JOHNSON CONTROLS
27
FORM 150.62-EG1 (507)
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YCAL0050EB
IPLV=13.7
YCAL0060EB
IPLV=14.5
YCAL0064EB
IPLV=13.7
YCAL0070EB
IPLV=13.8
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
105°F
110°F
115°F
120°F
125°F
TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER
40.0 41.7 67.3
6.9
40.2 71.2
6.3
29.2 51.4
6.1
20.2 35.3
5.9
19.4 37.4
5.4
42.0 43.4 67.7
7.1
41.8 71.7
6.5
30.2 52.1
6.3
21.0 35.6
6.1
20.1 37.7
5.6
44.0 45.0 68.2
7.3
32.6 49.5
7.1
31.4 52.4
6.5
21.9 35.7
6.3
21.0 37.8
5.8
45.0 45.9 68.5
7.4
33.2 49.7
7.2
32.0 52.5
6.6
22.3 35.8
6.5
21.4 37.9
5.9
46.0 46.7 68.7
7.5
33.9 49.8
7.3
32.7 52.7
6.7
22.7 35.9
6.6
21.9 38.0
6.0
48.0 48.4 69.3
7.8
35.2 50.1
7.6
34.0 53.0
7.0
23.7 36.1
6.8
22.8 38.2
6.2
50.0 50.2 69.9
8.0
36.5 50.5
7.8
35.3 53.3
7.2
24.6 36.2
7.1
23.7 38.3
6.5
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
105°F
110°F
115°F
120°F
125°F
TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER
40.0 46.7 69.7
7.4
45.1 73.9
6.8
43.5 78.3
6.2
22.4 37.3
6.3
21.5 39.6
5.7
42.0 48.5 70.2
7.7
46.8 74.4
7.0
45.2 78.8
6.4
23.3 37.5
6.5
22.4 39.7
5.9
44.0 50.1 71.2
7.8
48.4 75.4
7.2
46.7 79.9
6.5
24.3 37.6
6.7
23.4 39.9
6.2
45.0 51.0 71.4
8.0
49.3 75.6
7.3
25.7 35.5
7.5
24.8 37.7
6.9
23.8 39.9
6.3
46.0 51.9 71.7
8.1
50.2 75.9
7.4
26.2 35.6
7.6
25.3 37.7
7.0
24.3 40.0
6.4
48.0 53.9 72.1
8.3
52.1 76.4
7.6
27.3 35.7
7.9
26.3 37.9
7.3
25.3 40.2
6.6
50.0 55.8 72.6
8.6
54.0 76.9
7.9
28.3 35.8
8.2
27.3 38.0
7.5
26.3 40.3
6.9
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
105°F
110°F
115°F
120°F
125°F
TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER
40.0 50.9 82.5
6.8
49.1 87.3
6.3
39.8 72.7
6.0
32.0 60.1
5.7
30.7 63.8
5.2
42.0 52.9 83.1
7.1
51.1 87.9
6.5
41.4 73.1
6.2
33.3 60.4
5.9
32.0 64.1
5.4
44.0 55.0 83.8
7.3
53.1 88.6
6.7
43.1 73.5
6.4
34.6 61.0
6.1
33.3 64.4
5.6
45.0 56.0 84.1
7.4
54.1 88.9
6.8
43.9 73.7
6.5
35.3 61.2
6.2
34.0 64.6
5.7
46.0 57.1 84.4
7.5
55.1 89.3
6.9
44.8 74.0
6.7
36.0 61.3
6.3
34.7 64.8
5.8
48.0 59.2 85.1
7.7
57.2 90.0
7.1
46.5 74.4
6.9
37.5 61.7
6.6
36.1 65.2
6.0
50.0 61.4 85.8
8.0
59.3 90.8
7.3
48.3 74.9
7.1
39.0 62.0
6.8
37.5 65.5
6.2
AIR TEMPERATURE ON CONDENSER (°F)
LCWT
(°F)
105°F
110°F
115°F
120°F
125°F
TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER TONS KW
EER
40.0 56.8 90.3
7.0
54.7 95.4
6.4
52.7 100.6 5.9
35.7 65.6
5.9
34.2 69.2
5.4
42.0 59.0 90.9
7.3
56.9 96.1
6.6
54.8 101.4 6.1
37.1 66.1
6.1
35.7 69.7
5.6
44.0 61.3 91.5
7.5
59.1 96.8
6.9
40.2 62.9
6.9
38.7 66.5
6.3
36.9 70.9
5.7
45.0 62.5 91.9
7.6
60.3 97.1
7.0
41.0 63.1
7.0
39.4 66.7
6.4
37.6 71.1
5.8
46.0 63.7 92.2
7.7
61.4 97.5
7.1
41.8 63.3
7.1
40.2 67.0
6.5
38.4 71.3
5.9
48.0 66.1 93.0
7.9
63.8 98.3
7.3
43.2 64.2
7.3
41.6 67.9
6.7
40.0 71.7
6.1
50.0 68.5 93.8
8.2
66.2 99.1
7.5
45.0 64.5
7.6
43.3 68.2
6.9
41.7 72.1
6.3