55: ...in X Y Z 0060 58 6 40 2 39 8 0064 56 7 45 7 40 0 0070 56 8 45 5 40 0 0074 56 8 45 7 40 1 0080 56 8 45 5 39 6 C SIDE VIEW HOLES EACH SIDE 2 3 X 3 RIGGING G 11 1 4 X Z 24 1 4 WATER OUTLET 6 A 84 1 2 70...

Page 56: ...uts however the system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances...

Page 57: ...L Center of Gravity in X Y Z 0090 64 1 44 3 44 5 0094 64 8 44 4 44 2 WATER INLET 17 1 8 Z C G X 19 1 4 106 3 4 141 83 91 7 16 29 8 WATER OUTLET A 8 D A RIGGING HOLES EACH SIDE 148 96 2 3 X 3 D 3 4 DIA...

Page 58: ...isance high pressure safety cutouts however the system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators...

Page 59: ...Center of Gravity in X Y Z 0104 70 3 45 7 40 8 WATER INLET 17 1 8 14 1 4 Z 166 159 83 124 3 4 29 91 7 16 A D A WATER OUTLET 8 8 RIGGING HOLES EACH SIDE 96 2 3 X 3 D 3 4 DIA C HOLES TYP MOUNTING F 25...

Page 60: ...ut nuisance high pressure safety cutouts however the system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isol...

Page 61: ...FORM 150 62 EG1 507 ALUMINUM COPPER YCAL Center of Gravity in X Y Z 0114 82 2 45 5 43 7 0124 81 1 46 2 43 1 0134 81 9 46 8 42 5 YCAL Center of Gravity in X Y Z 0114 83 3 45 2 45 3 0124 82 3 45 9 44 7...

Page 62: ...m designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances Side to wall 2m rear...

Page 63: ...76 RIGGING HOLES EACH SIDE SIDE VIEW G C Z X 2670 2043 373 1575 267 3 737 616 229 235 1308 38 38 1737 940 POWER PANEL CONTROL PANEL ORIGIN 262 1993 LD04871 ALUMINUM COPPER YCAL Center of Gravity mm X...

Page 64: ...formance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances Side to wall 2m rear to wall 2m control panel to end wall 1...

Page 65: ...IGGING 3 4 WATER INLET WATER OUTLET A A ORIGIN X G C Y TOP VIEW 19 DIA MOUNTING HOLES TYP CONTROL PANEL POWER PANEL LD04860 Refers to Model YCAL0024 Refers to Model YCAL0030 and YCAL0034 ALUMINUM COPP...

Page 66: ...r must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances Side to wall 2m rear to wall 2...

Page 67: ...19 DIA 2045 TOP VIEW C G Y X 1270 38 HOLES TYP MOUNTING 387 38 POWER PANEL CONTROL PANEL ORIGIN 248 2527 LD04875 ALUMINUM COPPER YCAL Center of Gravity mm X Y Z 0040 1490 1021 1047 0042 1481 1026 100...

Page 68: ...e system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances Side to wall 2...

Page 69: ...IEW 53 229 CONTROL PANEL 248 ORIGIN Y 2527 POWER PANEL TOP VIEW C G X LD04879 ALUMINUM COPPER YCAL Center of Gravity mm X Y Z 0060 1485 1021 1001 0064 1435 1162 1001 0070 1437 1154 1002 0074 1438 1161...

Page 70: ...safety cutouts however the system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum...

Page 71: ...1064 YCAL Center of Gravity mm X Y Z 0090 1628 1125 1130 0094 1646 1127 1124 WATER INLET 435 Z C G X 490 2711 3581 2108 2323 737 8 WATER OUTLET A 8 D A RIGGING HOLES EACH SIDE 3759 2438 2 76 X 76 D 19...

Page 72: ...system designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances Side to wall 2m...

Page 73: ...5 YCAL Center of Gravity mm X Y Z 0104 1811 1155 1084 WATER INLET 435 363 C G X Z 4216 4038 2108 3169 737 2323 A D A WATER OUTLET 8 8 RIGGING HOLES EACH SIDE 2438 2 76 X 76 D 19 DIA C HOLES TYP MOUNTI...

Page 74: ...em designer must consider potential performance degradation Access to the unit control center assumes the unit is no higher than on spring isolators Recommended minimum clearances Side to wall 2m rear...

Page 75: ...FORM 150 62 EG1 507 ALUMINUM COPPER YCAL Center of Gravity mm X Y Z 0114 2115 1148 1151 0124 2089 1166 1135 0134 2106 1181 1121 YCAL Center of Gravity mm X Y Z 0114 2087 1156 1110 0124 2059 1172 1094...

Page 76: ...344 1 133 923 712 1 246 1 050 855 660 7 923 0114 1 531 1 326 1 121 916 1 439 1 246 1 053 860 9 491 0124 1 644 1 403 1 162 921 1 490 1 271 1 053 835 9 779 0134 1 704 1 469 1 235 1 000 1 499 1 293 1 08...

Page 77: ...251 1 041 832 1 364 1 169 973 777 8 867 0114 1 688 1 483 1 279 1 074 1 597 1 404 1 210 1 017 10 751 0124 1 799 1 560 1 320 1 081 1 649 1 430 1 210 990 11 039 0134 1 859 1 626 1 393 1 160 1 659 1 451 1...

Page 78: ...P 2 26 CP 2 25 0134 CP 2 28 CP 2 27 CP 2 27 CP 2 26 CP 2 27 CP 2 27 CP 2 26 CP 2 25 Aluminum Fin Seismic Isolator Selections YCAL VMC Model AEQM xxxx A B C D E F G H 0014 AEQM 97 AEQM 96 AEQM 98 AEQM...

Page 79: ...4 Blk 4 Blk 4 Blk 4 Blk 0044 4 Blk 4 Blk 4 Blk 4 Blk 0050 4 Blk 4 Blk 4 Blk 4 Blk 0060 4 Blk 4 Blk 4 Blk 4 Blk 0064 4 Red 4 Red 4 Red 4 Red 0070 4 Red 4 Red 4 Red 4 Red 0074 4 Red 4 Red 4 Red 4 Red 0...

Page 80: ...2 28 CP 2 26 0134 CP 2 32 CP 2 31 CP 2 28 CP 2 27 CP 2 31 CP 2 28 CP 2 28 CP 2 26 Copper Fin Seismic Isolator Selections VMC Model AEQM xxxx YCAL A B C D E F G H 0014 AEQM 97 AEQM 96 AEQM 98 AEQM 97...

Page 81: ...0042 4 Blk 4 Blk 4 Blk 4 Blk 0044 4 Blk 4 Blk 4 Blk 4 Blk 0050 4 Blk 4 Blk 4 Blk 4 Blk 0060 4 Blk 4 Blk 4 Blk 4 Blk 0064 4 Red 4 Red 4 Red 4 Red 0070 4 Red 4 Red 4 Red 4 Red 0074 4 Red 4 Red 4 Red 4...

Page 82: ...308439 27 ORANGE AEQM 97 301055 97 WHITE CP 1 28 308439 28 GREEN AEQM 98 301055 98 GRAY CP 1 31 308439 31 GRAY AEQM 99 301055 99 BLUE CP 2 25 308439 25 RED AEQM 1000 30106 1000 GREEN CP 2 26 308692 2...

Page 83: ...1 2 4 1 2 2 1 2 5 8 1 4 7 1 4 5 8 3 8 AEQM 99 7 5 1 2 4 1 2 2 1 2 5 8 1 4 7 1 4 5 8 3 8 AEQM 1000 8 1 2 6 1 2 6 4 1 2 3 4 3 8 8 3 8 7 8 1 2 AEQM 1300 8 1 2 6 1 2 6 4 1 2 3 4 3 8 8 3 8 7 8 1 2 AEQM 160...

Page 84: ...eration at ambient temperatures in excess of 95 F 35 C is anticipated 4 Maximum fuse size is based upon 225 of the rated load amps for the largest motor plus 100 of the rated load amps for all other l...

Page 85: ...150 110 125 110 125 10 1 14 1 0 2 4 0 37 4 278 37 4 278 2 7 6 230 60 94 100 110 125 110 125 10 1 14 1 0 2 4 0 34 6 278 34 6 278 2 7 4 380 60 54 60 60 70 60 70 10 1 14 1 0 14 2 19 9 151 19 9 151 2 4 5...

Page 86: ...575 60 49 60 60 60 60 60 10 1 14 1 0 14 2 19 0 148 19 0 148 2 3 1 0060 200 60 138 150 175 175 175 175 10 3 0 2 4 0 3 300 53 8 425 53 8 425 2 7 8 230 60 128 150 150 175 150 175 10 3 0 2 4 0 3 300 49 8...

Page 87: ...158 2 4 0 46 60 50 60 50 60 10 1 14 1 0 14 2 17 4 125 17 4 125 2 3 1 138 150 175 175 175 175 10 3 0 2 4 0 3 300 53 8 425 53 8 425 2 7 8 128 150 150 175 150 175 10 3 0 2 4 0 3 300 49 8 425 49 8 425 2 7...

Page 88: ...250 250 10 300 250 500 6 350 380 60 137 150 150 150 150 150 10 3 0 2 4 0 2 4 0 460 60 113 150 125 125 125 125 10 1 2 4 0 2 4 0 575 60 90 100 100 100 100 100 10 1 14 1 0 14 1 0 0060 200 60 262 400 300...

Page 89: ...0 148 2 3 1 17 4 125 17 4 125 2 3 1 53 8 425 53 8 425 2 7 8 53 8 425 53 8 425 2 7 8 49 8 425 49 8 425 2 7 8 49 8 425 49 8 425 2 7 8 28 7 239 28 7 239 2 4 7 28 7 239 28 7 239 2 4 7 23 7 187 23 7 187 2...

Page 90: ...3 3 0 0134 200 60 317 400 350 400 350 400 4 500 250 500 250 500 230 60 294 400 350 350 350 350 4 500 250 500 250 500 380 60 171 200 200 200 200 200 10 3 0 6 350 6 350 460 60 141 200 175 175 175 175 1...

Page 91: ...00 80 8 500 80 8 500 4 7 8 46 6 305 46 6 305 46 6 305 4 4 7 38 5 250 38 5 250 38 5 250 4 4 0 30 8 198 30 8 198 30 8 198 4 3 1 87 2 500 87 2 500 87 2 500 4 7 8 80 8 500 80 8 500 80 8 500 4 7 8 46 6 305...

Page 92: ...or 2 3 0 500 460 60 188 250 200 225 200 225 10 300 1 6 350 575 60 150 200 175 175 175 175 10 3 0 1 6 350 0104 200 60 454 600 500 500 500 500 2 6 500 2 250 500 230 60 422 600 450 450 450 450 2 6 500 2...

Page 93: ...5 69 4 505 3 7 8 87 2 500 87 2 500 3 7 8 64 3 505 64 3 505 64 3 505 3 7 8 80 8 500 80 8 500 3 7 8 37 0 280 37 0 280 37 0 280 3 4 7 46 6 305 46 6 305 3 4 7 30 6 225 30 6 225 30 6 225 3 4 0 38 5 250 38...

Page 94: ...ply if Control Transformer not Supplied Flow Switch See electrical note 9 Figure 1 Single Point Supply Connection Terminal Block Non Fused Disconnect Switch or Circuit Breaker YCAL0043 0253 Power Pane...

Page 95: ...r Supply Field Provided 120 1 Micropanel Power Supply if Control Transformer not Supplied Flow Switch See electrical note 9 Figure 4 Single Point Supply Connection Terminal Block or Non Fused Disconne...

Page 96: ...JOHNSON CONTROLS 96 CTB1 21 13 20 13 14 13 FLOW SW REMOTE START STOP PWM INPUT LOAD LIMIT INPUT Factory wired with optional transformer Control Wiring...

Page 97: ...JOHNSON CONTROLS 97 FORM 150 62 EG1 507 INTENTIONALLY LEFT BLANK...

Page 98: ...for special installation requirements Roof installations should incorporate the use of spring type isolators to minimize the transmission of vibration into the building structure GROUND LEVEL INSTALL...

Page 99: ...arged with refrigerant and oil by the Manu facturer B Unit shall be stored and handled per Manufacturer s instructions PART 2 PRODUCTS 2 01 Chiller Materials And Components A General Install and commi...

Page 100: ...cessor Enclosure Rain and dust tight NEMA 3R 12 IP55 powder painted steel cabinet with hinged latched and gasket sealed door C Microprocessor Control Center 1 Automatic control of compressor start sto...

Page 101: ...d through liquid tight conduit 2 07 Accessories And Options Some accessories and options supercede standard product features Your YORK representative will be pleased to provide assistance A Microproce...

Page 102: ...reen internal components and prevent unauthorized access to internal components 4 Louvered Wire Panels Louvered steel panels on external condenser coil faces painted as per remainder of unit cabinet H...

Page 103: ...id temperature X Sound Reduction Factory mounted 1 Low speed reduced noise fans 2 Compressor Acoustic Sound Blankets Y Vibration Isolation Field mounted 1 Neoprene Pad Isolators 2 1 Inch Deflection Sp...

Page 104: ...Form 150 62 EG1 507 Supersedes 150 62 EG1 205...

Reviews: