York YCAL Series Start-Up Checklist Download Page 4

FORM 150.66-CL2 (820)

4

 

JOHNSON CONTROLS

 

4.  Put the unit into Service Mode and cycle each 

condenser fan to ensure proper rotation.

 5.

  Connect a manifold gauge to system 1 suction and 

discharge service valves.

     Place the Unit Switch in the control panel to the 

“ON” position. As each compressor cycles on, 

ensure that the discharge pressure rises and the 

suction pressure decreases. If this does not oc-

cur, the compressor being tested is operating in 

the reverse direction and must be corrected. After 

verifying proper compressor rotation, turn the Unit 

Switch to “OFF.”

The chilled liquid setpoint may need to 

be temporarily lowered to ensure all 

compressors cycle “ON.”

This unit uses scroll compressors 

which can only operate in one direc-

tion. Failure to observe this will lead 

to compressor failure.

The chilled liquid setpoint may need to 

be temporarily lowered to ensure all 

compressors cycle “ON”.

CHECKING SUPERHEAT AND SUBCOOLING

The subcooling temperature of each system can be cal-

culated by recording the temperature of the liquid line 

at the outlet of the condenser and subtracting it from 

the liquid line saturation temperature at the liquid stop 

valve (liquid line saturation temp. is converted from a 

temperature/pressure chart).

Example:

 

Liquid line pressure = 

  328 psig converted to temp.  102°F 

 

minus liquid line temp.  - 87°F

 

Subcooling =   15°F

The subcooling should be adjusted to 15°F at design 

conditions.

 1. 

Record the liquid line pressure and its correspond-

ing temperature, liquid line temperature and sub-

cooling below:

 

  

  

 SYS 1

 

Liq Line Press =  _______  psig

 

Saturated Temp =  _______  °F

 

Liq Line Temp =  _______  °F

 

Subcooling =  _______  °F

     OPTIONS

    Display Language

    Sys 1 Switch

    Chilled Liquid

  * Ambient Control

    Local/Remote Mode

    Control Mode

    Display Units

  * Lead/Lag Control

  * Fan Control

    Manual Override

    Current Feedback

  **  Soft Start

  **  Unit Type

  **  Refrigerant Type

  **  Expansion Valve Type

  COOLING SETPOINTS

    Cooling Setpoint

   Range

    EMS-PWM Max. Setpoint

     PROGRAM

    Discharge Pressure Cutout

    Suct. Pressure Cutout

    Low Amb. Temp. Cutout

    Leaving Liquid Temp. Cutout

    Anti-Recycle Time

    Fan Control On Pressure

    Fan Differential Off Pressure

    Total # of Compressors

  * Number of Fans/System

  * Unit/Sys Voltage

    Unit ID

  * Sys 1 Superheat Setpoint

TABLE 1 – SETPOINTS ENTRY LIST

  *  NOT ON ALL MODELS

  **  VIEWABLE ONLY