![background image](http://html1.mh-extra.com/html/york/xp-series-w-simplicity/xp-series-w-simplicity_installation-manual_3516582020.webp)
5168273-YIM-A-1115
20
Johnson Controls Unitary Products
XP180/240 - High Static Drive With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
180
(15)
208-3-60 25
164
39
4.1
20
10
NONE
-
-
-
94.5
110
E18
13.5
1
37.5
141.3
150
E36
27
2
74.9
141.3
150
E54
40.6
2
112.7
178.4
200
E72
54.1
2
150.2
188.1
200
230-3-60 25
164
39
3.9
19.4
10
NONE
-
-
-
93.5
110
E18
18
1
43.3
147.6
150
E36
36
2
86.6
147.6
150
E54
54
2
129.9
166.7
175
E72
72
2
173.2
210
225
460-3-60 12.2
100
19
2.15
9.7
5
NONE
-
-
-
46.5
50
E18
18
1
21.7
73.5
80
E36
36
2
43.3
73.5
80
E54
54
2
65
83.3
90
E72
72
2
86.6
105
110
575-3-60
9
78
14
1.6
7.8
4
NONE
-
-
-
35.3
40
E18
18
1
17.3
56.9
60
E36
36
2
34.6
58.1
60
E54
54
2
52
66.7
70
E72
72
2
69.3
84
90
240
(20)
208-3-60 34.3
239
52
3.5
26
10
NONE
-
-
-
127.2
150
E18
13.5
1
37.5
174
175
E36
27
2
74.9
174
175
E54
40.6
2
112.7
185.9
200
E72
54.1
2
150.2
220.9
225
230-3-60 34.3
239
52
3.5
25
10
NONE
-
-
-
126.2
150
E18
18
1
43.3
180.3
200
E36
36
2
86.6
180.3
200
E54
54
2
129.9
180.3
200
E72
72
2
173.2
234.4
250
460-3-60 17.9
125
28
1.9
12.5
5
NONE
-
-
-
65.4
80
E18
18
1
21.7
92.4
100
E36
36
2
43.3
92.4
100
E54
54
2
65
92.4
100
E72
72
2
86.6
119.5
125
575-3-60 12.8
80
20
1.5
10
4
NONE
-
-
-
48.8
60
E18
18
1
17.3
70.5
80
E36
36
2
34.6
70.5
80
E54
54
2
52
70.5
80
E72
72
2
69.3
92.1
100