251933-YTG-J-1009
Johnson Controls Unitary Products
71
060
(5.0)
208-1-60 26.2 134.0
41.0
2.3
7.6
0.0
None
-
-
-
42.7
60
E05
4.0
1
19.2
66.7
80
E07
5.6
1
26.9
76.3
90
E10
8.0
1
38.5
90.7
100
E15
11.9
2
57.2
114.2
125
E20
15.9
2
76.4
138.2
150
E30
22.2
2
106.7
176.1
200
230-1-60 26.2 134.0
41.0
2.3
7.6
0.0
None
-
-
-
42.7
60
E05
5.3
1
23.0
70.3
90
E07
7.5
1
32.6
81.7
100
E10
10.6
1
46.1
97.9
110
E15
15.9
2
69.1
125.5
150
E20
21.2
2
92.2
153.1
175
E30
29.6
2
128.7
196.8
200
208-3-60 15.6 110.0
24.4
2.3
5.2
0.0
None
-
-
-
27.0
35
E05
4.0
1
11.1
40.9
50
E07
5.6
1
15.5
46.4
50
E10
8.0
1
22.2
54.8
60
E15
11.9
2
33.0
68.3
70
E20
15.9
2
44.1
82.2
90
E30
22.2
2
61.6
104.0
110
230-3-60 15.6 110.0
24.4
2.3
5.2
0.0
None
-
-
-
27.0
35
E05
5.3
1
13.3
42.9
50
E07
7.5
1
18.8
49.6
60
E10
10.6
1
26.6
58.9
60
E15
15.9
2
39.9
74.8
80
E20
21.2
2
53.2
90.7
100
E30
29.6
2
74.3
116.0
125
460-3-60
7.7
52.0
12.1
1.3
2.6
0.0
None
-
-
-
13.5
20
E07
6.8
1
8.5
23.7
25
E10
10.1
1
12.7
28.7
30
E15
13.6
2
17.1
34.0
35
E20
19.5
2
24.5
42.8
45
E30
28.8
2
36.1
56.8
60
575-3-60
5.8
38.9
9.1
1.3
2.0
0.0
None
-
-
-
10.3
15
E10
10.6
1
10.6
23.0
25
E15
15.9
1
16.0
29.4
30
E20
21.2
2
21.3
35.8
40
E30
30.4
2
30.5
46.9
50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP036-060 (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps