PSC BLOWER MOTOR BODY

HIGH

LOW

MEDIUM

B

LO

W

E

R

 S

P

E

E

D

 W

IR

E

Unit with Standard PSC Motor

Model

Motor 

Spd

Blower 

Size

Motor 

HP

Airflow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

012

H

6 x 8

 1/10

480

450

440

420

410

380

360

340

330

310

300

-

-

-

-

-

MH*

440

410

400

380

370

350

330

310

300

280

270

-

-

-

-

-

ML

395

370

360

340

330

310

290

280

270

250

240

-

-

-

-

-

L

325

310

300

280

270

250

240

230

220

210

200

-

-

-

-

-

018

H

9 x 7

 1/6

845

835

825

815

800

790

775

755

735

710

680

565

-

-

-

-

M

735

730

725

715

705

700

690

675

660

630

600

485

-

-

-

-

L

620

615

610

605

600

590

580

565

550

520

490

-

-

-

-

-

022

H

9 x 7

1/5

1110

1095

1080

1065

1045

1020

995

970

945

915

880

810

-

-

-

-

M

850

845

835

825

815

805

795

775

755

735

715

-

-

-

-

-

L

750

745

740

735

725

715

700

685

670

650

630

-

-

-

-

-

030

H

9 x 7

1/3

1290

1270

1245

1220

1190

1160

1125

1090

1055

1020

985

880

760

-

-

-

M

1100

1090

1075

1060

1045

1020

995

970

940

910

875

785

625

-

-

-

L

910

905

900

895

885

875

865

850

835

810

780

710

560

-

-

-

036

H

10 x 10

1/2

1665

1640

1610

1580

1550

1515

1480

1450

1415

1315

1215

1090

980

-

-

-

M

1465

1445

1425

1400

1375

1350

1325

1260

1190

1140

1090

990

890

-

-

-

L

1130

1115

1100

1090

1075

1035

995

965

930

895

860

795

730

-

-

-

042

H

10 x 10

1/2

2010

1975

1940

1905

1870

1825

1780

1735

1690

1640

1590

1470

1210

-

-

-

M

1670

1650

1630

1610

1590

1560

1530

1495

1460

1425

1390

1190

1080

-

-

-

L

1220

1215

1210

1295

1200

1180

1160

1130

1100

1060

1020

930

-

-

-

-

048

H

10 x 10

1/2

2010

1975

1940

1905

1870

1825

1780

1735

1690

1640

1590

1470

1210

-

-

-

M

1670

1650

1630

1610

1590

1560

1530

1495

1460

1425

1390

1190

1080

-

-

-

L

1220

1215

1210

1295

1200

1180

1160

1130

1100

1060

1020

930

-

-

-

-

060

H

11 x 10

1

2430

2400

2365

2330

2290

2255

2215

2180

2140

2095

2045

1945

1835

1715

1510

1330

M

2265

2235

2205

2175

2145

2110

2070

2035

2000

1960

1915

1825

1730

1605

1440

1260

L

2075

2050

2020

1995

1965

1940

1915

1885

1850

1820

1785

1720

1610

1505

1335

1175

070

H

11 x 10

1

2430

2400

2365

2330

2290

2255

2215

2180

2140

2095

2045

1945

1835

1715

1510

1330

M

2265

2235

2205

2175

2145

2110

2070

2035

2000

1960

1915

1825

1730

1605

1440

1260

L

2075

2050

2020

1995

1965

1940

1915

1885

1850

1820

1785

1720

1610

1505

1335

1175
2/7/12

Unit with Optional High Static PSC Motor

Model

Motor 

Spd

Blower 

Size

Motor 

HP

Airflow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

022

H

9 x 7

1/3

1290

1270

1245

1220

1190

1160

1125

1090

1055

1020

985

880

760

-

-

-

M

1100

1090

1075

1060

1045

1020

995

970

940

910

875

785

625

-

-

-

L

910

905

900

895

885

875

865

850

835

810

780

710

560

-

-

-

030

H

9 x 7

1/2

1365

1340

1325

1305

1280

1250

1215

1180

1140

1100

1055

960

850

-

-

-

M

1040

1040

1035

1030

1020

1005

990

970

945

915

885

810

735

-

-

-

L

880

880

880

880

875

870

860

840

820

800

775

730

480

-

-

-

036

H

10 x 10

1/2

1930

1905

1875

1840

1805

1765

1725

1680

1635

1530

1425

1270

1150

1025

-

-

M

1635

1620

1600

1580

1555

1530

1505

1465

1425

1335

1240

1135

1035

775

-

-

L

1230

1230

1225

1215

1200

1165

1130

1095

1060

1035

1005

935

795

675

-

-

042

H

10 x 10

3/4

2115

2075

2035

1980

1920

1900

1880

1840

1795

1730

1660

1390

1225

1070

-

-

M

2005

1980

1950

1910

1865

1815

1765

1725

1685

1585

1485

1315

1140

1025

-

-

L

1860

1835

1805

1780

1750

1715

1675

1635

1590

1540

1490

1260

1115

980

-

-

048

H

10 x 10

3/4

2115

2075

2035

1980

1920

1900

1880

1840

1795

1730

1660

1390

1225

1070

-

-

M

2005

1980

1950

1910

1865

1815

1765

1725

1685

1585

1485

1315

1140

1025

-

-

L

1860

1835

1805

1780

1750

1715

1675

1635

1590

1540

1490

1260

1115

980

-

-

Factory settings are in Bold

High-Static option not available for 012, 018, 060, and 070
Air flow values are with dry coil and standard filter
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).  
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by
0.16 in. wg.

1/25/12

Setting Blower Speed - PSC 

CAUTION: Disconnect all power before performing 
this operation.

Blower Performance Data cont.

AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL

Summary of Contents for YAFS018

Page 1: ...INAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www york geothermal com Additional rating information can found at www ahridi...

Page 2: ......

Page 3: ...ical Data 17 Blower Performance Data 19 Dimensional Data 24 Physical Data 28 The Aurora Control System 30 Reference Calculations and Legend 39 Wiring Schematics 40 Unit Startup 48 Operating Parameters...

Page 4: ...d ECM 4 5 Speed ECM Rev 04 27 2021 Notes 1 IntelliStart available 026 072 2 Symphony AWL not available YAF T 038 T L 1 4 1 C A 0 A 1 3 4 4 6 8 9 10 11 12 13 14 15 16 17 Model YAF Affinity Forced Air S...

Page 5: ...or service personnel to perform maintenance or repair Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a closet provisions must...

Page 6: ...tion could loosen a single nut To allow filter access one bracket on the filter side should be installed 180 from the position shown in Figure 3 The unit should be pitched approximately 1 4 inch towar...

Page 7: ...8 24 1 29 3 cm 209 3 70 6 61 2 74 4 072 in 99S500A03 82 4 27 8 24 1 29 3 cm 209 3 70 6 61 2 74 4 2 8 12 Weight Distribution Model Vertical Weight Horizontal Weight Horizontal Weight Distribution Front...

Page 8: ...maintaining the brass connector in the desired direction Tighten the connectors by hand then gently snug the fitting with pliers to provide a leak proof joint When connecting to an open loop ground wa...

Page 9: ...Threshold Velocity Fresh Water 6 ft sec 6 ft sec 6 ft sec NOTES Grains ppm divided by 17 mg L is equivalent to ppm 2 22 12 The heat exchangers and water lines in the units are copper or cupronickel t...

Page 10: ...rple Hot Water Limit Switch 130 F Blue 1 2 3 Cabinet HW Switch Field Supplied Relay for Heat Pump 1 Field Supplied Relay for Heat Pump 2 Heat Pump 1 Contactor Coil Heat Pump 2 Contactor Coil Field Sup...

Page 11: ...mmended to eliminate water hammer Figure 10 Open System Groundwater Application Open Loop Ground Water Systems Flexible Duct Collar Vibration Absorbing Pad P T Plugs Drain Desuperheater Connections Au...

Page 12: ...l units with hot water generators contain an internal circulator and fittings A water softener is recommended with hard water greater than 10 grains or 170 total hardness NOTES 1 Using a preheat tank...

Page 13: ...open until water dribbles out then replace Allow the pump to run for at least five minutes to ensure that water has filled the circulator properly Be sure the switch for the hot water generator pump s...

Page 14: ...electronic air cleaners humidifiers etc This relay contact should be used only with 24 volt signals and not line voltage power The relay has both normally open and normally closed contacts and can ope...

Page 15: ...r 4 or 5 counductor for communicating thermostats 20 AWG minimum wire Strip the wires back 1 4 inch longer strip lengths may cause shorts and insert the thermostat wires into the connector as shown Ti...

Page 16: ...3 3 60 0 60 60 60 60 60 60 L3 L4 34 7 40 0 43 3 50 0 45 50 45 50 40 50 All heaters rated single phase 60 cycle and include unit blower load All fuses type D time delay or HACR circuit breaker in USA S...

Page 17: ...87 253 26 0 16 6 79 0 28 0 0 4 5 4 7 6 30 0 34 2 50 048 208 230 60 1 187 253 31 0 19 8 109 0 38 0 0 4 5 4 7 6 33 2 38 2 50 060 208 230 60 1 187 253 41 2 26 4 134 0 47 0 0 4 5 4 7 6 39 8 46 4 70 070 20...

Page 18: ...optional 1 hp variable speed ECM motor With optional IntelliStart Rated voltage of 208 230 60 1 All fuses Class RK 5 HACR circuit breaker in USA only Dual Capacity Unit with 5 Speed ECM Motor Model Ra...

Page 19: ...iary heat package G may be located anywhere within the airflow table Cfm is controlled within 5 up to the maximum ESP Max ESP includes allowance for wet coil and standard filter 6 8 12 Dual Capacity U...

Page 20: ...y at the Aurora ABC board which utilizes the push button SW1 on the ABC board This procedure is outlined in the ECM Configuration Mode portion of the Aurora Base Control System section The Aux cannot...

Page 21: ...830 Low 1 G 1243 1182 1121 1061 1000 964 928 856 784 744 703 647 592 042 High 5 11 x 10 1 1934 1910 1886 1871 1855 1827 1799 1780 1760 1747 1734 1700 1659 1617 Med High 4 W 1799 1783 1767 1744 1720 16...

Page 22: ...gh 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 Med 3 Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 Med Low 2 Y1 1575 1560 1540 1520 1502 1487 147...

Page 23: ...2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330 M 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1...

Page 24: ...9 10 6 1 in Swivel 1 2 in Female 9 5 12 1 14 3 6 9 1 1 18 0 18 0 3 8 1 7 28 1 26 0 1 7 cm 65 0 80 3 128 0 5 8 18 5 40 4 48 0 26 9 24 1 30 7 36 3 17 5 2 8 45 7 45 7 9 7 4 3 71 4 66 0 4 3 042 049 in 25...

Page 25: ...Swivel 1 2 in Female 48 9 50 8 52 2 9 1 4 8 13 4 13 6 1 5 1 8 28 1 34 0 5 6 cm 64 8 80 0 158 8 110 2 122 9 144 8 152 4 9 1 124 2 129 0 132 6 23 1 12 2 34 0 34 5 3 8 4 6 71 4 86 4 14 2 Condensate is 3...

Page 26: ...3 15 9 18 9 10 6 1 Swivel 1 2 female 9 5 12 1 14 3 13 3 13 6 43 4 9 1 8 1 1 7 28 1 34 0 1 7 cm 65 0 80 3 148 3 5 8 18 5 40 4 48 0 26 9 24 1 30 7 36 3 33 8 34 5 110 2 23 1 20 6 4 3 71 4 86 4 4 3 Conden...

Page 27: ...8 26 7 23 9 14 7 7 1 77 5 42 9 3 3 036 038 in 25 6 72 0 21 3 2 3 7 3 15 9 18 9 0 8 1 in Swivel 1 2 in Female 9 5 12 1 14 3 SEE CHART 13 6 13 2 SEE CHART 2 8 35 5 18 9 1 3 cm 65 0 182 9 54 1 5 8 18 5 4...

Page 28: ...n mm n a 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 0 35 1 3 0 40 1 5 0 7 2 6 1 0 3 8 1 3 4 9 1 3 4 9 1 6 6 1 1 6 6 1 2 3 8 7 Vertical Air C...

Page 29: ...le Sweat I D in mm 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 0 7 2 6 1 3 4 9 1 6 6 1 1 6 6 1 2 3 8 7 Vertical Air Coil Dimensions H x W in mm 24 x 20 610 x 542 28 x 2...

Page 30: ...TStat inputs IntelliZone2 communicates to the heat pump via the AXB board With Optional AXB kit and IntelliZone2 Optional IntelliZone2 IntelliZone2 24V Compatibility Communicates to the heat pump via...

Page 31: ...t Elite Stat with full English fault codes and alerts communicating thermostat Monochrome thermostat allows instantaneous energy measurement only Optional Optional TPCC32U01YRK Color Touchscreen Commu...

Page 32: ...nd off Additionally when entering test mode LED1 red will flash the last lockout one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1...

Page 33: ...The Alarm output ALM and Lockout output L will be turned on The fault type identification display LED1 Red shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2...

Page 34: ...If there are no other commands from the thermostat the ECM will run on G speed until the G command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds...

Page 35: ...h not required for ECM airflow settings The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs displ...

Page 36: ...hen the DHW limit is reached and when conditions are not favorable for water heating Error code 15 will also be displayed on the AID Tool in the fault screen This flash code is a noncritical alert and...

Page 37: ...sensor Smoke CO Alarm Fault no lockout info only Switch output from Smoke CO sensor Dirty Filter Alarm no lockout info only Output from dirty filter sensor Monitoring Sensor Kits Energy Monitoring St...

Page 38: ...LED LED2 Yellow Description of Operation Configuration LED Yellow No Software Overwritten ECM Setting DIP Switch Overwritten Slow Flash ECM Configuration Mode Fast Flash Reset Configuration Mode OFF...

Page 39: ...nheit dry bulb wet bulb HC air heating capacity MBtu h TC total cooling capacity MBtu h SC sensible cooling capacity MBtu h kW total power unit input kilowatts HR total heat of rejection MBtu h HE tot...

Page 40: ...t Output Future Use Smart Grid Home Automation Dehumidification Output Analog Output 0 10VDC NOTE 5 NOTE 6 P8 MOTOR P6 RS485 P7 ZONE P9 ABC STEPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2...

Page 41: ...rce power is required 3 When Auxiliary Heat is installed the BLK WHT wire from CC L1 to PB2 2 and the GRY WHT wire from CC L2 to PB2 1 must be removed located in the heat pump control box 1 Use copper...

Page 42: ...Under Voltage Shutdown Flash Code 8 Future Use Flash Code 3 Future Use Flash Code 4 Load Shed Flash Code 5 OFF Input Fault Lockout Flash Code 1 Freeze Detection FP1 Flash Code 5 Flash Code 2 Low Pres...

Page 43: ...arness will then be connected to the auxiliary heat unit The auxiliary heat unit will then power the blower Refer to EAS EAM EAL Auxiliary Heat kit installation instructions 1 Switch blue and red wire...

Page 44: ...utput Analog Output 0 10VDC Future Use Home Automation Smart Grid NOTE 7 NOTE 8 P8 MOTOR P6 RS485 P7 ZONE P9 ABC STEPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R...

Page 45: ...ory Installed and are Required for auxiliary heat operation 1 Use copper or aluminum conductors 2 When Auxiliary Heat is installed the BLK WHT wire from CC L1 to PB2 2 and the GRY WHT wire from CC L2...

Page 46: ...Code 5 Flash Code 2 Low Pressure Lockout Flash Code 3 Freeze Detection FP2 Flash Code 4 High Pressure Lockout Dehumidification Mode Flash Code 2 DIP Switch Overide Slow Flash Status LED LED 3 Green N...

Page 47: ...G G Y R SW1 Test FP1 15oF 30oF JW2 Alarm P11 P5 P2 P1 P8 P7 P9 P6 P3 SW2 P13 P4 FP2 15oF 30oF RV B O ACC Dip 4 ACC Dip 5 CC Dual Single L Pulse Continuous Reheat Normal Factory Use Field Connections...

Page 48: ...lenoid see Open Loop Groundwater Systems section T Black FP2 Black CFM P13 P4 SW1 P5 JW2 P9 LO O B Y2 W DH P8 P7 RS485 NET RS485 NET P6 RS485 EXP P3 SW2 On Future Use L Output Type CC Dual Single Acc...

Page 49: ...P Switch Overide Slow Flash Fault LED LED1 Red Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Future Use Freeze Detection FP1 Reserved Condensate Overflow Lockout Over Unde...

Page 50: ...Internal Hot Water Generation Pump 1 5A 5A DHW Pump Purple Hot Water Limit Switch 130 F Blue 1 2 3 Blue Traditional Thermostat Communicating Thermostat AID Tool Water Solenoid see Open Loop Groundwat...

Page 51: ...re Overide OFF DIP Switch Overide Slow Flash Fault LED LED1 Red Normal Mode Input Fault Lockout High Pressure Lockout Low Pressure Lockout Future Use Freeze Detection FP1 Reserved Condensate Overflow...

Page 52: ...anced controls Confirm IntelliZone2 if installed is added and communicating Set Zoning system to off mode 2 Aurora Setup Screen a ECM Setup for Heating Airflow select G low high and aux blower speeds...

Page 53: ...ntaneous information only ii TPCM32U04AYRK Communicating Thermostat B W instantaneous information only iii TPCC32U01YRK Color Touchscreen Thermostat Both Instantaneously and historical 13 months Refri...

Page 54: ...e unit in the cooling mode Cooling setpoint must be set below room temperature 3 First stage cooling will energize after a time delay 4 Be sure that the compressor and water control valve or loop pump...

Page 55: ...B 67 F WB Heating performance based on entering air temperature of 70 F DB 2 15 12 Second Stage Operation Entering Water Temp F Water Flow gpm ton Cooling No Hot Water Generation Suction Pressure psig...

Page 56: ...Drop psi 30 F 50 F 70 F 90 F 110 F 026 full load 4 1 4 1 3 1 2 1 1 1 0 6 2 8 2 6 2 4 2 3 2 1 8 4 7 4 4 4 1 3 8 3 5 10 7 0 6 6 6 2 5 8 5 3 026 part load 3 0 8 0 7 0 7 0 7 0 6 5 2 0 1 8 1 7 1 6 1 5 7 3...

Page 57: ...lves Low High Low High Normal High Low Low TXV Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exchanger...

Page 58: ...2 0 53 1 68 7 83 7 89 6 90 6 85 2 15 0 42 1 56 8 71 6 85 0 80 8 90 0 91 0 85 4 81 9 18 0 42 6 57 9 73 9 88 6 81 4 90 6 91 6 85 9 82 2 Note operation not recommended in shaded areas 11 26 2014 Single S...

Page 59: ...rcuit Aurora Control System NOTE Refer to the Aurora Base Control Application and Troubleshooting Guide and the Instruction Guide Aurora Interface and Diagnostics AID Tool for additional information T...

Page 60: ...rge Pressure Transducer Air Coil Blower Leaving Air Thermistor Wire Bundle In Blower Compartment Coax Flow Meter Water OUT Water IN Flow Sensor Entering Water Thermistor Leaving Water Thermistor Water...

Page 61: ...sed COAX SOURCE HEA7 1 ANALYSIS EXPANSION VALVE F AIR COIL F COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE Line Voltage Loop Open Unit Amp Dra...

Page 62: ...Total Amps Comp Blower 3 n Amps n Amps Watts m x n x 0 85 o Watts o Watts 7 Capacity HEATING COOLING Cooling Capacity l o x 3 413 p Btu h p Btu h Heating Capacity l o x 3 413 8 Efficiency HEATING COOL...

Page 63: ...ion of the malfunctions and a description of the replacement parts required CAUTION Fin edges are sharp Preventive Maintenance Replacement Procedures Other Maintenance Filters Filters must be clean to...

Page 64: ...4P501A01 24P501A01 24P501A01 24P501A01 24P501A01 Electrical Contactor 13P004A03 13P004A03 13P004A03 13P004A03 13P004A03 13P004A03 13P004A03 13P004A03 13P004A03 Transformer 208 230 60 1 15P501B01 15P50...

Page 65: ...24P501A01 24P501A01 24P501A01 24P501A01 Electrical Contactor 13P004A03 13P004A03 13P004A03 13P004A03 13P004A03 Transformer 208 230 60 1 15P501B01 15P501B01 15P501B01 15P501B01 15P501B01 3 Pole Power...

Page 66: ...66 Notes AFFINITY AFFINITY ADVANCED SINGLE DUAL CAPACITY SERIES INSTALLATION MANUAL...

Page 67: ...CAPACITY SERIES INSTALLATION MANUAL Pages Description Date By 4 Nomenclature Update 27 May 2021 MA All Released Aluminum Air Coil Option 1 Sept 2015 MA All Wiring Schematics Updated Electric Heating U...

Page 68: ...cifications without notice Product Affinity Affinity Advanced Series Type Geothermal Water Source Heat Pump Size 1 1 5 Ton Single Speed 2 6 Ton Dual Capacity Document Type Installation Manual Part Num...

Reviews: